Adash A3900 II User manual

ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
USER MANUAL
A3900 II
Online Monitoring System

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
2
Contents
On-line vibration monitoring system................................................................................................... 3
Before the First Start-up ....................................................................................................................... 4
Unit description ..................................................................................................................................... 5
Data outputs ........................................................................................................................................................ 5
Front panel description ........................................................................................................................................ 5
A3900-II connection............................................................................................................................... 8
Terminals description .......................................................................................................................................... 8
Module connection .............................................................................................................................................. 8
Sensor connection............................................................................................................................................... 9
Output current loop 4-20mA ................................................................................................................................ 9
Output relay ....................................................................................................................................................... 10
Serial interface RS232....................................................................................................................................... 10
Data storage ...................................................................................................................................................... 10
A3900-II setting .................................................................................................................................... 11
Hyper Terminal setting:...................................................................................................................................... 11
Measurement parameters setting: ..................................................................................................................... 14
Technical Specification of Adash 3900-II.......................................................................................... 18
Dimensioned Sketch of Adash 3900-II .............................................................................................................. 18

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
3
Adash 3900-II
On-line vibration monitoring system
Application:
- Predictive maintenance
- Measurement of bearing condition
- Machine protection systems
- Machine control systems
- Machine monitoring systems
Characteristics:
- Measurement of vibration (mm/s, in/s) in freq.band 10-1000Hz
- Measurement of bearing condition (HF parameter, g=9.82m/s2) in freq.band 5-16kHz
- Wideband measurement of acceleration (g=9.81m/s2) in freq.band 0.8Hz-16kHz
- Measurement of TRUE RMS and TRUE PEAK values
- A3900-II settings from computer via RS232 interface
- A3900-II is possible to connect to memory module for data storage (standard CompactFlash card)
- Adjustable current loop 4-20mA for actual value output
- Complete checking of failures. Current of the loop drops to 3.5 mA immediately and the control
system does not generate any incorrect response
- Indication of exceeding the predefined vibration limits (ALARM, ALERT)
- ALARM limit relay
- The quality acceleration ICP sensor is used
- Continuous check of break of cable or sensor
- Simple connection to control systems (PLC)
- Simple installation to DIN rail

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
4
Before the First Start-up
1. Never connect any sensor to the ICP input of the unit other than the ICP sensor type! If you
are not sure, consult the procedure with your supplier.
2. Never connect the unit directly to the mains voltage !
3. Use only power supply units with a nominal voltage 20 - 28V DC to supply the unit !
4. Use only power supply units with a nominal voltage 10 - 30V DC to supply current loop !
5. Pay attention to the correct polarity of the supplied voltage !
Failure to respect any of the following recommendations may damage the device !
With a non-professional handling of voltage exceeding 50 V you expose yourself to accident
hazard.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
5
Unit description
The unit Adash 3900-II is simple tool for vibration measurements, which is intended for process control
and reliability systems, machinery protection systems and generally for all the applications concerning
the maintenance and monitoring of machinery state. Thus, a large variety of applications are possible
for motors, fans, pumps, gearboxes, small turbines, bearing diagnostics etc.
Data outputs
Actual measured value is displayed on three-digits, seven-segments display on the front panel.
There are also situated all LEDs for indication of unit state.
A3900-II unit contains two additional outputs:
- adjustable current loop 4-20mA - output of actual value for using in control systems (PLC)
- switch-over relay - for "ALARM" indication
Current loop, "ALARM" and "ALERT" limits and all others parameters are adjustable by software
"Hyperterminal" (standard MS-Windows program). Standard serial interface RS232 is used for
connection between PC and A3900-II. If "ALARM" limit is exceeded, then relay contacts are switched
on/off. Any failure of sensor, or cable (disconnection of cable too) is signalized by message "ICP" on
display.
Front panel description
On the front panel are situated:
- BNC connector for analogue output of measured signal
- three-digits, seven-segments display for real-time displaying of measured value
- three LEDs ("mm/s", "ips", "g") for indication of measured unit
- LED ("PEAK") for indication of evaluation of signal ( TRUE PEAK (LED is on) or TRUE RMS (LED is
off))
- three LEDs ("OK", "ALERT", "ALARM") for indication of limit exceeding
- LED ("LOOP") for indication of current loop status

