Dual PID Control Temperature Controller
TZN SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※Pleaseobserveallsafetyconsiderationsforsafeandproperproductoperationtoavoidhazards.
※Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution
Failure to follow these instructions may result in personal injury or product damage.
※The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
Ordering Information
TZN 4 S 1 4 R
Item
Digit
Size
Option output
Powersupply
Control
output
RRelay output
SSSR drive output
CCurrent output
4100-240VAC 50/60Hz
1※1Event 1
2Event 1 + Event 2
REvent1+PVtransmission(DC4-20mA)
TEvent 1 + RS485 communication
AEvent1+Event2+PVtransmission(DC4-20mA)
BEvent 1 + Event 2 + RS485 communication
SDIN W48×H48mm
MDIN W72×H72mm
WDIN W96×H48mm
HDIN W48×H96mm
LDIN W96×H96mm
49999(4-digit)
TZN Temperaturecontroller(PIDNewType)
Specications
Series TZN4S TZN4M TZN4W TZN4H TZN4L
Powersupply 100-240VAC 50/60Hz
Allowable voltage range 90 to 110% of rated power voltage
Powerconsumption
Max.5VA(100-
240VAC50/60Hz)
Max.6VA(100-240VAC50/60Hz)
Display method 7-segmentLED(PV:red,SV:green)
Character
size
PV(W×H) 7.8×11.0 mm 8.0×13.0 mm 8.0×10.0 mm 7.8×11.0 mm 9.8×14.2 mm
SV(W×H) 5.8×8.0 mm 5.0×9.0 mm 5.8×8.0 mm 8.0×10.0 mm
Input
type
RTD DPt100Ω,JPt100Ω,3-wire(allowedresistance:max.5Ωperline)
TC K(CA),J(IC),R(PR),E(CR),T(CC),S(PR),N(NN),W(TT)
(allowedresistance:max.100Ωperline)
Analog 1-5VDC ,0-10VDC ,DC4-20mA
Display accuracy F.S. ±0.3% or 3℃,greatervalue
Control
output
Relay 250VAC 3A 1c
SSR Max. 12VDC ±3V 30mA
Current DC4-20mA(loadresistancemax.600Ω)
Option
output
EVENT1 250VAC 1A 1a
EVENT2
-
250VAC 1A 1a
PVtransmission
-
DC4-20mA(loadresistancemax.600Ω)
Communication
-
RS485 communication
Control method ON/OFF,P,PI,PD,PIDF,PIDScontrol
Alarm output hysteresis 1 to 100℃(0.1to100.0℃)variable
Proportionalband(P) 0.0 to 100.0%
Integraltime(I) 0to3,600sec
Derivativetime(D) 0to3,600sec
Controlperiod(T) 1 to 120 sec
Sampling period 0.5 sec
LBA setting 1 to 999 sec
Ramp setting RampUp,RampDown:1to99mineach
Dielectric strength 2,000VAC50/60Hzfor1min(betweeninputandpowerterminals)
Vibration Mechanical
0.75mmamplitudeatfrequency10to55Hz(for1min)ineachX,Y,Zdirectionfor2hours
Electrical
0.5mmamplitudeatfrequency10to55Hz(for1min)ineachX,Y,Zdirectionfor10min
Relay
life cycle
Control output Mechanical:min.10,000,000operations,
Electrical:min.100,000operations(250VAC3Aresistanceload)
Option output Mechanical:min.20,000,000operations,
Electrical:min.500,000operations(250VAC1Aresistanceload)
Insulation resistance Over 100MΩ(at500VDCmegger)
Noise immunity Squareshapednoisebynoisesimulator(pulsewidth1㎲)±2kVR-phase,S-phase
Memory retention Approx.10years(non-volatilesemiconductormemorytype)
Environ
ment
Ambient temp. -10 to 50℃,storage:-20to60℃
Ambient humi. 35to85%RH,storage:35to85%RH
Approval
Weight※1Approx. 226g
(approx.164g)
Approx. 355g
(approx.246g)
Approx. 351g
(approx.232g)
Approx. 474g
(approx.303g)
Input Type and Range
Conguring Input Type
Pleaseconguretheinternalswitchesbeforesupplyingpower.Aftersupplyingpower,configuretheinputtype
[IN-T] in parameter group 2 according to the input type.
●Detachingthecase
Pressthefrontcasethenpullthecasetodetachthecasefromthebody.
Conguretheinternalswitchesasinputtype.
Input type S/W 1 S/W 2
Thermocouple
1 1 mA V
RTD
Analog
Voltage
(0-10VDC,
1-5VDC) 2 2 mA V
Current
(DC4-20mA) 2 2 mA V
Dimensions
Connections
(unit:mm)
(unit:mm)
Size
Series A B C D
TZN4S Min. 55 Min. 62 45.5+0.5
0 45.5+0.5
0
TZN4M Min. 91 Min. 91 68+0.7
0 68+0.7
0
TZN4W Min. 112 Min. 50 92+0.8
0 45.5+0.6
0
TZN4H Min. 50 Min. 102 45+0.6
0 92+0.8
0
TZN4L Min. 98 Min. 106 91+0.5
0 91+0.5
0
●TZN4S
30
73
12
10
