ActronAir EVA290T User manual

Model Numbers
EVA290T
EVA330T
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air conditioning unit.
That’s better. That’s Actron.
Variable Capacity Commercial
Split Ducted Units
Installation and Commissioning Guide - Indoor

2Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
Table of Contents
01. Introduction....................................................................................................................................3
. Information About This Guide
. Product Inspections
. Codes, Regulations and Standards
. Important Safety Symbols And Labels
02. Safety Instructions.......................................................................................................................... 4
03. Components Overview....................................................................................................................5
. Indoor Unit Components Overview
. Electrical Control Panel Overview
04. Unit Dimensions and Clearances......................................................................................................6
. EVAT / EVAT
05. Installation Instructions...................................................................................................................7
06. Unit Lifting Procedures....................................................................................................................8
. Crane Lifting Method
. Fork Lift Method
07. Condensate Drain.......................................................................................................................... 10
08. Electrical Installation ......................................................................................................................11
09. Wiring Diagram ............................................................................................................................. 12
10. Split Unit Electrical Connection .....................................................................................................13
11. Maximum Cable Lengths ................................................................................................................15
. Wall Controller Options
. Wiring Configuration : Recommended
. Alternate Wiring Configuration
12. Wiring Connections....................................................................................................................... 18
. LC- Wall Control Wiring Connections
. NEO Wall Control Wiring Connections
. LM-RS- Optional Sensor Wiring Connections
. AERSS Optional Duct Sensor Wiring Connections
13. EC Indoor Fan Commissioning .......................................................................................................20
14. Maintenance Frequency Checklist ................................................................................................. 21

Installation and Commissioning Guide Variable Capacity Commercial
3
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Introduction
CONGRATULATIONS on your purchase of an ActronAir Variable Capacity Commercial Series air conditioning unit. This
unit has been designed and engineered to provide optimum air conditioning and to achieve maximum energy efficiency.
Your air conditioning system has been manufactured from the highest quality materials. Numerous “in house” and
“external” test procedures were conducted to ensure satisfactory operation.
. Information About This Guide
This guide provides installation instructions, specific to your split ducted indoor unit. Read this manual thoroughly and
take into consideration all specifications and instructions to ensure correct installation and safe operation of your air
conditioning system.
IMPORTANT
Keep this document for future reference. Ensure all technicians that work on the unit can refer to this manual at any time.
. Product Inspections
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit,
components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer
Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.
Check the unit nameplate to verify the model, serial number and electrical rated specifications are correct.
. Codes, Regulations and Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant council,
state / federal codes, regulations and building code standards. All electrical wiring must be in accordance with current
electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.
. Important Safety Symbols And Labels
Safety Symbols and labels appear at appropriate sections throughout this manual to indicate immediate or potential
hazards. Pay full attention and comply to the safety information and instructions. Failure to follow safety instructions
increases the risks of personal injury, death and/or property damage. Damages to the product as a result of such failure
may void warranty.
ActronAir has endeavoured to provide sufficient safety warnings and recommendations, however current and prevailing
WH&S regulations must be observed and will take precedent whenever performing the installation instructions discussed
in this manual.

4Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Safety Instructions
●Only licensed HVAC technicians* should install and service this air conditioning equipment. Improper service or
alteration by an unqualified technician could result in significant and major damage to the product or property which
may render your warranty null and void. Such unqualified service could also lead to severe physical injury or death.
Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
●Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on
this manual. Safe work practices and environment must be the paramount importance in the performance of all the
service procedures.
●Ensure that unit installation complies with relevant council regulations and building code standards.
●All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to
be as per electrical diagram provided.
●Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury.
●Always wear appropriate PPE, remove any dangling jewelery and protect long hair by wearing a cap.
●Make sure that all panel covers are always firmly secured and not damaged before and during operation of unit.
●This appliance is not intended for use by young children or infirm persons unless they have been adequately
supervised by a responsible person to ensure that they can use the appliance safely. Young children should be
supervised to ensure that they do not play with the appliance.
●Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance
with the latest edition of the AS/NZS 3000 (also known as Australian Wiring Rules).
●Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
*Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training
dependent on local State/Territory regulations.
NOTES
• This indoor unit is designed to match only with a specific ActronAir outdoor unit as specified in the Technical Selection
Catalogue.
• This unit is designed for use with R-410A refrigerant only.
• The unit is supplied with factory charged dry air. Beware of the pressurised air charge when purging. Remove the caps
from the connection points and purge the system only when the field pipe connections are ready to be completed.
DANGER
Hazardous Voltage - Risk of Electrocution.
TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/
TAG-OUT (LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.
WARNING
EC Motors are fitted with high power capacitors and can have dangerous residual voltages at motor terminals after power
has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning service
work.
VISUAL INSPECTION AND WORK ASSESSMENT
Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important
to be familiar with the unit parts and components before proceeding with any service task.