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
6
Three-digits, seven-segments display - the report list
After start or restart
8.8.8. plus all LEDs are ON (user can check, whether all front panel components light)
X.XX firmware version (e.g. 2.20), all LEDs are OFF
During the Measurement
XXX measured value (0.00 - 999), there are three LEDs, which indicated a measured unit. The
"LOOP" LED indicates status of current loop and relation to predefined limits is indicated by
"OK", "ALERT" and "ALARM" LEDs.
- - - measurement is stopped, parameters are set via interface RS232 (if these segments are
blinking, then time delay for system restart is run)
ICP - cable or sensor is not connected
- failure of cable or sensor (short circuit, disconnection)
- failure of ICP power supply
Err memory failure
CAL system auto-calibration after restart
OVr input amplifier overload - failure state (you should use the lower sensitivity of sensor)
Unit state signalization
Status and settings of unit is signalized by LEDs on the front panel. Description of all adjustable
parameters - see Detailed description of menu.
Measured unit (mm/s, ips, g) and evaluation (RMS, PEAK )
mm/s, ips, g LED indicates measured unit
PEAK LED indicates evaluation of TRUE PEAK (LED is on) or TRUE RMS (LED is
off)
Measurement status (OK, ALERT, ALARM)
all of three LEDs are OFF check function does not run (Alarm value = 0)
OK LED is ON check function runs and status is OK (value lower than
Alert and Alarm value), COM-1 contacts are opened and 0-COM
contacts are closed
ALERT LED is ON - measured value is lesser than Alarm value, but it is greater
than Alert value, COM-1 contacts are opened and 0-COM contacts
are closed
ALARM LED is ON - measured value is greater than ALARM value and relay is
switch on: COM-1 contacts are closed and 0-COM contacts are
opened
Current Loop status
LOOP LED is OFF - current loop does not run (Loop max value = 0)
LOOP LED is blinking - current loop circuit is opened - power supply for current loop is failed
LOOP LED is ON - current loop works OK

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
7
Output signal from sensor
The BNC connector is the output of measured signal. It is possible to connect an external vibration-
analyser or other evaluation device for independent measurement of the signal.
The 3900 II unit is able to accept max. signal from sensor in range +/- 5V. You should use the sensor
with suitable sensitivity.
Signal on the BNC connector is separated from the sensor by amplifier with gain 1 and output
resistance aprox. 3k.
Signal on BNC does not contain DC component, which is created by ICP power supply.
Input parameters of external devices or short circuit on the BNC have no effect to the 3900 II data
processing.
ICP powered input of external device can be connected and used directly to BNC output.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
8
A3900-II connection
Terminals description
Power supply terminals
+24V positive pole of supply voltage 20–28 V
0V negative pole of supply voltage
They are two pairs and they are intended for power supply of module and current loop (in
active mode).
Input terminals
+ICP positive pole of ICP
ICP negative pole of ICP
SHLD sensor cable shield
Output terminals of current loop
+ LOOP positive pole of current loop 4-20 mA
- LOOP negative pole of current loop
Output terminal of relay (ALARM)
COM common contact of relay
1 contact of relay (in ALARM status it is closed with COM)
0 contact of relay (if not ALARM status it is closed with COM
Module connection