4
3.5 10
48
10 79.5
10.5
100
45
●TZN4M
10
72
73
83
67
●TZN4W
96
13 90 10
45
48
●TZN4H
48
13 90 10
90
96
AT
SV2 EV2
EV1
OUT
TEMPERATURE CONTROLLER
ATMD
PV
SV
°C
●TZN4L
96
13 90 10
90
A
C
D
B
45.4
61
3.9
7.4
15 4.5
4.2
41
12.2
48
47.8
61
TZN4S Series TZN4M,TZN4W,TZN4H,TZN4LSeries
BracketPanel cut-out dimensions
●TZN4S ●TZN4M
●TZN4L
EV1 OUT
250VAC 1A 1a
EV2 OUT
250VAC 1A 1a
SV2 IN
Max.5VDC
250㎂
B'
TC
RTD
SENSOR
B
A
-
+
MAIN OUT
SSR Current
12VDC ±3V
30mA Max.
DC4-20mA
Load600ΩMax.
mA
V
- -
+ +
15
14
15
14
MAIN OUT
250VAC 3A 1c
Resistive load
PVOUT
DC4-20mA
H
C
L
-
+
RS485(A+)
RS485(B-) -
+
SOURCE
100-240VAC
50/60Hz 6VA
●TZN4H
SOURCE
100-240VAC
50/60Hz 6VA
EV1 OUT
250VAC 1A 1a
EV2 OUT
250VAC 1A 1a
SV2 IN
Max.5VDC
250㎂
MAIN OUT
250VAC 3A 1c
Resistive load
PVOUT
DC4-20mA
B'
TC
RTD
SENSOR
B
A
H
CL
-
+
RS485(A+)
RS485(B-) -
+
-
+
●TZN4W
EV1 OUT
250VAC
1A 1a
EV2 OUT
250VAC
1A 1a
SV2 IN
Max.5VDC
250㎂
B'
RTD
TC SENSOR
B A
- +
SOURCE
100-240VAC
50/60Hz 6VA
MAIN OUT
250VAC 3A 1c
Resistive load
PVOUT
DC4-20mA
H
C
L
-
-
+
+
RS485
(A+)
RS485
(B-)
MAIN OUT
SSR Current
-
+
V
3
2
12VDC ±3V
30mA Max.
-
+
3
2
mA
DC4-20mA
Load600ΩMax.
MAIN OUT
SSR Current
-
+
V
7
6
12VDC ±3V
30mA Max.
-
+
7
6
mA
DC4-20mA
Load600ΩMax.
MAIN OUT
SSR Current
-
+
V
15
14
12VDC ±3V
30mA Max.
-
+
15
14
mA
DC4-20mA
Load600ΩMax.
MAIN OUT
SSR Current
-
+
V
15
14
12VDC ±3V
30mA Max.
-
+
15
14
mA
DC4-20mA
Load600ΩMax.
SOURCE
100-240VAC
50/60Hz 5VA
EV1 OUT
250VAC
1A 1a
SV2 IN
Max.5VDC
250㎂
MAIN OUT
250VAC 3A 1c
Resistive load
B'
RTD
TC
SENSOR
B
A
H
C
L
+
-
-
+
EV1 OUT
250VAC 1A 1a
EV2 OUT
250VAC 1A 1a
SV2 IN
Max.5VDC
250㎂
MAIN OUT
250VAC 3A 1c
Resistive load
PVOUT
DC4-20mA
SOURCE
100-240VAC 50/60Hz 6VA
H
RS485(A+)
RS485(B-)
C
L
-
-
-
+
+
+
B'
RTD
TC
SENSOR
B
A
-
+
DRW170714AA
Caution
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury
or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles,
railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failuretofollowthisinstructionmayresultinre,personalinjury,oreconomicloss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failuretofollowthisinstructionmayresultinelectricshockorre.
4. Check 'Connections' before wiring.
Failuretofollowthisinstructionmayresultinre.
5. Do not disassemble or modify the unit.
Failuretofollowthisinstructionmayresultinelectricshockorre.
1. When connecting the power input and relay output, use AWG 20(0.50mm2) cable or over and tighten
the terminal screw with a tightening torque of 1.0N.m.
When connecting the sensor input and communication cable without dedicated cable, use AWG
28~16 cable and tighten the terminal screw with a tightening torque of 1.0N.m.
Failuretofollowthisinstructionmayresultinreormalfunctionduetocontactfailure.
2. Use the unit within the rated specications.
Failuretofollowthisinstructionmayresultinreorproductdamage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failuretofollowthisinstructionmayresultinelectricshockorre.
4. Do not use the unit in the place where ammable/explosive/corrosive gas, humidity, direct sunlight,
radiant heat, vibration, impact, or salinity may be present.
Failuretofollowthisinstructionmayresultinreorexplosion.
5. Keep metal chip, dust, and wire residue from owing into the unit.
Failuretofollowthisinstructionmayresultinreorproductdamage.
※ The above specications are subject to change and some model may be discontinued
without notice.
※
Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Input type Decimal point Display Inputrange(℃) Inputrange(℉)
Thermo
couple
K(CA) 1KCaH -100 to 1300 -148 to 2372
K(CA) 0.1 KCaL -100.0 to 999.9 Not supported
J(IC) 1JIcH 0 to 800 32 to 1472
J(IC) 0.1 JIcL 0.0 to 800.0 Not supported
