Automated Logic M220NX Owner's manual

Automated Logic Corporation •1150 Roberts Blvd. •Kennesaw, GA 30144 • 770/429-3000 •770/429-3001 Fax •
www.automatedlogic.com • Copyright 2000 Automated Logic Corporation. All rights reserved. Automated Logic, the
Automated Logic logo, SuperVision, Eikon, and Alert are registered trademarks of Automated Logic Corporation.
InterOp is a trademark of Automated Logic Corporation. BACnet®is a registered trademark of ASHRAE. All other brand
and product names are trademarked by their respective companies.
Technical Instructions
M220nx
Using the M220nx 2
Specifications 3
Mounting 3
Addressing 3
Power Wiring 3
CMnet Communications 4
Using the M220nx on an ARC156 CMnet 4
Using the M220nx on a 9600 or 38.4K bps CMnet 4
To connect the M220nx to the CMnet 5
Communicating with the Workstation 5
Inputs 5
Digital Outputs 7
Channel Numbers 7
Transferring Memory 8
Troubleshooting 8
Formatting the Module 8
LEDs 8
Protection 9
Production Date 9

Revised 4/3/00 • M220nx 2 © 2000 Automated Logic Corporation
Using the M220nx
The M220nx is a general purpose controller
that can be used for a variety of applications.
TheM220nxispartoftheM-Line,which
allows a complete HVAC control system to be
built a piece at a time.
The M-Line consists of several general
purpose controllers that provide different
input and output point combinations. The
M220nx has
•two digital outputs
•two universal inputs
TheM220nxprovidesthecommunications
circuitry, non-volatile memory, and
removable screw terminals for I/O
connections.
The M220nx uses a 6.00g or later version of
the M2M Module Driver; for more
information, see the M2M Module Driver
document on the Automated Logic website at
www.automatedlogic.com.
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user’s authority to operate equipment.
NOTE This equipment has been tested and
found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
radio communications. Operation of this
equipment in a residential area is likely to
Figure 1. Module Dimensions and Layout
5RWDU\ $GGUHVV
3RZHU 6ZLWFK
$FFHVV 3RUW
71/2"
19.05cm
87/8"
22.5cm
23/4"
7cm
11/4"
3.2cm
1/4"
0.6cm
)RUPDW %XWWRQ
1
2
3
4
IN-1
IN-2
B
A
B
A
net
CM ARC156
Source Only
UseSingleClass2
B - Gnd/Loop Power
A - Input Signal
Shield
Over ARCNET156 KBaud
TM
BACnet
38.4k 9600
Comm Select
Baud Select
0-20 mA
0-5Vdc
dry-contact
Thermistor/
Mode Select
Universal Input
Access Port
Net -
Net +
Tx
Rx
Different Class 2 Circuits.
Interconnect the Outputs of
or Electrical Shock, Do Not
To Reduce the Risk of Fire
Caution:
3A Max.
24V Max.
Conductors Only
Use Copper
20VA, 0.83A
50-60 Hz
24Vac
Class 2
Format
Address
Module
10's 1's
Error
Run Power
Auto Off On
Power
On Off
24Vac
Gnd
E143900
TYPE: 006104
88FO
R
Management Equipment
Open Energy
1
2
3
4
DO-1
DO-2
CONTROL MODULE
M220NX
+2$
6ZLWFKHV
net
CM N/C
%DXG 6HOHFW
&RPP 6HOHFW
Inputs
5V Max, 20mA Max
*QG DQG 9DF
7HUPLQDOV