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
9
Sensor connection
A3900-II unit is intended to measure the vibrations by acceleration sensor. A real sensibility of used
sensor (mV/g) can be set by PC. A3900-II is possible join to PC by standard crossing cable RS232
see Detailed description of menu.
For sensor connection is recommended usage of shielded twisted pair, which is resistant to
electromagnetic field. The Adash Ltd. supplies the cable with this standard connection:
+ICPwhite
ICP blue or blue-white
SHLD cable shield
Output current loop 4-20mA
Current loop is intended for output of measured value. Output current is in range 3.5 - 22mA (4-20mA
- value output, 3.5, 3.75 and 22mA to indication of current loop state).It can be processed by external
devices or indicated by external ampere-meter.
Current loop is galvanic separated from measuring circuits. It can doing in active or passive mode (see
module connection). For power supply of loop in active mode is used input supply voltage 20-28V DC
and for power supply of loop in passive mode must be used external power source 10-30V DC (see
Module connection).
Output range of current for measured value
Output range of current loop for measured value is 4 - 20 mA. Minimum and maximum value of
current loop can be assigned to minimum and maximum value of measuring unit.
20 mA - "loop max value" (maximum of measured unit)
4 mA - "loop min. value" (minimum of measured unit)
Range of current loop for measured data is adjustable from PC (see Detailed description of menu).
Output current of loop out of the measuring range
If measured value of vibration exceeds "Loop max. value", then the output current is 22mA.
If measured value of vibration is less than "Loop min. value", then the output current is 3.75mA.
During unit initialization (e.g. after start unit) the output current is 3.5mA.
If measuring is stopped by command from PC, then the output current is 3.5mA.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
10
During unit setup by PC and when measuring is stopped, then the output current is 3.5mA.
If input of unit is overload by high-level signal, then output current is 3.5mA.
If any error is detected (e.g. ICP error), then output current is 3.5mA.
If current loop is switched-off by user (Loop max. value =0), then output current is 3.5mA.
If blackout occurs or if unit is restarted, then output current is aprox. 1.3mA (even if current loop is in
passive mode, see module connection).
Output relay
A3900-II unit contain output switch-over relay with one double throw contact (see Module connection).
If ALARM value is exceeded, relay is switched on COM-1 contacts and 0-COM contacts are switched
off (ALARM value has not to be zero).
User can decide, which pair of contacts to use.
Attention!!!
From relay state cannot be find out the status of unit. If unit is not power supplied, then contacts COM-
1 are opened and contacts 0-COM are closed.
If unit input is overloaded by signal from sensor (is signalized OVR on display), then relay remains in
the previous state. If the status was not "ALARM" before the OVR, then the OVR does not cause
switch of relay to "ALARM".
Using of the relay is recommended, if the RMS value is measured. If the PEAK value is measured,
any short-time high amplitude can generate alarm.
Serial interface RS232
A3900-II is possible join to PC by standard crossing cable RS232 with connector CANNON 9 (female,
female) and by reduction CANNON 9 / 10pin connector (see Module connection). This reduction is in
the standard distribution shops.
Data storage
A3900-II is possible to connect to memory module 3600MEM. There are stored measured data to
standard compact flash card. Stored data can by analysed in PC. For further information contact the
ADASH Ltd.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
11
A3900-II setting
A3900-II module is set by PC in the Hyper Terminal. Hyper Terminal is standard part of Windows.
After connection to PC (by RS-232), Hyper Terminal must be started and setting. Connection RS232
to A3900-II unit - see Serial interface RS232.
Hyper Terminal setting:
1/ Run Hyper Terminal (Windows Start / Programs / Accessories / Communication / Hyper Terminal).
2/ Create a new connection, describe a name of connection e.g. A3900 and click on OK button.
3/ Choose COM-port (used by A3900II) from field "Connect using" and click on OK button (other
settings are irrelevant).

