
I-41
LED Display, Single-Phase, Slim, Power Controller
(A)
Photoelectric
Sensors
(B)
Fiber
Optic
Sensors
(C)
Door/Area
Sensors
(D)
Proximity
Sensors
(E)
Pressure
Sensors
(F)
Rotary
Encoders
(G)
Connectors/
Connector Cables/
Sensor Distribution
Boxes/Sockets
(H)
Temperature
Controllers
(I)
SSRs / Power
Controllers
(J)
Counters
(K)
Timers
(L)
Panel
Meters
(M)
Tacho /
Speed / Pulse
Meters
(N)
Display
Units
(O)
Sensor
Controllers
(P)
Switching
Mode Power
Supplies
(Q)
Stepper Motors
& Drivers
& Controllers
(R)
Graphic/
Logic
Panels
(S)
Field
Network
Devices
(T)
Software
Unlike SOFT START which operates only once at supplying power,
this function protects load from the inrush current in the RUN mode.
When reached to the target output value, operation stops.
※
※This function can not be used for ON/OFF control method.
SOFT UP/DOWN [U-T/D-T]
Input correction [INB]
Input slope correction [SPN]
A: SOFT START function nished.
B: SOFT UP function nished.
C: SOFT DOWN function nished.
SOFT START set time SOFT DOWN set time
SOFT UP set time
100
50
0t/2 t Time
It compensates the offset between actual input value and measured
input value.
E.g.) When the input monitoring value is 5% at 4mA in DC4-20mA
control input, setting INB to -5 calibrates the input monitoring
value to 0%.
: Actual input signal (%)
: Input corrected signal (%)
0
050 1007525
100
80
60
40
20
: Actual input signal (%)
: Input corrected signal (%)
Actual input signal [%]
0
050 1007525
100
80
60
40
20
RUN/STOP switching
ON/OFF
RUN/STOP status of the power controller can be
switched with the external RUN/STOP contact.
In the RUN mode, the operation indicator on
the front turns on.
AUTO/MANUAL selection
ON/OFF
Operation mode (auto control/manual control)
of the power controller can be selected with
the external AUTO/MAN contact.
In the manual control mode, the manual
control indicator on the front turns on.
RESET
ON
In the event of system anomalies and
alarms, RESET input restarts the power
controller.(Parameters are not initialized.)
Or, hold the , keys for 2 sec, to operates
RESET.
It compensates the gain of the measured 100% input for actual
100% input value.
Calibrated monitoring value=Monitoring value+ Monitoring value ×SPN
100- SPN
E.g.) When the input monitoring value is 99% at 4mA in DC4-20mA
control input, setting SPN to 1 calibrates the input monitoring
value to 100%.
Actual input signal [%]
Measured input signal [%] Measured input signal [%] Output [%]
This function recognizes the load resistance value automatically.
Turning on this function operates the load with 100% of output for
approx. 3 sec and sets the load resistance value in the product
automatically.
※This is only for feedback control models.
Full load auto recognition [F-L]
Alarm
Type Error Operation Clear alarm
Display
priority
SCR error alarm
※1
SCR
Output stops.
(SCR OFF)
- Re-supply the power.
- RESET
- Switch to STOP mode
1
Overcurrent
alarm※1O-C 2
Fuse break alarm FUS 3
Heatsink
overheat alarm TEM 4
Overvoltage
alarm※1O-V 5
Heater break
alarm※1H-B Continues
operation
Automatically cleared
when returning within
the setting range
6
1) SCR error alarm
Even though output is 0%, if the current of 10% or more of the rated
load current ows for over 3 sec continuously, SCR error alarm
occurs and output stops.
2) Overcurrent alarm [OCU/OCT]
This function protects the load from overcurrent.
If the current ows over the overcurrent alarm setting value and
setting delay time, overcurrent alarm occurs and output stops.
3) Heatsink overheat alarm
When the temperature of a heatsink is over 85℃, heatsink overheat
alarm occurs and output stops.
4) Overvoltage alarm [OVV/OVT]
This function protects the load from overvoltage.
If the current ows over the overvoltage alarm setting value and
setting delay time, overvoltage alarm occurs and output stops.
5) Heater break alarm [HBV]
Comparing the full load resistance value and the current load
resistance value, if the current load resistivity is maintained under
the setting value for over 3 sec continuously, heater break alarm
occurs. Output does not stop and operates normally.
Current load resistivity(%) = Full load resistance value ×100
Current load resistance value
※1:This is only for feedback control models.
※ For models with alarm output, the error message and alarm
indicator ash at the same time, and alarm output turns on.
※ When multiple alarms occur at the same time, the highest priority
error message will be displayed based on priority.