Installation and Commissioning Guide Variable Capacity Commercial
5
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Components Overview
. Indoor Unit Components Overview
EC MOTOR
AND MODULE
FANS
COIL
LID ELECTRICAL
CONTROL PANEL
ELECTRICAL
CONTROL PANEL
. Electrical Control Panel Overview
SWITCH MODE
POWER SUPPLY
CONTROL BOARD
EMC FILTERS

6Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Unit Dimensions and Clearances
. EVAT / EVAT
OVERALL NOMINAL DIMENSION (H x W x D)
= 628 x 1754 x 820
SUPPLY DUCT (H x W) = 282 x 1098
RETURN DUCT = 533 x 1451
DRAIN CONNECTION = DN 25mm PN12
INDOOR COIL
GAS PIPES
Ø 28.58 mm (1-1/8")
SWAGED
LIQUID PIPE
Ø 15.88 mm (5/8")
SWAGED
INDOOR
FAN
PRIMARY DRAIN
DN 25mm PN12
SUPPLY
AIR
628 O/A
131
282
246
100
49 722 49
38
533
57
288 1098 288
820 O/A
93
1754 O/A
1451 130
INDOOR
FAN
ERQ290T-330T-B
TOP VIEW
FRONT VIEW SIDE VIEW
Unit Model Number Unit Weight (kg)
EVA290T 122
EVA330T 126
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless specified.
2. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between
the unit and the outside perimeter is
available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
THIRD ANGLE
PROJECTION
INDOOR COIL
INDOOR
FAN
INDOOR
FAN
ERQ290T-330T-B- Front
DUCT WORK
DUCT WORK
HEIGHT CLEARANCE = DUCT WORK
1200 mm
INDOOR FAN
AND
INDOOR COIL
SERVICE CLEARANCE
TOP VIEW
1200 mm
INDOOR FAN / COIL
AND
ELECTRICAL CONTROL
SERVICE CLEARANCE
Minimum Service Access Areas and Airflow Clearances

Installation and Commissioning Guide Variable Capacity Commercial
7
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Installation Instructions
The installation instructions provided below are intended as a guide only and do not supersede the relevant council,
state and federal codes, regulations and building code standards. Compliance and consultation with the authorities
having jurisdiction with the installation of this equipment is the responsibility of the installer. ActronAir will not be held
liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit
Installation and Commissioning Guide for further information and details.
Lifting the Unit
The installation instructions provided, in Section 06, adhere to WH&S regulations for safe and secure lifting practices in
order to prevent physical injury.
Suggested lifting procedures are outlined in Section 06 as a reference guide to safely lift and transport the unit, however,
this does not over rule the industry WH&S practices.
Location
This unit is intended for indoor installation only. It is highly recommended that this indoor unit and accessories, be
mounted in the roof cavity.
Mount the unit in a stable and rigid support wherein the weight is properly distributed, such as roof joist and rafters. Take
into consideration the minimum service access clearances provided in the unit drawings.
Locate the indoor unit away from the areas where noise is a critical factor. Use rubber mounting pad (not supplied) in
order to minimize the transfer of noise and vibration into building structures.
A hanging bracket assembly and rubber grommet (optional on other units) are also provided to secure the indoor unit
into the roof rafters. This configuration is most suitable for installations that require the unit to be rigidly secured up from
the roof joist.
Condensate Drain
A drain kit (not supplied) is required for the condensate drain to be externally trapped from the indoor unit. Suggested
condensate drainage instructions are provided in Section 07 of this document for your reference.
ActronAir recommends the installation of a condensate safety tray and drain (not supplied).
Supply Air and Return Air Duct
The indoor unit is supplied with a duct flange as standard in order to facilitate the system’s duct connection into the unit.
Supply and return air duct work must be adequately sized to meet the system’s air flow and static pressure requirements.
Refer to the unit drawing for supply air and return air duct dimensions, specific to your requirement.
NOTE
Fit a flexible duct connection in between the unit and the duct system, where noise and vibration is a critical consideration.
Return Air Filter
Return Air filters must be provided in the return air side of the unit to maintain the efficiency and prolong the operation
of the unit. These are also paramount to satisfy the requirement for a clean and hygienic room condition. Return Air
filters must be placed in an easily accessible location for service and maintenance.
NOTES
• Return Air filters are not supplied with the unit as individual air filtration requirements vary.
• Ensure that filters are cleaned / replaced regularly.

8Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
Field Pipe Connection
Specifications and installation requirements for field pipe connections are contained in the Installation and
Commissioning Guide of the outdoor unit that matches your indoor unit. Please refer to this guide and thoroughly
understand the procedures for safe and correct indoor and outdoor connection. Field pipes must be insulated.
Electrical Field Connection
The power supply and control communication data to the indoor unit are supplied via the outdoor unit. Please refer to
the wiring diagram supplied with the outdoor unit for specifications.
All electrical work must be performed by a licensed electrician and must conform with the wiring diagram and all
relevant electrical authorities.
. Unit Lifting Procedures
. Crane Lifting Method
WARNING
WH&S regulations must be observed and will take precedence during lifting process.
DANGER
Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent
potential damage to property, severe personal injury or death. Please check unit weight and weight distribution points on
unit drawing dimensions section.
NOTES
• Crane lifting method is recommended for high rise lifting.
• Refer to catalogue for unit weight before selecting shackles and slings.
• Lifting procedure and unit model shown are suggestions and for illustration purposes only.
• It is highly recommended that installer observe current industry safe and sound rigging and lifting procedure.
FIG. 1
Connect the loop ends of
slings into shackle
DETAIL A
Slip nylon slings
through the pallet
INDOOR UNIT
PALLET
A
Provide rubber pads
to prevent damage to
the unit

Installation and Commissioning Guide Variable Capacity Commercial
9
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
EQUIPMENT REQUIRED FOR CRANE LIFTING:
●1 x shackle
●2 x nylon slings
●4 x rubber pads
Procedure:
1. Slip nylon slings through the pallet as shown in Fig. 1.
2. Use a Bow or Dee shackle to connect the slings.
3. Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles .
This will prevent the unit from being damaged during lifting.
4. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location.
. Fork Lift Method
FIG. 2
Insert forklift
tines here
DO NOT LIFT UNIT from this end in order to
prevent damage to electrical panel and pipes.
CAUTION
ELECTRICAL
PANEL END
Procedure:
1. To move the unit around with a forklift, insert the fork tines through the pallet, as shown in Fig. 2.
2. Do not lift the unit through the electrical panel end of the unit (See illustration for location of electrical panel end).
CAUTION
Length of fork lift tines must pass the unit middle section, in order to safely carry the unit.
Pallet fork lifting hole dimensions
All dimensions in mm. 860
100
100
35
35
100
850
850

10 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Condensate Drain
NOTES
• Parts of condensate trap are not supplied with the unit.
• Ensure that safety condensate drain (not supplied) is run separately from main condensate drain.
Ensure Drain Pipe slopes
down from the unit at a
minimum of 10 mm per metre
DETAIL A
(Suggested trap details)
The top of the Trap must
be 125mm below the top
of the Evaporator Drain
Connection
50 mm
4 x PVC
Elbow
Install a T-Piece
as an Air Vent
for long drain runs
Hose
Clamps
Evaporator
Condensate Tray
The top of the Vent must be
50 mm higher than the top of
the Evaporator Condensate Tray
250 mm or high enough to
maintain positive Air Seal
Condensate Drain
Connection
DN 25mm PN12
Trap
Clear Plastic
Inspection Tube
125mm
TOP VIEW
INTERNAL CONDENSATE TRAY
INDOOR
FAN
INDOOR
FAN
INDOOR COIL
Condensate Drain
Connection
Ensure Drain Pipe slope down
from the unit at a minimum of
10 mm per metre
Provide a minimum slope
of 10 mm per metre
FRONT VIEW
SUPPLY
AIR
A