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
12
4/ Choose connection parameters like picture below / click on OK.
Now connection is created and actual value of measuring is displayed every aprox.1[s] time interval.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
13
6/ MENU display - click on the Hyper Terminal window and press ENTER or SPACE.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
14
Measurement parameters setting:
Enter, Space - Open menu (measuring will continue)
Esc - Close menu (if measuring isn't stopped)
m - Stop measuring / Start measuring (System is automatically resetting after Start measuring).
Most of the parameters setting needs to restart measuring.
s - Save new setting
'1' - Measured unit (mm/s, in/s, g)
Measured unit can be changed only if the measuring is stopped (by pressing the key 'm').
Submenu of measured unit is opened by pressing the key '1'.
'1' g-rms measuring of acceleration
'2' g-peak measuring of acceleration
'3' mm/s-rms measuring of velocity
'4' ips-rms measuring of velocity
'5' mm/s-peak measuring of velocity
'6' ips-peak measuring of velocity
Measured unit can be chosen from this submenu by pressing the key '1', '2', '3', '4', '5' or '6'.
A new measured unit is confirmed by pressing the key 's'. New measuring is started by pressing the
key 'm'.
If measuring of acceleration is choosen (g/rms or g/peak), then HF(5-16kHz)/LIN(0-16kHz) setting is
added to menu.
Attention!!! – if measured unit is changed by user, then Alarm value, Alert value, Loop max. value
and Loop min. value are reset to zero!
h - setting of frequency band of acceleration [g] – LIN [g] (0.5Hz–16kHz), or HF [g] (5kHz–16kHz).
It can be changed only if the measuring is stopped by pressing the key 'm'.
This menu is displayed only for measuring of acceleration. A setting of frequency band of acceleration
can be changed by pressing the key 'h'. A new setting of frequency band of acceleration is confirmed
by pressing the key 's'. New measuring is started by pressing the key 'm'.
'2' - Sensor sensitivity
Sensor sensitivity can be changed only if the measuring is stopped (by pressing the key 'm').
Sensor sensitivity can be changed by pressing the key '2'. A new sensor sensitivity is confirmed by
pressing the key 's'. New measuring is started by pressing the key 'm'.
Attention!!! sensor sensitivity has not to be zero
'3' - Alarm value (relay on)
Alarm value can be changed only if the measuring is stopped (by pressing the key 'm').
A Alarm value can be changed by pressing the key '3'. If Alarm value is zero, relay is deactivated. A
new Alarm value is confirmed by pressing the key 's'. New measuring is started by pressing the key
'm'.
measured data ALARM indicator contacts COM-1 contacts 0-COM
----------------------------------------------------------------------------------------------------------------------------------------
lower than Alarm is ON switched on switched off
value
more than Alarm is OFF switched off switched off
value

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
15
Attention!!! - if measured unit is changed by user, then Alarm value is reset to zero!
Attention!!! -from relay state cannot be find out state of unit. If unit haven't power supply, then
contacts COM-1 are switched off and contacts 0-COM are switched on.
Attention!!! - if unit input is overloaded by great signal from sensor (is signalized OVR by display),
then relay stay in the previous state. If unit don't measure Alarm value before the input is overloaded,
then OVR value don't cause switch of relay.
Attention!!! - Alarm value and Alert value are recommended to use only if RMS value is measured.
'4' - Alert value
Alert value can be changed only if the measuring is stopped (by pressing the key 'm').
A Alert value can be changed by pressing the key '4'. A new Alert value is confirmed by pressing the
key 's'. The Alert value must be lesser than Alarm value. New measuring is started by pressing the key
'm'.
measured data ALERT indicator
-----------------------------------------------------------------
lower than Alert value is ON
more than Alert value is OFF
Attention!!! - if measured unit is changed by user, then Alert value is reset to zero!
Attention!!! - if Alert value = 0, then this function is deactivated
Attention!!! - Alarm value and Alert value are recommended to use only if RMS value is measured.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
16
'5' - Loop max. value (value of measured unit which matches to
20mA)
Loop max. value can be changed only if the measuring is stopped (by pressing the key 'm').
A Loop max value can be changed by pressing the key '5'. If Loop max value is zero, current loop is
deactivated (LED is OFF, current of loop is 3,5mA). A new Loop max value is confirmed by pressing
the key 's'. New measuring is started by pressing the key 'm'.
Attention!!! - if measured unit is changed by user, then loop max value is reset to zero! If value of
measured unit exceeded maximum value, then current of loop is 22mA.
'6' - Loop min. value (value of measured unit which matches to 4mA)
Loop min. value can be changed only if the measuring is stopped (by pressing the key 'm').
A Loop min value can be changed by pressing the key '6'. Loop min value must be lesser than Loop
max value. A new Loop min value is confirmed by pressing the key 's'. New measuring is started by
pressing the key 'm'.
Picture: Two typical characteristic of current loop:
I I
[mA] [mA]
20 20
4 4
0 = LOOPMIN LOOPMAX MEASURED 0 LOOPMIN LOOPMAX MEASURED
VALUE VALUE
Attention!!! - if measured unit is changed by user, then Loop min value is reset to zero! If value of
measured unit is lesser than minimum value, then current of loop is 3,75mA.
'7' - Measuring activation delay
Measuring activation delay can be changed only if the measuring is stopped (by pressing the key 'm').
A measuring activation delay value can be change by pressing the key '7'. It is necessary to sensor
activating. A default value of the Measuring activation delay is 10s, maximum value of the Measuring
activation delay is 60s. A new Measuring activation delay value is confirmed by pressing the key 's'.
New measuring is started by pressing the key 'm'.
'8' - Values for averaging
Values for averaging is recommended to use for measuring of unstable vibration signals.
Values for averaging can be changed only if the measuring is stopped (by pressing the key 'm').
There is possible setting new Values for averaging (by pressing the key '8'). A default Values for
averaging is 3. A new Values for averaging is confirmed by pressing the key 's'. New measuring is
started by pressing the key 'm'.