R(PR) 1R PR 0 to 1700 32 to 3092
E(CR) 1ECrH 0 to 800 32 to 1472
E(CR) 0.1 ECrL 0.0 to 800.0 Not supported
T(CC) 1TCcH -200 to 400 -328 to 752
T(CC) 0.1 TCcL -199.9 to 400.0 Not supported
S(PR) 1S PR 0 to 1700 32 to 3092
N(NN) 1NN 0 to 1300 32 to 2372
W(TT) 1U TT 0 to 2300 32 to 4172
RTD
JPt100Ω 1JPtH 0 to 500 32 to 932
JPt100Ω 0.1 JPtL -199.9 to 199.9 -199.9 to 391.8
DPt100Ω 1DPtH 0 to 500 32 to 932
DPt100Ω 0.1 DPtL -199.9 to 199.9 -199.9 to 391.8
Analog Voltage 0 - 10VDC A--1 -1999 to 9999
(displayrangewillvarydependingonthe
decimalpoint.)
1 - 5VDC A--2
Current DC4 - 20mA A--3
ab
<Round>
ab
<Forked>
a Min. 3.5mm Min. 3.5mm
b Max. 7.2mm Max. 7.2mm
※Useteminalsofsizespeciedbelow.
SV setting Parameter group 1 Parameter group 2
+ 3 sec
RUN mode
3 sec
3 sec
3 sec
7. Mode key:enterparametergroup,returntoRUNmode,switchparameters,savesettingvalues
8. Auto-tuning key: hold the key for 3 seconds to start auto-tuning. Hold the key for 5 seconds while auto-
tuning to stop auto-tuning.
9. Setting keys:enterSVchangemode,switchelds,changevalue
(keyinthedottedlineisonlyavailableinTZN4MandTZN4Lmodels)
1. Present value (PV) display (red):
RUNmode:displaysthecurrentvalue(PV)
Setting mode: displays parameters
2. Set value (SV) display (green):
RUNmode:displaysthesetvalue(SV)
Setting mode: displays parameter setting values
3. SV2 operation indicator: turns ON when SV2 is operating
4. Auto-tuning indicator: turns ON when auto-tuning
5. Control output operation indicator: turns ON when
control output is ON. Does not operate when the input
type is current output.
6. Event output indicator: turns ON when the according
event output is ON.
( )key:Switchelds
,key: Change values
key
key
①RUN mode
②SV setting mode
8 9
1
3
2
5
6
4
7
Parameter groups
※Parametersettingorder Parameter group 2 Parameter group 1 SV setting
Theparametersarerelatedtoeachother.Pleasesettheparametersintheorderabove.
※Whenthereisnokeyinputfor60secondswhileinSVsettingmodeorparametergroups,theunitwillreturn
to RUN mode automatically.
● SV setting ※When changing the previous SV of 0℃to 170℃,
Thesettingeldwillblink.
③Complete SV setting
Unit Description
1. SV2 temperature
YoucancontrolanadditionaltemperaturevalueatadesiredrangebyusingSV2.Connectacontactsignal(under
5VDC,250㎂)attheexternalterminal,tooperateintherangewherethesignalturnsON.
Set the SV2 temperature in SV2 temperature [SU-2] in parameter group 1.
SV
SV 2 [SU-2]
External terminal
(SV2IN)
ON
Temperature
Time
E.g.)Theinternaltemperatureofanelectricovenmay
drop rapidly if the door is opened while the oven
ismaintainingaspecictemperature.SetSV2
temperature [SU-2]toahighervaluethanSV,and
inputasignaltotheexternalterminal(SV2IN),to
quickly raise the temperature.
2. Ramp
Therampfunctioncandelaytherateoftemperaturerise/fall.IftheSVvalueischangedduringstabilizedcontrol,
the temperature of the controlled target will rise/fall during ramp up/down time [RAPU,RAPD] of parameter group
1. The ramp function activates when the power is reset or when the SV value is changed during stable control.
※The ramp up/down time [RAPU,RAPD] appear only when the ramp function [RAMP] of parameter group 2 is
set to ON.
●Rampuptime[RAPU]
When delaying the rise of initial control
temperature or changing the SV during
stablecontrol,youcandelaytemperature
rise. Set the ramp up time [RAPU] longer
thanthetemperaturerisetime(tu)when
not using the ramp function.
: Not using ramp function
: Using ramp function
Changed SV
Initial SV
Time
tu tu
Ramp up time
[RAPU]
Ramp up time
[RAPU]
Temperature
●Rampdowntime[RAPD]
Delays declining temperature. Set the
ramp down time [RAPD] longer than the
temperaturedeclinetime(td)whennot
using the ramp function.