Installation and Commissioning Guide Variable Capacity Commercial
11
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Electrical Installation
All electrical work must be carried out by a qualified and licensed technician. Make sure all wiring is in accordance with
local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided.
DANGER
Live Electrical Supply !
• During installation of your air conditioning unit, it may be necessary to work in close proximity to live electricity. Only
licensed electricians are allowed to perform these tasks.
• Follow all electrical safety precautions when exposed to live electrical components.
• Always make sure that all power supply, including remote controls, are disconnected before performing maintenance.
• Observe proper LOCK-OUT / TAG-OUT (LOTO) procedures to ensure that power cannot be inadvertently energised.
• Failure to disconnect power before maintenance procedure can result in serious injury or death.
• All electrical wiring must be in accordance with the relevant electrical authority rules and regulations.
Wiring Diagram
The wiring diagram specific for your air conditioning system is located on the inside panel of the control access door.
Always refer all wiring installation, servicing and troubleshooting of this equipment to this diagram to ensure correct
electrical connection are satisfied.
Supply and Power Requirements Procedure
It is the installer’s responsibility to provide power supply wiring to the mains supply terminal strip of the outdoor unit.
Make sure all wiring are in accordance with local wiring rules. Wiring should conform to all current electrical authority
regulations and all wiring connections to be as per electrical diagram provided with the unit.
●Confirm that the power supply available is compatible with the unit nameplate ratings. The supply power must be
within +10% to -6% of the rated voltage as per AS60038.
●Protect electrical service from over current and short circuit conditions in accordance with the latest edition of the
AS/NZS 3000 “Australian / New Zealand Wiring Rules”. Size protection devices according to the electrical data of the
unit.
●Installer to connect an appropriate load break (AC3) isolator in sub-mains wiring.
●Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
●Provide proper unit earthing in accordance with local and national codes.