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
17
'9' - Display brightness
Display brightness can be changed anytime.
There is possible changed a Display brightness. First, press the key '9' and second change Display
brightness by pressing keys '+,-' (at interval 0-15). A new Display brightness is confirmed by pressing
the key 's'.
Other parameters
d - Data storage Data storage settings (see part Data storage)
c - Calibration unapproachable for user, needs password

ADASH Ltd. Adash 3900-II
ADASH Ltd., Czech republic, tel.: +420 596 232 670, fax: +420 596 232 671, email: info@adash.cz
For more information visit www.adash.com
18
Technical Specification of Adash 3900-II
Dimensioned Sketch of Adash 3900-II
Technical Specification:
Inputs: - ICPfor vibration measurement (accelerometer with ICP
supply). Input is able to process signal with maximum voltage ±5 V
Outputs: - Galvanic separated current loop 4- 20 mA (selectable active/passive)
with setting of range of measured unit
- relay terminal 250V/2A (50Hz)
- input signal monitor
(BNC connector)
Measuring Ranges: - 0 – 20 g, 0 – 999 mm/s (by sensor sensitivity, input signal: max. ±5 V)
Frequency Bands: - [ g ] 0,8 Hz – 16 kHz
- [ g ] 5 kHz – 16 kHz
- [ mm/s ], [ ips ] 10 Hz – 1 kHz
Freq. ranges are possible to manufacture according to any user option.
Sensor: - accelerometer, ICPpowered
LEDs: - PWR check of power supply
-ICP
Err wrong sensor or cable
Supply: - 20 - 28 V DC (70mA/24V DC), external current loop supply (10-30V DC)
Dimensions: - 90 x 53 x 58 mm
Weight: - 130 g
Protection: - IP 20
ICP
is registered trademark of PCB Piezotronics, Inc
Table of contents
Other Adash Measuring Instrument manuals

Adash
Adash 4400 VA4 Pro User manual

Adash
Adash A3716 User manual

Adash
Adash 4300 VA3Pro User manual

Adash
Adash VIBRAMON 1 User manual

Adash
Adash 4300 - VA3 User manual

Adash
Adash 4900 Vibrio III User manual

Adash
Adash VA4 Pro II User manual

Adash
Adash 4900 Vibrio M User manual

Adash
Adash A4900 - Vibrio M User manual

Adash
Adash A3716 User manual
Popular Measuring Instrument manuals by other brands

GHM
GHM Delta OHM PYRAsense LPS03 Series operating manual

ROOTECH
ROOTECH Accura 2550TEMP Quick setup guide

SEW
SEW 3800 CL instruction manual

GBS Elettronica
GBS Elettronica 41986 instruction manual

Hanna Instruments
Hanna Instruments HI97737 instruction manual

Emerson
Emerson Rosemount 3818 Maintenance and troubleshooting manual