: Not using ramp function
: Using ramp function
Changed SV
Initial SV
td Time
Ramp down time
[RAPD]
Temperature
Functions
Com.
speed
Cautions during Use
Major Products
RS485 Communication
ApplicableformodelsthatsupportRS485communication.Pleasereferto' Ordering Information'.
It is used to transmit PVorSV,and/orsettheSV.
Protocol BCC Communication speed 2400,4800,9600bps
Applied standard EIA RS485 Start bit 1-bitxed
Max. connections 31units(address:1to99) Data bit 8-bitxed
Communication method 2-wire half duplex Paritybit None
Synchronization method Asynchronous Stop bit 1-bitxed
Communication distance Within 1.2km
Error Dispaly
Display Description Troubleshooting
OPEN Blinks when input is disconnected. Check input status.
HHHH Blinks when the measured input value is higher than the temperature range. Adjust the value to within
the temperature range.
LLLL Blinks when the measured input value is lower than the temperature range.
Symptoms Troubleshooting
OPEN isdisplayedonthePV
display during operation
Disconnect the power and check the input connection.
Iftheinputisconnected,disconnecttheinputwiringfromthetemperature
controllerandshortthe+and-terminals.Powerthetemperaturecontroller
and check if it displays the room temperature. If it does not display the room
temperature and continues to display OPEN,thecontrollerisbroken.Please
contactourtechnicalsupport.(Inputtypeisthermocouple)
Load(heater,etc.)doesnot
operate during operation
Check the state of the control output indicator on the front panel.
Iftheindicatorisnotworking,checkparametersettings.Iftheindicatoris
working,disconnectthewiringfromtheoutputterminalofthetemperature
controllerandchecktheoutput(replaycontact,SSRdrive,current)
ERR0(error)isdisplayedon
thePVdisplayduringoperation
Indicatesdamagetointernalchipbystrongnoise(2kVAC).
Pleasecontactourtechnicalsupport.Locatethesourceofthenoiseand
devise countermeasures.
Troubleshooting
Parameter group 2
Parameter Default Parameter Default Parameter Default
SU-2 0 P #0 IN-B 0
AL1 10 I 0 REST )0
AL2 10 D 0 RAPU 10
LBA 600 T 20 RAPD 10
AHYS 2 HYS 2 LOC OFF
Parameter Default Parameter Default Parameter Default
IN-T KCaH O-FT HEAT FS-L `00
EU-1 AL-1 UNIT ?C RAMP OFF
EU-2 AL-2 H-SC 1300 BPS 2400
AL-T AL-A L-SC `00 ADRS 01
AtT TVN1 DOT 0 LOC OFF
PIDT PIdS FS-H 1300
Parameter group 1
Factory Default
4. Auto-tuning
Auto-tuning allows the temperature controller to detect the thermal characteristics and response rates of the
controltarget.ItthencalculatesthePIDtimeconstantandsetsthevaluetoallowfastresponseratesandhigh
accuracy. Hold the key for 3 seconds during RUN mode to start auto-tuning. The auto-tuning indicator will
blink.Whenauto-tuningiscompleted,theauto-tuningindicatorwilldurnoffandthePIDtimeconstantwillbe
saved to each parameter of parameter group 1. The saved parameters can be adjusted as desired.
Tomanuallystopauto-tuning,holdthe key for 5
seconds.Whenauto-tuningisstopped,thecontroller
maintainsthePIDvaluebeforeauto-tuning.
TZN Series supports 2 auto-tuning modes.
Select TUN1 mode or TUN2 mode [TUN1,TUN2]
from auto-tuning mode [AtT] of parameter group 2.
※
Run auto-tuning during initial setup of the
temperature controller.
※
If the thermal characteristics of the control target
devicehaschangedafterextendedusage,re-run
auto-tuning.
3. Alarm (Event)
Alarmoutputcanbeconguredbycombiningalarmoperationandalarmoptions.Setthealarmoperationin
event 1/2 [EU1,EU2]ofparametergroup2,andsetthealarmoptionsinalarmoption[AL-T].
1)Alarmoperation
Mode Name Alarm operation Description
ㅁAL-0 - - Alarm output not used.
AL-1
Deviation
high-limit
alarm SV
100℃
PV
110℃
OFF ONHIfthedeviationofPVandSVare