Revised 4/3/00 •M220nx 3 © 2000 Automated Logic Corporation
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.
Specifications
Power 24VAC ± 10%, 50-60Hz (24VAC
±10%, 60Hz for UUKL Smoke Control
Systems), 20VA power consumption
(single Class 2 source only, 100VA or
less).
Inputs two universal inputs, configurable
for0-5VDC,0-20mA,orthermistor.
Input Resolution 10 bit A/D.
Digital Outputs two digital outputs, relay
contacts rated at 3A resistive @ 24VAC.
Configured as normally open.
Output Resolution 8bitD/A.
Communication 156 kbps ARCNET, 9600
bps or 38.4 kbps CMnet; twisted pair
wiring.
Environmental Operating Range 0°to
130°F(-17.8°to 54.4°C); 10 to 90%
relative humidity, non-condensing.
Status Indication Visual (LED) status of
CMnet communication, running, errors,
and power. (For UUKL Smoke Control
Systems, 32 to 120.2 °F[0to49°C]; 10 to
85% relative humidity, non-condensing.)
Memory 512KB Flash memory and 512KB
non-volatile battery-backed RAM.
Protection Voltage, current, and ESD
protection on incoming power and
CMnet.
Bat t e ry Seven-year lithium BR2325 battery
provides a minimum of 10,000 hours of
data retention during power outages.
Listed by UL 916 (PAZX), cUL C22.2 No.
205-M1983 (PAZX7), FCC Part 15 -
Subpart B - Class A.
Mounting
Screw the M220nx into an enclosed panel
using the mounting holes provided on the
cover plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.
Addressing
Before setting or changing the address, make
sure the M220nx’s power is off. The M220nx
only reads the address when the module is
turned on. After changing the address, you
must transfer memory to the module. Refer to
“Transferring Memory”on page 8.
The M220nx has two rotary switches for
assigning the module’s CMnet address. One
switch corresponds to the tens digit and the
other corresponds to the ones digit. For
example, if the module’saddressisthree,set
the tens switch to zero and the ones switch to
three, as shown in Figure 2.
Power Wiring
Whenever possible, make sure the module’s
power and communications connections are
working properly before connecting any input
or output points.
CAUTION The M220nx module is a Class 2
device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the M220nx module in a control
panel where non-Class 2 devices (for
example, 120VAC) or wiring are present.
You can power several modules from the
same transformer if you maintain the same
polarity.
Figure 2. Setting the module’s address
10's 1's

Revised 4/3/00 •M220nx 4 © 2000 Automated Logic Corporation
The M220nx has an operating range of
21.6VAC to 26.4VAC. If voltage measured at
the module’s power input terminals is outside
this range, the module may not work
properly.
1. Turn the module’s power off. This
prevents the module from being powered
up before the proper voltage is verified.
2. Make sure the 24VAC power source is off.
3. Connect the power wires to the module’s
power terminals labeled Gnd and 24VAC
(see Figure 1 on page 2 for location).
4. Apply power to the transformer.
5. Make sure that 24VAC is present at the
module’spowerinputterminals.
6. Set the module’s address. Refer to
“Addressing”on page 3 for details about
setting the address.
7. Turn the module’s power switch on.
When the module turns on, the Run and
Power LEDs turn on. The Run LED begins
blinking and the Error LED turns off. See
Table 5 on page 8 to troubleshoot the
LEDs. If the module does not respond,
call Technical Support at (770) 429 3002.
CMnet Communications
A CMnet is a peer to peer network that allows
multiple control modules to communicate
over an EIA-485 standard. A token passing
scheme is used to control access to the
network. A CMnet may be configured as a
legacy CMnet at 9600 bps or 38.4 kbps or an
ARCNET CMnet at 156 kbps. The ARCNET
CMnet configuration provides BACnet
compatibility, as well as better performance
over a legacy CMnet. All modules on a CMnet
must communicate at the same speed.
When communicating at 156 kbps, the CMnet
uses a unique implementation of the industry
standard ARCNET protocol called ARC156.
For a summary of the differences between
ARCNET and ARC156, please refer to the
156K CMnet Wiring Technical Instructions.
Using the M220nx on an ARC156
CMnet
Use the appropriate wire for CMnet
communications. When communicating with
the ARC156 protocol use an A3ARC156 wire
available from:
Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
When the Comm Select jumper is set to
ARC156, the CMnet port is connected to an
ARCNET processor, enabling the M220nx to
communicate on an ARC156 CMnet.
Communication speed is 156 kbps regardless
of the Baud Select jumper setting (see below).
Using the M220nx on a 9600 or
38.4K bps CMnet
Use a dedicated 22AWG to 18AWG twisted
pair wire for legacy CMnet (EIA-485) wiring.
When the Comm Select jumper is set to
CMnet,themodulecommunicatesona
legacy CMnet at the baud rate set by the Baud
Select jumper (see the following diagrams).
NOTE The jumper below the Comm Select
jumper must always be set to CMnet.
CM
net ARC156
Comm Select The module communicates
on an ARCNET CMnet at
156 kbps.
CM
net ARC156
Comm Select The module communicates on
a legacy CMnet at 9600 bps.
Baud Select
960038.4k
CM
net N/C

