P/N 466-5570 (EN) • REV E • ISS 22MAR22 15 / 18
Options affected by other regulations
WARNING! Fire alarm and smoke detection products used
with Advisor Advanced systems are intended solely for
convenience and should not be used as life safety products.
The combination does not meet requirements set by law for life
safety products or for use as fire detection systems. Carrier
accepts no liability for any damages caused by incorrect
application of the products.
ACPO policy
Required settings are all EN 50131 Grade 2 settings with the
following modifications:
•4.2.n.5.1 Entry alarms, Delayed
•8.2.4 Engineer reset, tamper enabled
•8.7.6 Alarm confirm:
- AB mode, enabled for all relevant areas
- AB time, 30 min minimum, 60 min maximum
- EE Confirm, enabled
- TA confirm, enabled
Note: ACPO policy allows a higher level manager to become
a level 3 user. Also, level 3 user menu access may be allowed
without level 2 user authorization if it is provided by appropriate
written agreement from the customer.
Note: If the system must be compliant with both ACPO and
CPNI, all ACPO and CPNI required settings must be set. See
also “CPNI policy” below.
CPNI policy
To conform with UK CPNI (Centre for the Protection of
National Infrastructure) requirements, upon Installation, select
the default setting UK Grade 3.
The current minimum firmware for CPNI compliance is MR 4.7.
The main configuration settings included in the UK Grade 3
default settings required for CPNI (and PD6662:2017)
conformance are summarised below, and these must be
checked and configured when installing a new system or when
upgrading an existing system.
•4.2.n.4.2 Prealarm time: 0 s for all areas
•8.2.1 User code required: Yes
•8.2.4.2 Tamper: Yes
•8.2.4.4 Confirmed alarm: B-Alarm
•8.4.6 Pending alarms: Enable
•8.7.4 PIN length: 6
•8.7.6.4 EE confirm: Yes
•8.7.6.9 Reporting delayed: Yes
See Advisor Advanced Installation and Programming Manual
for further details on set-up.
CPNI approved control panels
The following Aritech Control Panels are approved for use on
CPNI sites:
•ATS1500A-IP-MM (requires ATS-MM-TK added for
compliance)
•ATS3500A-IP-MM
•ATS4500A-IP-MM
CPNI approved peripherals
The following Aritech Advisor Advanced peripherals are
approved for use with the above panels on CPNI sites:
•ATS-MM-TK (rear tamper kit required for ATS1500A-IP-
MM panel variant)
•ATS608, ATS626
•ATS1201E, ATS1203E, ATS1204E, ATS1210LE,
ATS1211E, ATS1202
•ATS1136, ATS1180, ATS1181, ATS1184
•ATS1740, ATS1744
•ATS1810, ATS1811
•ATS1451, ATS1452, ATS1455, ATS1457, ATS1458W,
ATS1458B, ATS1459, ATS1482
Wiring and interconnections, when used for CPNI
applications
The use of wiring and the associated interconnections shall be
appropriate for the system performance required and the local
conditions within the service environment.
The installation should conform to good working practices and
be in accordance with the requirements of the relevant
electrical installation regulations (for example, BS 7671) as
well as the specific recommendations of the equipment
manufacturer(s).
All cables must be adequately supported and run in positions
where there is least risk of physical damage. Cables installed
below 2 m above floor level and cables that may be exposed to
accidental damage must be mechanically protected by ducting,
trunking, or conduit. Cables that drop to protective switches
mounted on the floor (for example, for the protection of roller
shutter doors) should be encased in conduit to provide
mechanical protection. Where the mechanical protection is
made of conductive material it must also be properly earthed.
Wherever possible, wired interconnections should be run
inside the supervised area. However, where this is impractical,
interconnections shall be provided with protection against
tampering, for example, by enclosing the cables in metal
conduit.
The choice of cable used to interconnect the other intruder
detection system components may depend upon the specific
requirements of the installation, for example, some installations
might require fire resistant cabling. However, where no specific
requirements are defined, the use of a screened twisted pair
type cable is preferred as it provides superior immunity to
electrical interference compared with standard unscreened
alarm cable.
In certain circumstances, mains borne electrical interference
may cause false alarms. This can generally be overcome with
the use of screened cabling and by filtering the mains input to
the power supplies and separating the intruder detection
system interconnecting cables from mains and/or high voltage
cables.
Although the electrical standards require low voltage cables
used in intruder detection systems to be run in separate
containment from the mains power or high voltage cabling, it is
worth confirming that adequate separation has actually been
provided.
All joints in the interconnection wiring should be both
mechanically and electrically secure. Where conduit access
points and/or junction boxes are fitted outside the supervised
area they shall incorporate tamper detection. The removal of
their access covers shall require the use of a tool and the