AUMA Aumatic AC 01.1 User manual

Actuator controls
AUMATIC AC 01.1/ACExC 01.1
Manual Operation and setting
Control:
Parallel
Profibus DP
Profibus DP with FO
Modbus
Modbus with FO
DeviceNet
àFoundation Fieldbus

Table of contents Page
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 General notes on safety 5
1.2 Range of application 6
1.3 Warnings and symbols 6
2 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Name plate 7
2.2 Short description 8
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.1 Local operation 9
3.2 Operation from REMOTE 9
3.3 Menu navigation via push buttons (for settings and indications) 10
3.3.1 Short overview: functions of the push buttons 10
3.3.2 Structural design and navigation 11
3.4 Operation and setting via AUMA COM-AC programming software 12
3.4.1 Operation setting via COM-AC 12
3.5 Password change 13
3.6 Language change in the display 14
3.7 LCD contrast setting of the display (applies only to controls with green display) 14
4 Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 Status indications in the display 15
4.1.1 Status indication S0/S6 - operation 15
4.1.2 Status indication S4 - torque 16
4.2 Torque indication: edit 16
4.3 Electronic name plate 17
4.3.1 Display indication: enable view 17
4.3.2 Electronic name plate: view 17
4.4 Indication lights/LEDs 19
4.4.1 Standard indication 19
4.4.2 Configuration of the signals: view/edit 20
4.4.3 Blinking behaviour of indication lights/LEDs: view/edit 21
5 Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.1 Signals via fieldbus 22
5.1.1 Configuration of adjustable (user-definable) signals 22
5.2 Feedback via output contacts (binary) - (option) 23
5.2.1 Configuration for output contacts 1 to 5: view/edit 23
5.2.2 Configuration alarm contacts (collective fault signal): view/edit 25
5.2.3 Output contacts 1 to 5: use as running indication (blinker) 26
5.3 Feedback signals (analogue) - (option) 27
5.3.1 Position transmitter/actual position source (E2): view 27
5.3.2 Source of the torque signal E6: view 28
5.3.3 Feedback signals (configuration) via analogue output 1: view 28
5.3.4 Signal range at the analogue output 1: view/edit 29
5.3.5 Feedback signals (configuration) via analogue output 2: view 30
5.3.6 Signal range at the analogue output 2: view/edit 30
2
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
Read operation instructions first
.Observe safety instructions.
Reference documents:
.Operation instructions (assembly, operation, commissioning) for actuator
.Manual (Fieldbus device integration) AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses from page 94).

Page
6 Operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.1 Operation mode OFF 31
6.2 Operation mode LOCAL 32
6.2.1 Push-to-run operation or self-retaining: set for the operation mode LOCAL 32
6.3 Operation mode REMOTE 33
6.3.1 Push-to-run operation or self-retaining: set for operation mode REMOTE 33
6.4 Operation mode EMERGENCY 34
6.4.1 Operation mode (type of duty) activation for an emergency operation 34
6.4.2 EMERGENCY operation: switch on or off/signal behaviour definition 35
6.4.3 Actuator behaviour definition in case of an emergency operation 35
6.4.4 EMERGENCY position definition 36
6.4.5 Motor protection and/or torque switching: by-pass 36
6.5 Fault State behaviour in case of bus communication loss 37
6.6 Failure behaviour in case of analogue signal loss (option) 37
7 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
7.1 Type of seating: check/edit end positions 40
7.2 Torque switching: check/set 41
7.3 Limit switching setting 42
7.4 Intermediate positions (option) 43
7.4.1 Display indication: enable view 43
7.4.2 Intermediate positions: switch on or off 44
7.4.3 Intermediate position definition 44
7.4.4 Operation behaviour = actuator behaviour definition 45
7.4.5 Intermediate positions: set the signalling 45
7.5 Intermediate positions with multiport valve function (option) 47
7.5.1 Check: Multiport valve function available? 47
7.5.2 Check: Positioner active? 48
7.5.3 Display indication: enable view 48
7.5.4 Intermediate positions: switch on or off 48
7.5.5 Intermediate position setting 48
7.5.6 Operation behaviour = actuator behaviour definition 49
7.5.7 Intermediate positions signalling 49
7.5.8 Intermediate positions in LOCAL: direct approach without stopping 49
7.6 Positioner (operation mode SETPOINT MODE) 50
7.6.1 Adaptive behaviour: switch on or off 50
7.6.2 Overrun (inner dead band): set manually 51
7.6.3 Max. error variable (outer dead band): set manually 52
7.6.4 Dead time setting 52
7.6.5 Closing fully/opening fully (end position tolerance for setpoint E1) 53
7.6.6 Open-close duty (REMOTE) or modulating duty (SETPOINT) selection 53
7.6.7 Source of setpoint E1: view 54
7.6.8 Input range of setpoint 1: view/edit 55
7.7 Stepping mode (option) 56
7.7.1 Display indication: enable view 56
7.7.2 Stepping mode: switch on or off 57
7.7.3 Stepping range setting (start and end of stepping mode). 57
7.7.4 ON and OFF times setting 58
7.8 Local controls enable function (option) 59
7.8.1 Selector switch functions: enable/disable 59
7.9 EMERGENCY STOP function (option) 60
7.9.1 Description of the functions 60
7.9.2 Feedback signals on the display 61
7.9.3 Feedback signals setting via output contacts 61
7.9.4 Feedback signal setting via LEDs 61
3
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus

Page
7.10 Foundation Fieldbus interface 62
7.11 External inputs for bus (option) 63
7.11.1 Signals assignation for operation commands 63
7.12 Combination fieldbus/standard interface (option) 66
7.13 Monitoring and failure functions 67
7.13.1 Torque monitoring 67
7.13.2 Motor protection (thermal monitoring) 68
7.13.3 Monitoring of the max. number of starts per hour and max. running time per hour 69
7.13.4 Operating time monitoring 71
7.13.5 Reaction monitoring 72
7.13.6 Phase failure monitoring 73
8 Corrective action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.1 Fault indications and warning indications 74
8.1.1 Status indication S0 - faults and warnings 74
8.1.2 Status indication S1 - faults 75
8.1.3 Status indication S2 - warnings 76
8.1.4 Status indication S3 - causes for not ready remote 77
8.2 Diagnostics 78
8.2.1 Operating data logging 78
8.2.2 Diagnostic indications (D) via the display 80
8.3 Troubleshooting 91
8.3.1 Problems with position feedback/indication E2 (from actuator) 91
8.3.2 Display hardly readable or illegible 91
8.3.3 Actuator does not run 91
8.3.4 Actuator does only operate from local 91
8.3.5 Actuator is not switched off by limit seating in direction CLOSE or OPEN 91
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
Parameter index and indications on the display . . . . . . . . . . . . . . . . . . . 93
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual

1 Safety instructions
1.1 General notes on safety
5
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Standards/directives AUMA products are designed and manufactured in compliance with recog-
nised standards and directives. This is certified in a declaration of incorpora-
tion and a declaration of conformity.
The end user or the contractor of the plant must observe national laws and
regulations regarding assembly, electrical connection, and commissioning
on site.
This includes in particular the fulfilment of the requirements in standards
and directives for potentially explosive areas, such as e.g. EN 60079-17
“Inspection and maintenance of electrical installations in hazardous areas
(other than mines) (IEC 60079-17:2002)”.
This includes, in particular the observance of the applicable configuration
directives for fieldbus applications.
Safety instructions/
warnings
All personnel working with this device must be familiar with the safety and
warning instructions in this manual and observe the instructions given.
Safety instructions and warning signs on the device must be observed to
avoid personal injury or property damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and mainte-
nance must be carried out exclusively by suitably qualified personnel
authorised by the end user or contractor of the plant.
Prior to working on this product, the staff must have thoroughly read and
understood these instructions and, furthermore, know and observe officially
recognised rules regarding occupational health and safety.
Work performed in potentially explosive atmospheres is subject to special
regulations which have be observed. The end user or contractor of the plant
are responsible for respect and control of these regulations, standards, and
laws.
Commissioning Prior to commissioning, it is important to check that all settings are in com-
pliance with the requirements of the application. Incorrect settings might
present a danger to the application, e.g. cause damage to the valve or the
installation.
The manufacturer will not be held liable for any consequential damage. Such
risk lies entirely with the user.
Safe operation Prerequisites for safe and smooth operation:
.Correct transport, proper storage, mounting and installation, as well as
careful commissioning.
.Exclusively operate the device if it is in perfect condition while observing
these instructions.
.Immediately inform about any faults and damage and allow for corrective
measures.
.Observe recognised rules for occupational health and safety.
Protective measures The end user or the contractor are responsible for implementing required
protective measures on site, such as enclosures, barriers, or personal
safety equipment for the staff.
Maintenance Any device modification requires the consent of the manufacturer.

