
6 3
Functional Testing
Testing the operation of the detector can be achieved in two ways, provided it is safe to do
so:
• A real flame from a portable flickering yellow bunsen flame or cigarette lighter
• A portable flame detector tester unit.
Maintenance Guide
The flame detector is designed to give years of trouble-free operation with minimal atten-
tion. However the periodic maintenance steps listed below are essential to maintain reli-
able fire protection.
1. Inform all appropriate personnel of intention to work on the flame detector.
2. Disable any automatic systems that may be activated by the flame detector if not
required as part of the maintenance check.
Alarms Extinguishers Control
Audio/Visual Gas systems Plant stops
Auto dialers Water sprays Dampers/doors
3. Check that the flame detector’s control panel is functioning correctly and shows no
faults.
4. Inspect the detector viewing window for any build-up of dust or other contaminants
on the optical surface. If necessary clean the optical surface with a cotton wipe wet
with commercial liquid glass cleaner, but not polishes. Rinse with clean water and dry
with a clean cloth.
The detector specification for performance is with a clean optical sensor window.
Contaminants like dust, oil and paint will reduce sensitivity.
5. Ensure the detector still has a clear line of sight of the area it is protecting and no
obstacles obstruct its view.
6. Check that the detector is securely fitted.
7. Visually check the exterior of the detector for any mechanical or corrosive damage.
8. Test the operation of the detector with either a portable flame sensor test unit or if
practical a flame.
9. Reinstate any automatic system disabled during maintenance.
Quantities required and positioning of detectors
The number of detectors required and their positioning depends on:
• the anticipated size of the flame
• the distance of the flame from the detector and
• the angle of view of the flame detector
The flame detector is designed to operate to Class 1 performance as defined in EN54-10.
The detector will, therefore, detect a flame of approximately 0.1m² or a clear flame of
0.25m² at 25m.
In fact, the flame detector will detect fires at distances of up to 40m, but the flame size at
such distances needs to be proportionally greater in order to be sure of reliable detection.
Thus the flame that can be detected at 25m, provided that its size is not less than 0.1m², will
have to be 0.4m² in order to be detected at 40m. In a rectangular room the distance from
the flame detector to the fire is calculated by the formula:
L² + W² + H²
In the example shown in Fig 1 the room in which the flame detector is to be installed meas-
ures 20m x 10m x 5m; the distance from the detector to the flame will therefore be:
20² + 10² + 5²
Height
Width
Length
© A
ollo Fire Detectors Limited 2000-2010/RHD/TB
Fig 1 Calculation of distance from detector to flame
The flame detector should be positioned at the perimeter of the room, pointing directly
at the area of the anticipated flame or at the centre of the area to be protected. If the
detector cannot ‘see’ the whole of the area to be protected, one or more additional
detectors may be required.
The flame detector is not affected by most normal indoor light sources but should be posi-
tioned so that daylight is not in view.
www.acornfiresecurity.com
www.acornfiresecurity.com