Automated Logic LGE Owner's manual

Automated Logic Corporation •1150 Roberts Blvd. •Kennesaw, GA 30144 • 770/429-3000 •770/429-3001 Fax •
www.automatedlogic.com • Copyright 1999 Automated Logic Corporation. All rights reserved. Automated Logic, the
Automated Logic logo, SuperVision, Eikon, and Alert are registered trademarks of Automated Logic Corporation.
InterOp is a trademark of Automated Logic Corporation. BACnet®is a registered trademark of ASHRAE. All other brand
and product names are trademarked by their respective companies.
Technical Instructions
LGE
Using the LGE 2
Specifications 3
Mounting 3
Addressing 3
LGnet Addressing 3
IP Addressing 4
Wiring 5
Power Wiring 5
Communications Wiring 5
Transferring Memory 6
Troubleshooting 6
Communicating with the Workstation 6
Formatting the Module 7
LEDs 8
Protection 8
Production Date 8

Revised 12/22/99 • LGE 2 © 1999 Automated Logic Corporation
Using the LGE
The LGE is a gateway module that provides
communication between a workstation and a
control module network (CMnet) consisting of
fewer than 100 modules. Up to 199 gateways
can be networked together on an LGnet,
allowing the LGEs to route global information
between CMnets. Note that versions of
SuperVision earlier than 3.01 do not support
more than 60 gateways.
The LGE provides an Ethernet 10base-T port
for 10Mbps communication with the LGnet,
one console port that can be connected to a
workstation or portable computer, and an
Access Port. The console port has a 9-pin
connector that can be used to connect to a
workstation, portable computer, or modem.
TCP/IP (Transmission Control Protocol/
Internet Protocol) is a family of protocols used
for computer communications. The LGE uses
the UDP/IP (User Datagram Protocol/Internet
Protocol) of the TCP/IP family. The
workstation must be configured to
communicate with the LGE over TCP/IP as
discussed in the document TCP/IP Setup for
SuperVision.
The LGE uses the CEM module driver; for
more information, see the CEM Module Driver
document on the Automated Logic website at
www.automatedlogic.com.
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user’s authority to operate equipment.
NOTE This equipment has been tested and
found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
Figure 1. Module dimensions and layout
6"
15.2cm
1"
2.54cm
1/5"
0.5cm
7 1/20"
17.9cm
Console transmit
Console receive
Error
CMnet transmit
CMnet receive
Power
Run
Link
Lan
9600/38.4k baud
Default/Assigned
ARC156/Legacy
LGnet Address
Port
Access
Keypad/Display
Port
Console Port
n/c
EIA-232
Ethernet
OnOff
Ground
24 Vac
Power
Format
LGnet
Address
10's
1's
UTOMATED
CORPORATION
A
OGIC
L
Management Equipment
TYPE: 03305
E143900
88FO
R
Open Energy
LGE
CMnet
Connection
Over ARCNET156 KBaud
BACnet
TM
10 baseT
Legacy
IP Ad dr
+0 / +100
Source Only
Single Class 2
24 Vac
50-60 Hz
7.2VA
0.3A
Use Copper
Conductors
Only
Shield
Net -
Net +
01
3
4
5
2
7
89
6
01
3
4
5
2
7
89
6
n/c
n/c
n/c
+10v 3
8
94
5
7
62
1
tx
dtr
sig gnd
rx
dcd
!

Revised 12/22/99 •LGE 3 © 1999 Automated Logic Corporation
reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
radio communications. Operation of this
equipment in a residential area is likely to
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.
Specifications
Power 24VAC ±10%, 0.3A 50-60Hz, 7.2VA
power consumption (single Class 2
source only, 100VA or less).
Communications LGnetPortwithEthernet
10base-T (10Mbps). EIA-485 CMnet port,
twisted pair, selectable for 156 kbps, 38.4
kbps, or 9600 bps. One Console Port for
direct connect or modem. One Access
Port for direct network using an APT. One
Keypad/Display Port (Auxiliary Device
Port).
Environmental Operating Range 0to
130°F(-17.8to54.4°C); 10 to 90% relative
humidity, non-condensing.
Status Indication Visual (LED) status of
CMnet, Console Port 1 and Ethernet
communications, errors, running, and
power.
Memory 1MBflash,1MBRAM.
Protection Built-in surge and transient
protection circuitry.
Bat t e ry 7-year lithium BR2325 battery
provides a minimum of 10,000 hours of
data retention during power outages.
Listed By UL 916 (PAZX), cUL C22.2
No.205 - M1983 (PAZX7), FCC Part 15-
Subpart B - Class A.
Mounting
Screw the LGE into an enclosed panel using
the mounting holes provided on the cover
plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.
Addressing
LGnet Addressing
The LGE has two rotary switches and a DIP
switch used to assign the LGE’sLGnet
address. One rotary switch corresponds to the
tens digit and the other corresponds to the
ones digit. DIP switch four corresponds to the
100s digit.
For example, if the LGE’s LGnet address is 3,
set DIP switch four to zero (see Figure 2), the
rotary tens switch to zero, and the rotary ones
switch to three (see Figure 3).
NOTE SuperVision v2.6 and some gateways
may not recognize an LGE if its address is
higher than 60. However, LGEs recognize
gateways with addresses from 1 to 199.
Figure 2. DIP Switches
Figure 3. Setting the Module’s Address
9600/38.4k baud
Default/Assigned
ARC156/Legacy
LGnet Address
+0/+100
Legacy
IP Addr
1
2
3
4
10's 1's