1.2 Range of application
AUMA actuator controls are exclusively designed for the operation of AUMA
actuators.
Other applications require explicit (written) confirmation by the manufac-
turer.
The following applications are not permitted, e.g.:
.motor activation
.pump activation
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the
device’s designated use.
1.3 Warnings and symbols
The following references and symbols are used in these instructions:
Potentially hazardous situation. Failure to observe this warning may result in
property damage.
Information The term Information preceding the text indicates important notes and
information.
For assembly, operation, and commissioning, observe the additional safety
and warning instructions of the reference documents (page 2).
Symbol for CLOSED.
Symbol for OPEN.
ÆVia the menu to parameter
Describes the path within the menu to the parameter. By using the push but-
tons of the local controls you may quickly find the desired parameter in the
display.
ÈDescription of the parameter settings/indications
Describes the setting/viewing possibilities of a parameter.
òStep by step
Provides a detailed description of each step for setting/viewing the parame-
ter.
6
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
NOTICE

2 Identification
2.1 Name plate
Each device is equipped with a name plate (figure 1).
Identification data on the controls’ name plate:
Type and size These instructions apply to the following controls types:
Type: AC = actuator controls AUMATIC
Size: 01.1
Commission number An order-specific commission number is assigned to each device. You can
use this number to download the wiring diagram, inspection records and fur-
ther information from the Internet (www.auma.com).
Wiring diagram/control Controlling the actuator controls is performed via a Foundation Fieldbus
interface , if the 11th position in the ACP wiring diagram contains the letters
B or C. Example: ACP 11F1-2M0—B000.
The actuator controls are designed for the Non-Intrusive version (refer also
to page 8), if the 7th position in the ACP wiring diagram contains the figure
M, e.g.: ACP 11F1-2M0—B000.
7
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
1 Type and size of the controls
2 Commission number
3 Wiring diagram/control
Figure 1
1 Name plate controls
auma
AC 01.1
Com No: 1309595
ACP M B:
P:1,5kW
No: 0902MA97286
KMS: TP180/001
11F1-2 0-- 000
3 ~ 400V IP67
Control: RS 485
1
2
3
Figure 2

2.2 Short description
Actuator controls The AUMATIC actuator controls is used to operate AUMA actuators and is
supplied ready for use.
The controls can be mounted directly to the actuator but also separately on
a wall bracket.
The functions of the AUMATIC controls include standard valve control in
OPEN - CLOSE duty, positioning, process control, logging of operating data,
diagnosis functions right through control via fieldbus.
Local controls/
COM-AC/fieldbus
Operation, setting, and display can be performed on site directly at the con-
trols or alternatively from REMOTE via a fieldbus interface.
On site it is possible to
.operate the actuator via the local controls (push buttons and display) and
perform settings (contents of these instructions).
.read in or out data or modify and save settings via the AUMA COM-AC
programming software (option), using a computer (laptop or PC).
Depending on the version, the connection between computer and
AUMATIC can be made with cable (infra-red interface) or without cable
(Bluetooth interface)(not included in these instructions).
Intrusive – Non-Intrusive Intrusive version:
.Limit and torque setting is performed via switches in the actuator.
Non-Intrusive version:
.Limit and torque setting is performed via the controls, actuator and con-
trols housings do not have to be opened.
For this purpose, the actuator is equipped with an MWG (magnetic limit
and torque transmitter), also supplying analogue torque feedback sig-
nals/torque indication.
8
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual

3 Operation
3.1 Local operation
The local operation of the actuator is performed using the push buttons
(figure 3).
ÒSet selector switch (5) to position Local control (LOCAL).
The actuator can now be operated using the push buttons (1 – 3).
1. Run actuator in direction OPEN: Press push button (1).
2. Stop actuator: Press push button (2).
3. Run actuator in direction CLOSE: Press push button (3).
Information The OPEN - CLOSE operation commands can be given either in
push-to-run operation or in the self-retaining mode.
3.2 Operation from REMOTE
ÒSet selector switch to position Remote control (REMOTE).
Now, it is possible to operate the actuator by remote control via opera-
tion commands (OPEN, STOP, CLOSE) or via analogue setpoint
(e.g. 0 – 20 mA).
Information .Use the MODE input (refer to wiring diagram) to select between REMOTE
MODE (open-close duty) and SETPOINT MODE (modulating duty).
.The FAILURE MODE and EMERGENCY MODE operation modes are set
via parameters.
9
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
1 Push button OPEN 4 Push button Reset
2 Push button STOP 5 Selector switch
3 Push button CLOSE 6 Indication lights/LEDs
0
I
I
0
I
I
1
41
2
3
5
Figure 3