12 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Wiring Diagram
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
RR
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
Revision Revision
Description: Description:
CC
WD2102 WD2102
A5 A5
Size: Size:
INDOOR EVAPORATOR WIRING DIAGRAM WITH
CMI INDOOR CONTROL BOARD & EC INDOOR FAN
INDOOR EVAPORATOR WIRING DIAGRAM WITH
CMI INDOOR CONTROL BOARD & EC INDOOR FAN
Base
Model No:
Base
Model No:
Variation: Variation:
EVA290/330T EVA290/330T
Variation Code: Variation Code:
Drawing No: Drawing No:
Drawn: Drawn:
Date: Date:
30-01-2019 30-01-2019
RL RL
Approved: Approved:
JL JL
Date: Date:
01-06-2020 01-06-2020
Rev. Rev.
Description Description
Date Date
By
RL
By
PCR
3280
PCR
ORIGINAL
CHANGED WC WIRING COLOUR REFERENCE & REMOVED WC-3 & ADDED TWC-1
ORIGINAL
B
C
B
FIELD WIRING
IF-1
1 EC
IF-2
1 EC
ECM
CONTROL
MODULE
ECM
CONTROL
MODULE
FERRITE
FERRITE
ECM-2 ECM-1
EE
N
N
A
A
NN
AA
LINE 1
NEUTRAL
LINE 2
LINE 3
EAR TH
OPTIONAL
FILTER INDICATION
RELAYOUTPUT
(240V 10A MAX)
INPUT VOLTAGE
N/C OUTPUT
+12V
OUTPUT
COM
0-10V
OUTPUT
0-10V
INPUT
COM
COM
N/O OUTPUT
INDOOR
COIL
TEMP
SENSOR
SMPS
240V AC
NEUT
30 W
+12VDC
0VDC
SHIELD
WIRE
CMI
POT
ADJUST
AMB
SENSOR
FILTER
IND ICAT IO N
PWM
FAN1 OUT
PWM
FAN2 OUT
FAN IN WALL CONT ROLLER OUTDOOR
485 FAN
AUX SENSOR
ECON OUTAUX OUT AUX IN
+12V
0-10V
+12V
COM
COM
AA
A
S1
0-10V
0-10V
BB
B
COM
COM
COM
GG
G
S2
COIL
T E MP
DISPLAY
PWR
0-10V
0-10V
0-10V
FAN2 OUT
0-10V
FAN1 OUT
COM
COM
NC NO
COM
COM 1 COM 2
COM 3 +12VDC
POWER IN
V+
V-
ZONE
MASTER SECONDARY
OFF
ON
PWM FAN OUT PUT
0-1 0V FAN INP UT S
INT ERNAL FAN SPEED
12 345678
STANDARD DIP
SWITCH SETTINGS
MANUAL FAN SPEED
POT AD JUST
OPTIONAL
FAN RUN
INDICATION
OUTPUT
OPTIONAL
OUTSIDE AIR
DAMPER CONTROL
OUTPUT
OPTIONAL
3RD PARTY
FAN CONTROL
INPUT
TO OUTDOOR UNIT
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR
DATA CABLE WITH SCREEN WIRE CONNECTED TO
TERMINAL "G" ON OUTDOOR & INDOOR UNIT
WALL CONTROL
485 A
Power
485 A
Power
OPTIONAL WC-2 & TWC-1 WALL CONTROLLERS
NOTE: MAX 3 WC ALLOWED ONLY
(REFER TO INSTALLATION & COMMISSIONING
GUIDE FOR OTHER WIRING CONFIGURATIONS)
FIELD WIRING BY INSTALLER -
CABLE MUST BE CAT5e DATA CABLE
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
WALL CONTROLLER WIRING
POWER:
485 A:
485 B:
GND:
NOT USED:
- BROWN / ORANGE
- BLUE
- BLUE-WHITE
- BROWN-WHITE / ORANGE-WHITE
- GREEN / GREEN-WHITE
FIELD
WIRING
BY
INSTALLER
12VABG
FIELD WIRING
IF-1
1 EC
IF-2
1 EC
ECM
CONTROL
MODULE
ECM
CONTROL
MODULE
FERRITE
FERRITE
ECM-2 ECM-1
EE
N
N
A
A
NN
AA
LINE 1
NEUTRAL
LINE 2
LINE 3
EAR TH
OPTIONAL
FILTER INDICATION
RELAYOUTPUT
(240V 10A MAX)
INPUT VOLTAGE
N/C OUTPUT
+12V
OUTPUT
COM
0-10V
OUTPUT
0-10V
INPUT
COM
COM
N/O OUTPUT
INDOOR
COIL
TEMP
SENSOR
SMPS
240V AC
NEUT
30 W
+12VDC
0VDC
SHIELD
WIRE
CMI
POT
ADJUST
AMB
SENSOR
FILTER
IND ICAT IO N
PWM
FAN1 OUT
PWM
FAN2 OUT
FAN IN WALL CONT ROLLER OUTDOOR
485 FAN
AUX SENSOR
ECON OUTAUX OUT AUX IN
+12V
0-10V
+12V
COM
COM
AA
A
S1
0-10V
0-10V
BB
B
COM
COM
COM
GG
G
S2
COIL
T E MP
DISPLAY
PWR
0-10V
0-10V
0-10V
FAN2 OUT
0-10V
FAN1 OUT
COM
COM
NC NO
COM
COM 1 COM 2
COM 3 +12VDC
POWER IN
V+
V-
ZONE
MASTER SECONDARY
OFF
ON
PWM FAN OUT PUT
0-1 0V FAN INP UT S
INT ERNAL FAN SPEED
12 345678
STANDARD DIP
SWITCH SETTINGS
MANUAL FAN SPEED
POT AD JUST
OPTIONAL
FAN RUN
INDICATION
OUTPUT
OPTIONAL
OUTSIDE AIR
DAMPER CONTROL
OUTPUT
OPTIONAL
3RD PARTY
FAN CONTROL
INPUT
TO OUTDOOR UNIT
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR
DATA CABLE WITH SCREEN WIRE CONNECTED TO
TERMINAL "G" ON OUTDOOR & INDOOR UNIT
WALL CONTROL
485 A
Power
485 A
Power
OPTIONAL WC-2 & TWC-1 WALL CONTROLLERS
NOTE: MAX 3 WC ALLOWED ONLY
(REFER TO INSTALLATION & COMMISSIONING
GUIDE FOR OTHER WIRING CONFIGURATIONS)
FIELD WIRING BY INSTALLER -
CABLE MUST BE CAT5e DATA CABLE
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
WALL CONTROLLER WIRING
POWER:
485 A:
485 B:
GND:
NOT USED:
- BROWN / ORANGE
- BLUE
- BLUE-WHITE
- BROWN-WHITE / ORANGE-WHITE
- GREEN / GREEN-WHITE
FIELD
WIRING
BY
INSTALLER
12VABG
LEGEND
LEGEND
CMI
CMI
ECM
ECM
IF
IF
SMPS
SMPS
WC
WC
TWC
TWC
52% PWM
67% PWM
EVA290T
EVA330T
DEFAULT FAN SPEED
SETTINGS (@ 100pa)
52% PWM
67% PWM
EVA290T
EVA330T
DEFAULT FAN SPEED
SETTINGS (@ 100pa)
01-06-2020
RL3280
CHANGED WC WIRING COLOUR REFERENCE & REMOVED WC-3 & ADDED TWC-1C01-06-2020