higherthanthehigh-limitdeviation,
the alarm output turns ON.
High-limit deviation: 10℃
AL-2
Deviation
low-limit
alarm PV
90℃
SV
100℃
OFFON HIfthedeviationofPVandSVare
higherthanthelow-limitdeviation,
the alarm output turns ON.
Low-limit deviation: 10℃
AL-3
Deviation
high-limit
/low-limit
alarm
PV
90℃
PV
110℃
SV
100℃
OFFON ONH H IfthedeviationofPVandSVare
higher than the high-limit deviation
orlow-limitdeviation,thealarm
output turns ON.
High-limit/low-limit deviation: 10℃
AL-4
Deviation
high-limit
/low-limit
reverse
alarm
PV
90℃
PV
110℃
SV
100℃
OFF OFFONH H IfthedeviationofPVandSVare
higher than the high-limit deviation
orlow-limitdeviation,thealarm
output turns OFF.
High-limit/low-limit deviation: 10℃
AL-5
Absolute
value
high-limit
alarm
PV
90℃
SV
100℃
OFF ONH
SV
100℃
PV
110℃
OFF ONH
AlarmoutputturnsONwhenPVis
higher than the absolute value.
Absolute value alarm:
90℃
Absolute value alarm:
110℃
AL-6
Absolute
value
low-limit
alarm
PV
90℃
SV
100℃
OFFON H
SV
100℃
PV
110℃
OFFON H
AlarmoutputturnsONwhenPVis
lower than the absolute value.
Absolute value alarm:
90℃
Absolute value alarm:
110℃
SBA Sensor
break
-
Alarm output turns ON when sensor
disconnection is detected.
LBA Loop
break
-
Alarm output turns ON when loop
break is detected.
※H: Alarm output hysteresis [AHYS]
Mode Name Description
AL-A Standard
alarm
AlarmoutputturnsONuponalarmcondition,andalarmoutputturnsOFFwhen
condition is cleared.
AL-B Alarm latch Alarm output turns ON and maintains ON upon alarm condition.
AL-C Standby
sequence
Therstalarmconditionisignored.Itwilloperateasstandardalarmfromthesecond
alarmcondition.Ifitisunderalarmconditionwhenpowerissupplied,itwillignorethe
condition and operate as standard alarm from the next alarm condition.
AL-D
Alarm latch
and standby
sequence
It will operate as both alarm latch and standby sequence upon alarm condition. If it is
underalarmconditionwhenpowerissupplied,itwillignoretheconditionandoperate
as alarm latch from the next alarm condition.
3)Sensorbreakalarm
Alarm output turns ON when sensor is not connected or loses its connection during temperature control. Sensor
disconnection can be tested by connecting buzzers or other devices to the alarm output contact. Sensor break
alarm output operates through EV1 OUT or EV2 OUT contacts. Alarm output is disengaged after resetting the
power.
4)LoopbreakAlarm(LBA)
Diagnose control loop and transmit alarm output through temperature change of control target. During
heating(cooling)control,thealarmoutputturnsONifthePVdoesnotrise/dropbyaspecicamount(approx.2℃)
during LBA monitoring period [LBA]whilecontroloutputamountisat100%(0%).
※
Ifthethermalresponseofthecontroltargetisslow,theLBAmonitoringperiod[LBA] of parameter group 1
should be set longer.
※
LBAonlyoperateswhenthecontroloutputamountis100%(0%)soitcannotbeusedincurrentoutputmodels.
※
IfthealarmoutputturnsONafterthesensorhasbeendisconnected,thealarmoutputwillnotturnOFFeven
afterreconnectingthesensor.Todisengagethealarmoutput,thetemperaturecontrollerpowermustbereset.
TUN1
mode
[TUN1]
Temperature
Time
SV
Auto-tuning
TUN2
mode
[TUN2]
Temperature
Time
70%
SV
Auto-tuning
6. Input correction [IN-B]
Used to correct deviation from external devices such as temperature controllers.
E.g.)Iftheactualtemperatureis80℃but the display value is 78℃,settheinputcorrection[IN-B] value to 2
and it will display 80℃as the display value.
High-
speed
response
mode
[PIdF]
Temperature
Time
SV
S
t
PV Usedtominimizethetime(t)requiredtoreachtheSV.
Overshoot(S)occurs.
Used in machinery that may require warming up.
(injectionmoldingmachine,electricfurnace,etc.)
Low-
speed
response
[PIdS]
Temperature
Time
t
SV PV Usedtominimizeovershoot(S).Time(t)requiredto