3.3 Menu navigation via push buttons (for settings and indications)
The push buttons of the local controls (figure 4) are used to view, edit, and
show various indications on the display.
ÒSet selector switch (5) to position 0(OFF).
Now, settings and indications can be performed via the push buttons (1 – 4).
3.3.1 Short overview: functions of the push buttons
10
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
1
6
1
2
3
4
5
p
q
8
C
Figure 4
1Push button p4Push button C
2Push button q5 Selector switch
3Push button 86 Display
0
I
I
Push
buttons Functions
pq
Scrolling within a group
(The triangles
in the display show the direction of scrolling.)
Change values
Enter figures from 0 to 9
8Confirm the selection to go to a new menu/subgroup.
C
Cancel process
Return to previous display: press briefly
Change to another group (S, M, D)
- press for approx. 3 seconds until group M0 is displayed.
- hold down for more than 3 seconds until group D0 is displayed
(thereby, group Mis skipped).
Table 1

3.3.2 Structural design and navigation
The indications on the display are divided into 3 groups:
.Group S= status indications
.Group M= menu (settings)
.Group D= diagnostic indications
The active group is displayed on the top right corner of the display.
Change groups Change from group Sto group M:
ÒPress Cpush button and hold it down for approx. 3 seconds until group
M0 appears.
Change from group Sto group D:
ÒPress Cpush button and hold it down until group D0 appears
(group Mis hereby skipped).
Change from any group Mor Dback to group S:
ÒBriefly press C.
Scrolling ÒPress qp:
The triangles
in the top left corner of the display indicate the possible
scrolling direction (within one group) of scrolling.
Enter the password In the menu (group M), the settings are protected by a password.
To change the parameters, a password must first be entered.
The following default password is set in the factory: 0000.
After selecting EDIT, the following is displayed:
1. Select figures 0 to 9: Press qp.
2. Move to the next position: Press 8.
3. Repeat steps 1 and 2 for all four digits.
4. To cancel a process: Press C.
Information If no input is received over a longer period of time (approx. 10 min), the con-
trols automatically returns to the status indication S0.
11
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
ENTER PASSWORD
0***
:EDIT ↵:OK C:ESC
OFF S0
OPEN POSITION
E2 100%
M0
M0
OFF S0
OPEN POSITION
E2 100%

3.4 Operation and setting via AUMA COM-AC programming software
Data from the actuator can easily be imported, exported and settings
changed and saved using the AUMA COM-AC programming software
(option) in combination with a computer.
Depending on the version, the connection between computer and AUMATIC
can be performed with cable (infra-red interface) or without cable (Bluetooth
interface) (not included in these instructions) .
3.4.1 Operation setting via COM-AC
The COM-AC software can transmit the operation commands OPEN, STOP,
CLOSE to the actuator.
ÆVia the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
COM-AC CONTROL (M1P0)
LOCAL CLIENT (M1P10)
Default value: REMOTE AND LOCAL
Description of the parameter settings:
REMOTE AND LOCAL
The actuator can be operated in selector switch position LOCAL CONTROL
or REMOTE CONTROL via the COM-AC with the OPEN, STOP, CLOSE
commands.
LOCAL CONTROL ONLY
The actuator can be operated in selector switch position LOCAL CONTROL via
the COM-AC with the OPEN, STOP, CLOSE commands.
No operation control is possible in selector switch position REMOTE CONTROL.
12
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
3
1 2
Figure 5
1 Infra-red interface 2 Bluetooth interface (option)
3 Bluetooth LED
EDIT M1P10
LOCAL CLIENT
REMOTE AND LOCAL
:EDIT ↵:OK C:ESC

3.5 Password change
The following default password is set in the factory: 0000.
ÆVia the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
CHANGE PASSWORD (M1D)
òStep by step:
1. Set selector switch to position 0(OFF).
2. Press Cand hold down it for approx 3 seconds.
Display indicates:
3. Press q.
Display indicates:
4. Press 8.
Display indicates:
5. Select CHANGE PASSWORD (M1D) using q.
Display indicates:
6. Press 8.
Display indicates:
7. Enter password (see page 11).
13
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
0
I
I
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
SETTINGS M1D
POSITIONER
INTERMED. POSITION
CHANGE PASSWORD
CHANGE PASSWORD M1D0
PASSWORD
0000
↵:EDIT C:ESC