Revised 4/3/00 •M220nx 5 © 2000 Automated Logic Corporation
To connect the M220nx to the CMnet
1. Turn the M220nx’spowerswitchoff.
2. Set the CMnet mode (legacy or ARC156
CMnet) using the Comm Select jumper.
3. If communicating on a legacy CMnet, set
the Baud Select jumper for either 9600 bps
or 38.4 kbps.
4. ChecktheCMnetwiringforshortsand
grounds.
5. Connect the CMnet communication wires
to the M220nx CMnet terminals (see
Figure 1 on page 2 for location). Follow
the same polarity used throughout the rest
of the CMnet.
6. Turn the M220nx’spowerswitchon.
Communicating with the
Wo r k s tat i o n
You can connect a workstation or portable
computer directly to the M220nx module
using an APT and the module’sAccessport
(see Figure 3). This type of connection can be
used to troubleshoot the module or transfer
memory. If you are using an ARC156 CMnet,
you can receive colors while connected to a
module’sAccessportifagatewaymoduleis
on the CMnet. You cannot receive alarms
through the Access port, however.
The Access Port’sbaudrateisdeterminedby
the Baud Select jumper on the module.
1. Connect the computer’s serial port to the
EIA-232 port of the APT using a standard
straight-through serial cable.
2. Set the APT’s Mode Select switch.
•On an ARC156 CMnet, use the TTL
setting.
•On a legacy CMnet, use the 485 setting.
3. Connect the Access Port of the APT to the
Access Port of the module.
4. In SuperVision, define the connection type
using Table 1.
Inputs
TheM220nxmodulehastwouniversalinputs
to accept the types of signals listed below.
RefertoTable2onpage6forinformation
about wire length, gauge, and shielding.
•Thermistor: Precon type 2 (10kohm at
77°F). Input voltages should range
between 0.489V and 3.825V for
thermistors.
CM
net ARC156
Comm Select The module communicates on
a legacy CMnet at 38.4 kbps.
Baud Select
960038.4k
CM
net N/C
Figure 3. Using the Access Port
Table 1. Connection Types
SuperVision
Version
Type of
CMnet
Gateway
Present?
Use Connection
Type
3.0 any n/a Access Port
2.6 ARC156 yes Direct Connect
2.6 ARC156 no Direct Network
2.6 legacy n/a Direct Network
9
Rx
61
2- Tx out
3- Rx in
5- Gnd
1,6,8- +10V or floating
Tx +5V
APT
5
Exec. 4 relay
Isolate Network
Mode Select
TTL 485
ACCESS
PORT
EIA-232
Port
Mode Select
Switch
Exec. 4 relay
Switch
Access
Port
COR P O R ATION
OGIC
L
UTOM ATED
A
Over A RC NE T15 6 K Bau d
TM
BAC net
Format10's 1's
Error
Ru n Pow er
Auto Off On
CONTROLM ODULE
M220NX