Revised 12/22/99 •LGE 4 © 1999 Automated Logic Corporation
Before setting or changing the address, make
sure the LGE’s power is off. The LGE only
reads the address when the module is turned
on. After changing the address, you must
transfer memory to the module. Refer to
“Transferring Memory”on page 6.
IP Addressing
TCP/IP must be set up on the workstation
with an active IP address before configuring
the module’s IP address (refer to TCP/IP Setup
for SuperVision for a detailed procedure).
You can use a default IP address for the LGE
that is created by the module, or assign an IP
address if required by the customer. The IP
Addr switch (see Figure 2 on page 3)
determines which IP address is used.
•Default: When the IP Addr DIP switch
is set to Default, the following IP
networking parameters are
automatically set on the CEM Parameter
page:
IP Address = 192.168.168.XXX, where
XXXistheLGE’s LGnet address (see
“LGnet Addressing”on page 3).
Subnet Mask = 255.255.255.0
D e fau lt G at e way A d d r e s s =
19 2 . 168.168.254
NOTE The default gateway address is
an intranet address. This means that
data packets from this address are
dropped by all internet routers and are
not sent beyond the local network
segment.
•Assigned: When the IP Addr DIP
switch is set to Assigned, you must set
the above parameters on the CEM
Parameter page.
Use the following procedure to set the IP
address when using the Default mode:
1. SettheIPAddrDIPswitchtoDefault.
2. Turn the LGE’s power on.
3. If using SuperVision v2.6, edit your HOSTS
file to include the following line for each
gateway (see TCP/IP Setup for SuperVision
for a detailed procedure):
192.168.168.x
Wherexisthegateway’saddressas
defined in “LGnet Addressing”on page 3.
4. If using SuperVision v2.6, run Setup.exe
on the disk shipped with your LGE.
This setup copies updated Portman files to
your emsys folder.
5. Configure the connection as Network in
SuperVision Plus v3.01 or NetBIOS in
SuperVision v2.6.
Use the following procedure to set the IP
address when using the Assigned mode:
1. ObtainanIPaddressfromthejobsite’s
Network Administrator.
2. Establish communication with the LGE
through SuperVision using one of the
connection types in Table 1.
3. Enter the following information, provided
by the Network Administrator, on the CEM
Parameter page:
•the Assigned IP Address
Table 1. Connecting with the Workstation
Port Cable
SuperVision
v3.01
SuperVision
v2.6
Ethernet 10baseT Network NetBIOS
Access Port APT Access Port Direct
Network
Console
Port
DC95,DC99,
or APT
Direct
Connect
Direct
Connect