3.6 Language change in the display
ÆVia the menu to parameter:
MAIN MENU (M0)
LANGUAGE/CONTRAS (M00)
LANGUAGE (M010)
Default value: GERMAN
Setting range: GERMAN, PORTUGUESE, ITALIAN, SPANISH,
FRENCH, ENGLISH, TUERKCE, POLSKI, MAGYAR
3.7 LCD contrast setting of the display (applies only to controls with green display)
To improve the legibility of the display under unfavourable lighting condi-
tions, the contrast may be adjusted.
This setting is only possible for green displays. The contrast setting has no
effect on the blue display.
ÆVia the menu to parameter:
MAIN MENU (M0)
LANGUAGE/CONTRAST M00)
LCD CONTRAST (M011)
Default value: 80 %
Setting range: 0%to 100 %
Information Alternatively, the LCD contrast can be set as follows:
1. Press Cand hold it down.
The menus S,M,Dare skipped.
After approximately 10 seconds, the LED display will continuously
change from bright to dark and vice versa.
2. Release push button
The current brightness level is saved.
14
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
EDIT M010
GERMAN
ENGLISH
:EDIT ↵:OK C:ESC
EDIT M011
LCD CONTRAST
30 %
:EDIT ↵:OK C:ESC

4 Indications
4.1 Status indications in the display
The status indications on the display locally indicate the current operation
states in plain text or as bar chart.
Table of contents:
4.1.1 Status indication S0/S6 - operation
4.1.2 Status indication S4 - torque
Further information on this topic:
For status indications regarding faults and warnings, refer to pages 74 et seqq.
4.1.1 Status indication S0/S6 - operation
Information For actuators equipped with active process controllers in the logic
sub-assembly, status indication S6 is displayed instead of status indication
S0 in selector switch position REMOTE. The description below applies to
both indications (S0 and S6).
Operation mode display Line 1 indicates the current operation mode (LOCAL MODE, OFF,
SETPOINT MODE, ...)
Operation command/
setpoint display
Line 2 indicates currently incoming operation commands
(OPEN, STOP, CLOSE) or the setpoint E1 in % of the total travel.
Valve position display Line 3 indicates the valve position in % of the travel.
This indication is only available if the actuator is equipped with a position
transmitter.
0 % = Actuator is in end position CLOSED
100 % = Actuator is in end position OPEN
End position/running indication Line 4 indicates the current actuator status.
ÈDescription of indications in line 4:
RUNNING OPEN
Actuator runs logically OPEN (remains set during operation pauses).
15
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
LOCAL MODE S0
OPEN
E2 1-+
00 %
LOCAL MODE S0
OPEN
E2 100%
RUNNING OPEN
LOCAL MODE S0
OPEN
E2 100%
RUNNING OPEN

RUNNING CLOSE
Actuator runs logically CLOSE (remains set during operation pauses).
OPEN POSITION
End position OPEN reached.
CLOSED POSITION
End position CLOSED reached.
SETPOINT POSITION
Setpoint (modulating actuators only).
ÈDescription of the fault signals:
See page 74.
4.1.2 Status indication S4 - torque
This indication is only available if the actuator is equipped with an MWG
(magnetic limit and torque transmitter); refer to page 8.
A deflection to the left side indicates torque in direction CLOSE.
A deflection to the right side indicates torque in direction OPEN.
Example: SA 07.5 with 20 – 60 Nm
100 % corresponds to 60 Nm of the nominal torque.
50 % corresponds to 30 Nm of the nominal torque.
4.2 Torque indication: edit
The torque value can be displayed in percent, Newtonmeter (Nm) or in
Lbs/ft.
ÆVia the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
TORQUE INDICATION (M1317)
Default value: NEWTONMETER
ÈDescription of the parameter settings:
PERCENT
Indication of the nominal torque in percent
NEWTONMETER
Indication in Nm
LBS.FT.
Indication in Lbs./ft.
16
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
TORQUE S4
TORQUE 50 %
EDIT M1317
TORQUE INDICATION
NEWTONMETER
:EDIT ↵:OK C:ESC