Revised 4/3/00 •M220nx 6 © 2000 Automated Logic Corporation
•0to5VDC:Theoutputimpedanceofa0
to 5VDC source must not exceed
10kohms. The input impedance of the
M220nx is approximately 1Mohm.
•0 to 20mA: The input resistance on the
“A”input is 250 Ohms. The “B”terminal
supplies a voltage source to power the
4-20mA transducer. The “B”terminal is
capable of supplying 18 to 24VDC, but
the total current of both “B”terminals
must not exceed 40mA. If the voltage
measured from the “B”terminal to Gnd
is less than 18VDC, you need to use an
additional external power supply.
•Dry Contact: A 5VDC wetting voltage is
used to detect contact position. This
results in a 0.5mA maximum sense
current when the contacts are closed.
The M220nx accumulates up to ten input
pulses per second.
1. Be sure the M220nx’s power is off before
wiring any inputs or outputs.
2. Connect the input wiring to the screw
terminals on the module as shown in
Figure 4.
NOTE If a 4-20 mA sensor uses an
external 24VAC power supply, connect
one leg of the 24VAC supply to the module
ground.
3. Set the configuration jumper for each
input to indicate the type of input used.
Make sure the jumper is positioned
correctly, and be sure to grip the jumper
by the sides only. See Figure 5 on page 7.
4. For each input, enter the channel number,
offset, and gain on the Function Block’s
Parameter page in SuperVision. Valid
channel numbers are listed in “Channel
Numbers”on page 7.
5. To verify each input’s operation, have
each sensor create a known value and
Table 2. Input wiring restrictions
Input
Maximum
Length
Minimum
Gauge Shielding
0to5VDC 50feet
15 meters
24AWG shielded and
grounded to
module’s“B”
or Gnd
terminal
Thermistor
Dry contact
50 feet
15 meters
24AWG shielded and
grounded to
module’s“B”
or Gnd
terminal
0 to 20mA 150 feet
46 meters
20AWG unshielded
Figure 4. Input Wiring
PWR
PWR
PWR
OUT
OUT
GND
GND
GND
0-5VDC
DRY
CONTACT
PASSIVE
TRANSDUCER
4-20mA
12V or 24V
LOOP INPUT
THERMISTOR
3WIRE
4-20mA
ISOLATED AC
or DC POWER
SUPPLY
4WIRE
4-20mA
OUT +
OUT -
OUT +
OUT - TO MODULE GND
Universal Input
Mode Select
0-5VDC
0-20mA
Thermistor
Dry Contact
Inputs
5V Max, 20mA Max

Revised 4/3/00 •M220nx 7 © 2000 Automated Logic Corporation
compare it to the condition reported on
the FB’s Status page.
Digital Outputs
TheM220nxmodulehastwodigitaloutputs
which can be connected to a maximum of 24
Volts AC/DC. Each output is a dry contact
(rated at 3A maximum) that is normally open.
Be sure the M220nx’s power is off before
wiring any inputs or outputs. Connect the
output wiring to the screw terminals on the
module as shown in Figure 6.
NOTE Donotpowerpilotrelaysfromthe
same transformer that powers the M220nx.
To verify each output’s operation, lock the
output to a known condition using the
Function Block’s Parameter page, then make
sure the equipment actually operates as
specified.
Each digital output can be placed in Manual
or Auto mode by setting the HOA switches
(see Figure 1 on page 2 for the switches’
location). You can monitor the status of the
HOA switches through SuperVision by
assigning each switch a digital input in the FB
using channel numbers 81 and 82.
An off status on these channels means the
HOAswitchisinAutomode.Anonstatus
means the HOA switch is in Manual mode.
Channel Numbers
The following tables show the valid channel
numbers for each point on the M220nx. Enter
the channel number, offset, and gain for each
point in Eikon before the Function Block is
made, or on the FB’s Parameter page in
SuperVision. If an offset and gain are not
provided here, use SuperVision’sPoint
Configuration or Point Help feature to
determine the offset and gain.
Figure 5. Jumper Position
Figure 6. Digital Output Wiring
Grip
Here
0-20 mA
0-5 VDC
Thermistor/
dry-contact
Universal Input
Mode Select
DRY
CONTACT
24VAC
B
A
B
A
Table 3. Input Channel Numbers
Point Signal Type Channel
Number †Range Offset Gain
UI 1
Thermistor 31 -17° to 213° F
-27° to 100.6° C 0.00
0.00 15.88
15.69
mA or Volts 31 0 to 20mA
0to5V §§
Digital 21
UI 2
Thermistor 32 -17° to 213° F
-27° to 100.6° C 0.00
0.00 15.88
15.69
mA or Volts 32 0 to 20mA
0to5V §§
Digital 22
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User’s Guide for more information.
§ Use the Point Configuration or Point Help feature in SuperVision v2.0 or
later.
Table 4. Digital Output Channel Numbers
Point Signal Type Channel
Number
DO 1 Digital
HOA Status† 11
81
DO 2 Digital
HOA Status† 12
82
† Use a digital input microblock to
monitor the status of HOA Switches.