reach SV may be slower.
Used for machinery or environments where overshoot
maycauseexplosionorre.(oiltemperaturecontrol,
metalplatingmachinery,etc.)
5. Dual PID control
TheresponserateofthePIDcontrolcanbeselecteddependingonthecharacteristicsofthecontroltarget.
Select high-speed response mode or low-speed response mode [PIdF,PIdS]fromPIDmethod[PIDT] of
parameter group 2.
PhotoelectricSensors Temperature Controllers
Fiber Optic Sensors Temperature/Humidity Transducers
Door Sensors SSRs/PowerControllers
Door Side Sensors Counters
Area Sensors Timers
ProximitySensors PanelMeters
PressureSensors Tachometer/Pulse(Rate)Meters
Rotary Encoders Display Units
Connector/Sockets Sensor Controllers
SwitchingModePowerSupplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/LogicPanels
Field Network Devices
LaserMarkingSystem(Fiber,CO₂,Nd:YAG)
Laser Welding/Cutting System
http://www.autonics.com
HEADQUARTERS:
18,Bansong-ro513beon-gil,Haeundae-gu,Busan,
SouthKorea,48002
TEL: 82-51-519-3232
E-mail: [email protected]
DRW170714AA
7. Manual reset [REST]
Whenusingproportionalcontrol(Pcontrol),thetimeoftemperature
rising time and falling time may differ depending on factors such as
the heat capacity of the control device or the heater. A certain amount
of deviation occurs even under stable conditions.
Thisdeviationisreferredtoasoffset,andcanbecongured/corrected
using manual reset [REST].
WhenPVandSVareequal,theresetvalueis50.0%.IfthePVis
lowerthantheSVduringstablecontrol,setthevaluetoover50.0%,
andifthePVishigherthantheSV,setthevaluetounder50.0%
Conguringmanualreset[REST]
according to control results.
Reset value set at under 50.0%
Reset value set at over 50.0%
Offset
Offset
SV
1.Followinstructionsin'CautionsduringUse'.Otherwise,Itmaycauseunexpectedaccidents.
2. Check the polarity of the terminals before wiring the temperature sensor.
ForRTDtemperaturesensor,wireitas3-wiretype,usingcablesinsamethicknessandlength.
Forthermocouple(CT)temperaturesensor,usethedesignatedcompensationwireforextendingwire.
3. Keep away from high voltage lines or power lines to prevent inductive noise.
Incaseinstallingpowerlineandinputsignallineclosely,uselinelterorvaristoratpowerlineandshielded
wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the
power.
5.Donotusetheunitforotherpurpose(e.g.voltmeter,ammeter),buttemperaturecontroller.
6.Whenchangingtheinputsensor,turnoffthepowerrstbeforechanging.
Afterchangingtheinputsensor,specifyinternalswitchandmodifythevalueofthecorrespondingparameter.
7. Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect
of external noise.
8. Make a required space around the unit for radiation of heat.
Foraccuratetemperaturemeasurement,warmuptheunitover20minafterturningonthepower.
9. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
10. Do not wire to terminals which are not used.
11. This unit may be used in the following environments.
①Indoors(intheenvironmentconditionratedin'Specications') ②Altitudemax.2,000m
③Pollutiondegree2    ④Installation category II
Comprehensive Device Management Program[DAQMaster]
DAQMaster is a comprehensive device management software for setting parameters and monitoring
processes. DAQMaster can be downloaded from our website at www.autonics.com.
Item Minimumspecications
System IBMPCcompatiblecomputerwithPentiumⅢor above
Operations Windows98/NT/XP/Vista/7/8/10
Memory 256MB+
Hard disk 1GB+ of available hard disk space
VGA Resolution: 1024×768 or higher
Others RS232Cserialport(9-pin),USBport
2)Alarmoptions
ON ON1
OFF Unlock
ON Lock parameter 1
( keyavailable)
ON1 Lock parameter 1
(keyunavailable)
Setting range:
※1: : ( )key-Switchelds, , key-Change values