Revised 12/22/99 •LGE 5 © 1999 Automated Logic Corporation
•the Assigned Subnet Mask
•the Default Gateway Addr
4. Log out of SuperVision and set the IP Addr
DIPswitchtoAssigned.
5. Turn the LGE’s power on.
6. If using SuperVision v2.6, edit your HOSTS
file to include the following line for each
gateway (see TCP/IP Setup for SuperVision
for a detailed procedure):
IP Address LGx
Where IP Address is the address assigned
by the Network Administrator and x is the
gateway’s LGnet address.
7. If using SuperVision v2.6, run Setup.exe
on the disk shipped with your LGE.
This setup copies updated Portman files to
your emsys folder
8. Configure your connections page for
Network in SuperVision Plus v3.01 and
later, or NetBIOS in SuperVision v2.6.
Wiring
Power Wiring
The LGE has an operating range of 21.6VAC to
26.4VAC. If voltage measured at the module’s
power input terminals is outside this range,
the module may not work properly.
CAUTION The LGE module is a Class 2
device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the LGE module in a control panel
where non-class 2 devices or wiring are
present.
You can power several modules from the
same transformer if you maintain the same
polarity.
1. Turn the module’s power off. This
prevents the module from being powered
up before the proper voltage is verified.
2. Make sure the 24VAC power source is off.
3. Connect the power wires to the module’s
power terminals labeled Ground and
24VAC (see Figure 1 for location).
4. Apply power to the transformer.
5. Make sure that 24VAC is present at the
module’spowerinputterminals.
6. Set the module’s LGnet address. Refer to
“Addressing”on page 3 for details about
setting the address.
7. Turn the LGE’s power switch on and verify
that the Run and Error LEDs are blinking.
Verify that the Error LED turns off and the
Run LED continues blinking (see Table 3
on page 8 to troubleshoot the LEDs).
Communications Wiring
When communicating at 156 kbps, the CMnet
uses a unique implementation of the industry
standard ARCNET protocol called ARC156.
For a summary of the differences between
ARCNET and ARC156, please refer to the
ARC156 CMnet Wiring Technical Instructions.
Use the appropriate wire for CMnet
communications. When communicating with
the ARC156 protocol, use an A3ARC156 wire
available from:
Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Use a dedicated 22AWG to 18 AWG twisted
pair (EIA-485) for legacy CMnet wiring. For
more information about CMnet wiring, refer
to the Technical Handbook or to ARC156
CMnet Wiring Technical Instructions.
Connecting to the CMnet
1. Turn off the power.
2. Connect the CMnet wires to the LGE’s
screw terminals as shown in Figure 4 on
page 6. Be sure to follow the same

Revised 12/22/99 •LGE 6 © 1999 Automated Logic Corporation
polarity as used throughout the rest of the
CMnet.
3. Make sure the LGE is configured for the
correct baud rate.
On an ARC156 CMnet (156 kbps), set DIP
switch three to ARC156 (see Figure 2 on
page 3).
If you are using a legacy CMnet (9600 bps
or 38.4 kbps), set DIP switch three to
Legacy, and set DIP switch one to
determine the baud rate (see Figure 2 on
page 3).
Connecting to the LGnet
Connect a LAN 10base-T cable to the
Ethernet port (see Figure 1 on page 2).
Transferring Memory
The LGE uses the CEM module driver. No
other FBs can be added to the LGE. If any
problems occur during this procedure,
contact Technical Support at (770) 429-3002.
Memory transfers that include changing the
module driver or its version number take
longer than other types of transfers.
1. Connect your workstation or portable
computer to the LGE. Refer to
“Communicating with the Workstation”.
2. Navigate to the module driver and look at
the module status report in SuperVision.
Make sure the type is 70 and make sure
the CMnet address agrees with the
module.
•To view the module status report in
SuperVision v3.0, click Tools-
Troubleshooting-Module Status.
•To view the module status report in
SuperVision v2.6b, press the Esc key,
type MO , , module address,15
and press Enter.
3. Transfer memory to the module.
•In SuperVision v3.0, click Tools-
Troubleshooting-Transfer Memory to
Module.
•In SuperVision v2.6b, download
memory for This Module.
4. When the memory transfer is finished,
check the module status report again.
Make sure the FB List on this page shows
all the FBs you intended to transfer.
Troubleshooting
Communicating with the Workstation
The LGE has one console port with a baud
rate of 38.4 kbps that you can use to connect
to a workstation. The console port can
connect directly to the workstation’sserial
port or to a modem, through which you can
dial the workstation. Use the wiring diagrams
in Figure 5 on page 7 to connect the Console
Port to a workstation or a modem.
The Access Port must connect to a
workstation through an APT (see Figure 6).
The Access Port’sbaudrateisdeterminedby
thebaudrateDIPswitchonthemodule(see
Figure 2 on page 3).
Use the following procedure to connect the
Access Port to a workstation.
1. Connect the computer’s serial port to the
EIA-232 port of the APT using a standard
straight-throughcable(seeFigure6).
Figure 4. Wiring the CMnet
CMnet
Connection
Shield
Net -
Net +
# 309