Revised 4/3/00 •M220nx 8 © 2000 Automated Logic Corporation
Transferring Memory
TheM220nxmodulecanstoreupto14
Function Blocks (FBs) and the M2M module
driver. If you have any problems transferring
memory to the module, contact Technical
Support at (770) 429 3002.
1. Log in to SuperVision on a workstation
connected to the CMnet. You can also
connect directly to the module using the
Access Port; see “Communicating with the
Workstation”on page 5.
2. Navigate to the module driver and look at
the module status report in SuperVision to
make sure the module type and number
agree with the module.
•To view the module status report in
SuperVision v3.0, click Tools-
Troubleshooting-Module Status.
•To view the module status report in
SuperVision v2.6b, press the Esc key,
type MO , , module address,15
and press Enter.
3. Transfer memory to the module.
•In SuperVision v3.0, click Tools-
Troubleshooting-Transfer Memory to
Module.
•In SuperVision v2.6b, choose Download
Memory for This Module.
4. When the memory transfer is finished,
check the module status report again.
Make sure the FB List on this page shows
all the FBs you intended to transfer.
Troubleshooting
Formatting the Module
When you are unable to communicate with a
module, you can, as a last resort, manually
format the module to try to restore
communication. Formatting the module
erases all memory, so you need to transfer
memory back to the module once it is
formatted.
1. Turn the module’s power off. Make sure
the module’saddressswitchesarenotset
to ’0,0’.
2. Press and hold the Format button (see
Figure 1 on page 2 for location).
3. While continuing to hold the Format
button, turn the module’s power on.
4. Continue to hold the button until the Error
LED flashes three times in sync with the
Run LED.
5. Release the Format button.
6. Transfer memory to the module. Refer to
“Transferring Memory”.
LEDs
The M220nx module has several LED
indicators to show the status of certain
functions. Table 5 explains the Run and Error
LED signals in detail to assist troubleshooting.
Table 5. LED Signals
Run LED Error LED Condition
2flashes
per second
Off Normal
2flashes
per second
1 flash per
second
Normal, but module is
alone on the CMnet
2flashes
per second
2flashes
alternating
per second
Five minute auto-restart
delay after system error
2flashes
per second
2 flashes in
sync per
second
Module is configured for a
different baud rate than the
rest of the CMnet
2flashes
per second
3flashes
per second
Module has just been
formatted
2flashes
per second
4flashes
per second
Two or m ore items in the
database have the same
ARC156 CMnet address
2flashes
per second
On Exec halted after frequent
system errors
5flashes
per second
On Exec start-up aborted, Boot
is running

Revised 4/3/00 •M220nx 9 © 2000 Automated Logic Corporation
Power - indicates power is being supplied to
the module.
Rx - lights when the module receives data
from the CMnet.
Tx - lights when the module transmits data
over the CMnet.
Digital Output Status - lights when the digital
output is activated.
Protection
The M220nx module is protected by internal
solid state Polyswitches on the incoming
power and CMnet. These Polyswitches are
not replaceable and will reset themselves if
the condition that caused the fault returns to
normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in SuperVision. Refer to
the SuperVision User’s Guide for more
information about the module status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next three characters show the year, month,
and week of manufacture. (The month digit is
in hexadecimal.)
5flashes
per second
Off Firmware transfer in
progress
7flashes
per second
7flashes
per second
Ten second recovery
period after brownout
14 flashes
per second
14 flashes
per second
Brownout
Table 5. LED Signals (Continued)
Run LED Error LED Condition
Table of contents
Other Automated Logic Control Unit manuals

Automated Logic
Automated Logic LGE Owner's manual

Automated Logic
Automated Logic UNI/32 Owner's manual

Automated Logic
Automated Logic S6104 Owner's manual

Automated Logic
Automated Logic R683 Owner's manual

Automated Logic
Automated Logic InterOP8500 Owner's manual

Automated Logic
Automated Logic G4106 Owner's manual

Automated Logic
Automated Logic U253 Owner's manual

Automated Logic
Automated Logic UNI/16 Owner's manual

Automated Logic
Automated Logic T-Line Series Owner's manual

Automated Logic
Automated Logic UNI/59 Owner's manual