※2:Pressthe key after checking or changing the values in parameter
settings to save the setting value and move to the next parameter.
※Hold the key for 3 seconds anytime during parameter settings to save the
setting value and return to RUN mode.
※The dotted line parameters may not appear depending on the model or
other parameter settings.
SV 2
temperature
Event 1
alarm
temp.
Event 2
alarm
temp.
LBA
monitoring
time
Alarm
output
hysteresis
Proportional
band
Integral
time
Derivative
time
Control
period
Hysteresis
Input
correction
Manual
reset
Ramp
up time
Ramp
down time
Lock
SU-2
AL1
AL2
LBA
AHYS
P
I
D
T
HYS
IN-B
REST
RAPU
RAPD
LOC
3 sec
3 sec
RUN mode
0
10
10
600
2
#0
0
0
20
2
0
)0
10
10
OFF
● Parameter group 1
※2
Setting range: refer to " Input Type and Range".
Setting range: refer to " Input Type and Range".
※[AL1,AL2] parameters do not appear when Event 1/2 [EU-1,
EU-2] of parameter group 2 is set to AL-0,LBA,SBA.
※[AL2] parameter only appears in models that support Event 2
output.
Setting range: 0 to 999 sec
※Only appears when Event1/2 [EU-1,EU-2] of parameter
group 2 is set to LBA.
※Does not appears in current output models.
Setting range: 1 to 100℃/℉(0.1to100.0℃/℉)
※Does not appears when Event 1/2 [EU-1,EU-2] of parameter
group 2 is set to AL-0,LBA,SBA.
Setting range: 0.0 to 100.0%
※ON/OFF control: Set to )0,PIDcontrol:Settoover)0
※OnlyappearsduringPID
control(proportionalband
[P] set to over )0).
Setting range: 1 to 100℃/℉(0.1to100.0℃/℉)
※OnlyappearsduringON/OFFcontrol(proportionalband
[P] set to )0).
Setting range: -49 to 50℃/℉(-50.0to50.0℃/℉)
Setting range: 0.0 to 100%
※OnlyappearswhenPcontrol(proportionalband[P] set to over
)0,integraltime[I],andderivativetime[D] are set to 0)
Setting range: 1 to 99 min
※Only appears when ramp function [RAMP] of parameter group
2 is set to ON.
Settingrange:0to3,600sec
※Integral operation is turned OFF
when set to 0.
Settingrange:0to3,600sec
※Derivative operation is turned
OFF when set to 0.
Setting range: 1 to 120 sec
※Set to a small value in SSR drive
outputmodels.(i.e.2sec)
PV display SV display
※1
● Parameter group 2
+
3 sec
Setting range: refer to " Input Type and Range".
OFF Unlock
ON Lock parameter 2
Setting range:
Input type
Event 1
Event 2
Alarm
option
Auto-tuning
mode
PIDmethod
Heating/
Cooling
Temperature
unit
SV
high-limit
SV
low-limit
Decimal
point
Trans. output
high-limit
Trans. output
low-limit
Ramp
function
3 sec
RUN mode
※2
Setting range: refer to " Input Type and Range".
Setting range: refer to '3. Alarm'.
※Event 2 [EU-2] only appears in models that support Event
2 output.
Setting range: refer to '3. Alarm'.
※Does not appear when Event 1/2 [EU-1,EU-2] is set to
AL-0,LBA,SBA.
Setting range: 0,)0,)00,)000
※Only appears with analog input.
Setting range: refer to " Input Type and Range".
※OnlyappearsinmodelsthatsupportPVtransmission.
※1
Com.
address
Lock
※Only appears in models
that support RS485
communication
Settingrange:1to99(address)
※1: : ( )key-Switchelds, , key-Change values
※2:Pressthe key after checking or changing the values in parameter
settings to save the setting value and move to the next parameter.
※Hold the key for 3 seconds anytime during parameter settings to save the
setting value and return to RUN mode.
※The dotted line parameters may not appear depending on the model or
other parameter settings.
※Pleasesetaccordingtocontrolapplication.
Do not change the settings during operation.
Itmayresultinreoraccidents.
PV display SV display
IN-T
EU-1
EU-2
AL-T
AtT
PIDT
O-FT
UNIT
H-SC
L-SC
DOT
FS-H
FS-L
RAMP
KCaH
AL-1
AL-2
AL-A
1300
`00
0
1300
`00
※2
※1
ON
ON
4800 9600
BPS
ㅁㅁ ADRS
LOC
01
OFF
OFF
2400
TVN2
PIdF
COOL
?F
TVN1
PIdS
HEAT
?C