Revised 12/22/99 •LGE 7 © 1999 Automated Logic Corporation
2. Set the APT’s Mode Select switch.
•On an ARC156 CMnet, use the TTL
setting.
•On a legacy CMnet, use the 485 setting.
3. Connect the APT’sAccessPorttothe
module’sAccessPort.
4. In SuperVision, define the connection type
using Table 2.
Formatting the Module
When you are unable to communicate with a
module, you can, as a last resort, manually
format the module to try to restore
communication. Formatting the module
erases all memory, so you need to transfer
memory back to the module once it is
formatted.
1. Turn the module’s power off. Make sure
the module’saddressswitchesarenotset
to ‘00’.
2. Press and hold the Format button (see
Figure 1 on page 2 for location). While
continuing to hold the Format button, turn
the module’s power on.
3. Continue to hold the button until the Error
LED flashes three times in sync with the
Run LED.
4. Release the Format button.
5. Transfer memory to the module. Refer to
“Transferring Memory”on page 6.
Figure 5. Wiring Diagrams
Figure 6. Using the Access Port
*DTR 4
GND 5
*DCD 1
RX 2
TX 3
Console Port
(9 pin)
1 DCD*
5GND
4DTR*
3TX
2RX
Workstation
(9 pin)
*DCD 1
GND 5
*DTR 4
TX 3
RX 2
Console Port
(9 pin)
20 DTR*
7GND
8DCD*
3RX
2TX
Workstation
(25 pin)
*DCD 1
*DTR 4
TX 3
RX 2
GND 5
Console Port
(9 pin)
*DSR 6
*RI 9
**CTS 8
**RTS 7
8 DCD*
20 DTR*
2TX
3RX
7GND
Modem
(25 pin)
6DSR*
22 RI*
5CTS**
4RTS**
* Wire connection usually not needed
** Needed only if hardware handshaking is used
9
Rx
61
2-Tx out
3-Rx in
5-Gnd
1,6,8-+10V orfloating Tx +5V
APT
5
Exec . 4 relay
Isolate Network
ModeSelect
TTL 485
ACCESS
PORT
EIA-232
Port
Mode Select
Switch
Exec.4 relay
Switch
Access
Port
G round
24 V ac
Optiona l
She ild
Net -
Net +
LGE
Table 2. Connection Types
SuperVision
Version
Typ e o f
CMnet Use Connection Type
3.0 any Access Port
2.6 ARC156 Direct Connect
2.6 legacy Direct Network

Revised 12/22/99 •LGE 8 © 1999 Automated Logic Corporation
LEDs
The LGE has several LED indicators to show
the status of certain functions. Table 3 on
page 8 explains the Run and Error LED
signals in detail to assist troubleshooting. See
Figure1onpage2forlocationofLEDsignals.
Power - indicates power is being supplied to
the module.
CMnettransmit-indicatesthattheLGEis
transmitting data over the CMnet.
CMnet receive -indicates that the LGE is
receiving data from the CMnet.
Console transmit - indicates that the Console
Port is transmitting data.
Console receive - indicates that the Console
Port is receiving data.
Link- indicates communication through the
Ethernet port.
Lan - blinks to indicate network activity.
Protection
The LGE is protected by internal solid state
Polyswitches on the incoming power and
network lines. These Polyswitches are not
replaceable and will reset themselves if the
condition that caused the fault returns to
normal.
Production Date
To determine when a module was
manufactured, check the Module Status
report in SuperVision. Refer to the SuperVision
User’s Guide for more information about the
Module Status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next three characters show the year, month,
and week of manufacture. (The month digit is
in hexadecimal.)
Table 3. LED Signals
Run LED Error LED Condition
2flashes
per second
Off Normal
2flashes
per second
1 flash per
second
Normal, but module is
alone on the CMnet
2flashes
per second
2flashes
alternating
per second
Five minute auto-restart
delay after system error
2flashes
per second
2 flashes in
sync per
second
Module is configured for a
different baud rate than the
rest of the CMnet
2flashes
per second
3flashes
per second
Module has just been
formatted
2flashes
per second
4flashes
per second
Two o r more i tem s in the
database have the same
ARC156 CMnet address
2flashes
per second
On Exec halted after frequent
system errors
5flashes
per second
On Exec start-up aborted, Boot
is running
5flashes
per second
Off Firmware transfer in
progress
7flashes
per second
7flashes
per second
Ten second recovery
period after brownout
14 flashes
per second
14 flashes
per second
Brownout
Table of contents
Other Automated Logic Control Unit manuals

Automated Logic
Automated Logic UNI/59 Owner's manual

Automated Logic
Automated Logic UNI/32 Owner's manual

Automated Logic
Automated Logic M220NX Owner's manual

Automated Logic
Automated Logic S6104 Owner's manual

Automated Logic
Automated Logic U253 Owner's manual

Automated Logic
Automated Logic G4106 Owner's manual

Automated Logic
Automated Logic T-Line Series Owner's manual

Automated Logic
Automated Logic R683 Owner's manual

Automated Logic
Automated Logic InterOP8500 Owner's manual

Automated Logic
Automated Logic UNI/16 Owner's manual