Installation and Commissioning Guide Variable Capacity Commercial
13
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Split Unit Electrical Connection
DETAILED WIRING DIAGRAM IS PROVIDED WITH THE UNIT
Outdoor Unit: Located at the back of electrical/compressor access panel.
Indoor Unit: Located at the back of electrical box cover.
MAINS WIRING (400VAC)
(Three Phase +Neutral+Earth) 50Hz
INTER-CONNECTING POWER CABLE (400VAC)
(Three Phase + Neutral+Earth) 50Hz
DATA CABLE TO WALL CONTROL
(Cat5E UTP (AWG 24) Data Cable)
EXTRA LOW VOLTAGE DATA CONTROL WIRING
(2 Core Shielded Twisted Pair 7/0.30 (0.5mm2) Shielded Data Cable)
4
3
2
1
SUB-MAINS
TO UNIT
SUB MAINS
LOAD BREAK ISOLATOR
SUB MAINS
CIRCUIT BREAKER
(CB/RCBO/RCD)
4
3
SUB MAIN SUPPLY FROM
DISTRIBUTION BOARD
1
INDOOR UNIT
WALL
CONTROL
EXTRA LOW VOLTAGE
DATA CONTROL WIRING
(INDOOR TO OUTDOOR)
DATA CABLE
INTER-CONNECTING
POWER CABLE
OUTDOOR - INDOOR
2
OUTDOOR UNIT
MAIN
SWITCHBOARD
NOTE
To minimise noise interference, Data and Power cable clearance should be maintained as much as possible (minimum
300mm).

14 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
2 Core Twisted Data Cable Shielding Instructions
(ActronAir Part Number: AEDC2)
NOTES
• Maintain the twist of the core wires up to the Green Terminal Plug.
• Maximum strip length of outer insulation to the Green Terminal Plug is 50mm.
• Make sure the cable colours used for the Data Terminal in Outdoor Unit match the Data Terminal in Indoor unit.
Outdoor Unit Data Terminal (Green Plug)
“Terminal A” - White Wire
“Terminal B” - Black Wire
“Terminal G” - Shield Wire
Indoor Unit Data Terminal (Green Plug)
“Terminal A (+)” - White Wire
“Terminal B (-)” - Black Wire
“Terminal G” - Shield Wire
Insert data cable through the lower snap bushing and first cable tie on the right hand side of the electrical panel.
Connect core wires and shield wire into the Outdoor Board green terminal plug marked “ INDOOR A, B and G”.
(Refer to unit wiring diagram for complete wiring connection details).
OUTDOOR
BOARD
OUTDOOR BOARD
TERMINAL PLUG
CIRCUIT BREAKER SIZE AND CABLE SIZE REQUIREMENT
Model
Circuit Breaker Size Cable Size *(mm2)
Amps MAIN O.D. to I.D.
EVA290T / EVA330T 32.0 6.0 1.0
* Suggested Minimum Cable Size should be used as a guide only, refer to the latest edition of the AS/NZS 3000
“Australian / New Zealand Wiring Rules” for more details.

Installation and Commissioning Guide Variable Capacity Commercial
15
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Maximum Cable Lengths
. Wall Controller Options
Maximum of three (3) wall controllers in below combinations is allowed on unit. See below table.
Combinations Wall Controllers
WC 1 WC 2 WC 3
1st Option NEO
2nd Option NEO NEO
3rd Option NEO NEO LC7-2
4th Option NEO LC7-2
5th Option NEO LC7-2 LC7-2
6th Option LC7-2
7th Option LC7-2 LC7-2
8th Option LC7-2 LC7-2 LC7-2
NOTES
• NEO - Available in White (NTW-1000) and Black (NTB-1000) colours.
• LC7-2 - Available in White and Grey colours.
• In the instance of a combination of NEO and LC7-2 being connected together, the NEO will always need to be addressed
as C1.