4.3 Electronic name plate
The electronic name plate provides information about the order data (impor-
tant for enquiries in the factory)
Table of contents:
4.3.1 Display indication: enable view
4.3.2 Electronic name plate: view
4.3.1 Display indication: enable view
The EL. NAME PLATE setting must be set to VIEW ENABLED:
ÆVia the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SPECIAL FUNCTIONS (M40)
EL. NAME PLATE (M4013)
Default value: VIEW ENABLED
ÈDescription of the parameter settings:
VIEW NOT ENABLED
The electronic name plate is not shown in the display.
VIEW ENABLED
The electronic name plate is shown in the display.
4.3.2 Electronic name plate: view
ÆVia the menu to parameter:
MAIN MENU (M0)
EL. NAME PLATE (M3)
ORDER DATA (M30)
PRODUCT DATA (M31)
PROJECT DATA (M32)
SERVICE DATA (M33)
17
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
EL.NAME PLATE M30
ORDER DATA
PRODUCT DATA
PROJECT DATA
EDIT M4013
EL. NAME PLATE
VIEW ENABLED
:EDIT ↵:OK C:ESC

Project and user specific data are freely definable and can be entered by
the user:
Service information such as the AUMA service phone number and the
AUMA Internet address can be indicated here:
18
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
Order data (M30)
COMMISS NO.AUMATIC set in the factory
COMMISS NO.ACTUATOR set in the factory
KKS NO. set in the factory
VALVE NO. adjustable
PLANT NO. adjustable
Product data (M31)
PRODUCT TYPE set in the factory
WORKS NO. ACTUATOR set in the factory
WORKS NO. AUMATIC set in the factory
LOGIC SFTWR. VER. software version of the logic, set in the factory
LOGIC HRDWR. VER. hardware version of the logic, set in the factory
DATE OF FINAL TEST set in the factory
WIRING DIAGRAM set in the factory
TERMINAL PLAN set in the factory
Table 2
Project data (M32)
PROJECT NAME adjustable (fields for customer input)
CUSTOMER FIELD 1 adjustable (fields for customer input)
CUSTOMER FIELD 2 adjustable (fields for customer input)
Table 3
Service data (M33)
SERVICE PHONE set in the factory
INTERNET ADDRESS www.auma.com, set in the factory
SERVICE TEXT 1 can only be changed by service technician
SERVICE TEXT 2 can only be changed by service technician
Table 4

4.4 Indication lights/LEDs
The indication lights/LEDs locally display the different operation states as
optical signal. The assignment of signals is freely selectable.
Table of contents:
4.4.1 Standard indication
4.4.2 Configuration of the signals: view/edit
4.4.3 Blinking behaviour of indication lights/LEDs: view/edit
4.4.1 Standard indication
Figure 6 shows the indication lights/LEDs on the local controls:
Table 5 describes the standard indication.
Information The behaviour (blinking/illuminated) can be changed via the BLINKER
parameter.
19
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
LED 1 (left)
( symbol)
illuminated Actuator is in end position CLOSED
blinking Running indication: Actuator runs in direction
CLOSE
LED 2 (T) illuminated Torque fault CLOSE
LED 3 (Th) illuminated Motor protection tripped
LED 4 (T) illuminated Torque fault OPEN
LED 5 (right)
( symbol)
illuminated Actuator is in end position OPEN
blinking Running indication: Actuator runs in direction
OPEN
LED 6 (BT)
(option) illuminated Bluetooth connection available
Table 5
Figure 6
Version (standard): Version (option):
LED marking with letters LED marking with figures

4.4.2 Configuration of the signals: view/edit
ÆVia the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
LED 1 (LEFT HAND) (M1312)
LED 2 (M1313)
LED 3 (M1314)
LED 4 (M1315)
LED 1 (RIGHT HAND) (M1316)
Default values: LED 1 (LEFT HAND) = CLOSING BLINK
LED 2 = TORQUE FAULT (CLOSE)
LED 3 = THERMO FAULT
LED 4 = TORQUE FAULT (OPEN)
LED 5 (RIGHT HAND)= OPENING BLINK
Information Table 8, page 23 describes the signals which can be assigned to the LEDs.
Table 8 applies to both the LEDs and the output contacts.
20
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual
EDIT M1312
LED 1 (LEFT HAND)
CLOSING BLINK
:EDIT ↵:OK C:ESC
Other manuals for Aumatic AC 01.1
4
This manual suits for next models
1
Table of contents
Other AUMA Controllers manuals

AUMA
AUMA SA 07.2 User manual

AUMA
AUMA SVCR 05.1 User manual

AUMA
AUMA GSTI Series User manual

AUMA
AUMA SAEx Series User manual

AUMA
AUMA AM 01.1 Manual

AUMA
AUMA SA 07.1 User manual

AUMA
AUMA SAExC 07.1 User manual

AUMA
AUMA PROFOX PF-M100X User manual

AUMA
AUMA AC 01.2-22X User manual

AUMA
AUMA SQVEx 05.2 User manual