16 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Wiring Configuration : Recommended
4
INDOOR UNIT
DATA CONTROL
CABLE
3
LMRS2
OPTIONAL
AERSS
OPTIONAL
2a
NEO
WALL CONTROLLER
1
OPTIONAL
2b
NEO
WALL CONTROLLER
2
OPTIONAL
LC72
WALL CONTROLLER
3
OPTIONAL
2c
1
OUTDOOR UNIT
NOTES
• Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
• Daisy connection is not allowed for NEO wall controller.
Item Description Maximum Cable Length
1 to 4 Outdoor PCB to Indoor PCB 100 m
4 to 2a, 4 to 2b Indoor PCB to Wall Controller 90 m
4 to 2C Indoor PCB to Wall Controller 3 100 m
4 to 3 Indoor PCB to Remote Sensor 100 m
Description Cable Type
LC7-2 and NEO Field Control Wiring Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor Cat5E UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable 2 Core Shielded Twisted Pair 7/0.30 (0.5mm2) Shielded Data Cable

Installation and Commissioning Guide Variable Capacity Commercial
17
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. Alternate Wiring Configuration
1
OUTDOOR UNIT
2a
LC72 WALL CONTROL
1
OPTIONAL
LC72 WALL CONTROL
2
OPTIONAL
LC72 WALL CONTROL
3
OPTIONAL
2b 2c
4
INDOOR UNIT
DATA CONTROL
CABLE
3
LMRS2
OPTIONAL
AERSS
OPTIONAL
NOTES
• Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
Item Description Maximum Cable Length
1 to 4 Outdoor PCB to Indoor PCB 100 m
4 to 2a Indoor PCB to Wall Control 1 100 m
4 to 2c Indoor PCB to Wall Control 3 (last controller) 75m total (Daisy Chain)*
4 to 3 Indoor PCB to Remote Sensor 100 m
* Maximum Daisy Chain connection is up to 2 wall Controls.
Description Cable Type
LC7-2 Field Control Wiring Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor Cat5E UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable 2 Core Shielded Twisted Pair 7/0.30 (0.5mm2) Shielded Data Cable

18 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. Wiring Connections
. LC- Wall Control Wiring Connections
WALL CONTROL
GND
485 B
485 A
Power
WC-1
WALL CONTROLLER
+12V AB G
CUT OFF
GR / GR-WH
BR / OR
BL
BL-WH
BR-WH / OR-WH
BR / OR
BL
BL-WH
BR-WH / OR-WH
INDOOR
CONTROL
BOARD
WALL CONTROL WIRING
POWER: - BROWN / ORANGE
485 A: - BLUE
485 B: - BLUE-WHITE
GND: - BROWN-WHITE / ORANGE-WHITE
NOT USED: - GREEN / GREEN-WHITE
. NEO Wall Control Wiring Connections
. NEO RJ Wiring
WALL CONTROL
TWC-1
+12V
A
B
G
INDOOR
CONTROL
BOARD
RJ45
WALL CONTROL
TWC-2
+12V
A
B
G
RJ45
WALL CONTROLLER
. NEO Hard Wiring
WALL CONTROL
WALL CONTROLLER
+12V A B G
CUT OFF
GR / GR-WH
INDOOR
CONTROL
BOARD
+12V
A
B
G
RJ45
WALL CONTROL WIRING
POWER: - BROWN / ORANGE
485 A: - BLUE
485 B: - BLUE-WHITE
GND: - BROWN-WHITE / ORANGE-WHITE
NOT USED: - GREEN / GREEN-WHITE

Installation and Commissioning Guide Variable Capacity Commercial
19
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
. LM-RS- Optional Sensor Wiring Connections
REMOTE SENSOR WIRING
PAIR 1 (BLUE / BLUE-WHITE)
PAIR 2 (ORANGE / ORANGE-WHITE)
PAIR 3 (GREEN / GREEN-WHITE)
PAIR 4 (BROWN / BROWN-WHITE)
INDOOR
CONTROL
BOARD
OPTIONAL
SENSOR 3
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
S1 S2 S3 COM
TEMP
SENSORS
LM-RS LM-RS LM-RS
PAIR 1
PAIR 1
PAIR 1
PAIR 2
PAIR 2
PAIR 1
PAIR 1
PAIR 1
PAIR 2
PAIR 2
NOTE:
• PAIR 1 AND 2 USED FOR ILLUSTRATION
PURPOSES ONLY.
• CUT OFF AND TERMINATE ANY
UNUSED PAIRS TO ENSURE NO WIRING
IS LEFT EXPOSED
REMOTE SENSOR WIRING
PAIR 1: - BLUE / BLUE-WHITE
PAIR 2: - ORANGE / ORANGE-WHITE
PAIR 3: - GREEN / GREEN-WHITE
PAIR 4: - BROWN / BROWN-WHITE
. AERSS Optional Duct Sensor Wiring Connections
REMOTE SENSOR WIRING
PAIR 1 (BLUE / BLUE-WHITE)
PAIR 2 (ORANGE / ORANGE-WHITE)
PAIR 3 (GREEN / GREEN-WHITE)
PAIR 4 (BROWN / BROWN-WHITE)
INDOOR
CONTROL
BOARD
S1 S2 S3 COM
TEMP
SENSORS
PAI R 1
PAI R 1
PAI R 1
PAI R 2
PAI R 1
PAI R 1
PAI R 1
PAI R 2
PAI R 2
PAI R 2
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
OPTIONAL
SENSOR 3
WIRE
JOINERS
WIRE
JOINERS
AERSS AERSS
REMOTE SENSOR WIRING
PAIR 1: - BLUE / BLUE-WHITE
PAIR 2: - ORANGE / ORANGE-WHITE
PAIR 3: - GREEN / GREEN-WHITE
PAIR 4: - BROWN / BROWN-WHITE
NOTE:
• PAIR 1 AND 2 USED FOR ILLUSTRATION
PURPOSES ONLY.
• CUT OFF AND TERMINATE ANY UNUSED
PAIRS TO ENSURE NO WIRING IS LEFT
EXPOSED

20 Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068 Ver. 3 201104
Installation and Commissioning Guide Variable Capacity Commercial
. EC Indoor Fan Commissioning
There are various ways of commissioning Indoor Fan Airflow. This could be done using the Outdoor Unit CPU, NEO/LC7-2
Wall Control or 3rd Party Controller depending on the installation requirement. See Outdoor Unit Commissioning Guide
for details.
It is possible to operate the fan, without an outdoor or NEO/LC7-2 connected, to allow air balancing to take place. This
can be done by following the steps below:
Step 1. On the CMI board, set dip switch 8 to ON.
Step 2. Apply power to the Indoor unit. Using the on-board potentiometer, manually adjust the fan PWM speed. This will
be displayed on the 7 segment display.
FILTER
INDICATION
PWM
FAN1 OUT
PWM
FAN2 OUT
AUX SENSOR
S1 COM S2
NC NO
COM
OFF
ON
PWM FAN OUTPUT
0-10V FAN INPUTS
INTERNAL FAN SPEED
12 345678
STANDARD DIP
SWITCH SETTINGS
MANUAL FAN SPEED
POT ADJUST
7 SEGMENT LCD DISPLAY
SWITCH 8
Step 3. Once the air balancing is complete, set the dip switch 8 back to OFF.
Step 4. Refer back to Outdoor Unit for completing system configuration.
NOTE
Once dip-switch number 8 is on the indoor fan will start immediately. If the dip switch is left on the indoor fan will remain
running at all times.
This manual suits for next models
1
Table of contents
Other ActronAir Air Conditioner Accessories manuals

ActronAir
ActronAir PKV160T User manual

ActronAir
ActronAir LR7-1W User manual

ActronAir
ActronAir BMS MODBUS 485 User manual

ActronAir
ActronAir Que Touch Series User manual

ActronAir
ActronAir CRQ2-14AS User manual

ActronAir
ActronAir LM7-2W User manual

ActronAir
ActronAir MRE-035AS User manual

ActronAir
ActronAir Easyconnect OSK105 Assembly instructions

ActronAir
ActronAir CP05 User manual

ActronAir
ActronAir Classic 2 EVA100S User manual