Other manuals for TZN4S Series

1

This manual suits for next models

4

Other Autonics Controllers manuals

Autonics TN Series User manual

Autonics

Autonics TN Series User manual

Autonics SPR3 Series User manual

Autonics

Autonics SPR3 Series User manual

Autonics MD5-HF14 Series User manual

Autonics

Autonics MD5-HF14 Series User manual

Autonics SFC-R Series User manual

Autonics

Autonics SFC-R Series User manual

Autonics TN Series Use and care manual

Autonics

Autonics TN Series Use and care manual

Autonics TM2-22RB User manual

Autonics

Autonics TM2-22RB User manual

Autonics SPR1 Series User manual

Autonics

Autonics SPR1 Series User manual

Autonics TZN Series User manual

Autonics

Autonics TZN Series User manual

Autonics SPC Series User manual

Autonics

Autonics SPC Series User manual

Autonics SPR3 Series User manual

Autonics

Autonics SPR3 Series User manual

Autonics SFC Series User manual

Autonics

Autonics SFC Series User manual

Autonics DPU Series User manual

Autonics

Autonics DPU Series User manual

Autonics TK Series User manual

Autonics

Autonics TK Series User manual

Autonics TZ4SP User manual

Autonics

Autonics TZ4SP User manual

Autonics TR1D Series Use and care manual

Autonics

Autonics TR1D Series Use and care manual

Autonics PA10-U User manual

Autonics

Autonics PA10-U User manual

Autonics PMC-1 HS User manual

Autonics

Autonics PMC-1 HS User manual

Autonics TM Series User manual

Autonics

Autonics TM Series User manual

Autonics PMC-2HSP Series User manual

Autonics

Autonics PMC-2HSP Series User manual

Autonics SPRM Series User manual

Autonics

Autonics SPRM Series User manual

Autonics SPR Series Use and care manual

Autonics

Autonics SPR Series Use and care manual

Autonics PMC-2HS Series User manual

Autonics

Autonics PMC-2HS Series User manual

Autonics PA10 Series User manual

Autonics

Autonics PA10 Series User manual

Autonics TZN Series User manual

Autonics

Autonics TZN Series User manual

Popular Controllers manuals by other brands

Alpha Microsystems AM-219 installation instructions

Alpha Microsystems

Alpha Microsystems AM-219 installation instructions

Securefast T/SED900/033A installation instructions

Securefast

Securefast T/SED900/033A installation instructions

Siemens Simatic S7-1500 Getting started

Siemens

Siemens Simatic S7-1500 Getting started

FlowLine DataPoint LC52-1001 manual

FlowLine

FlowLine DataPoint LC52-1001 manual

Siemens SQS65 Mounting instructions

Siemens

Siemens SQS65 Mounting instructions

Siemens BACnet PTEC Dual Duct 2 AVS installation instructions

Siemens

Siemens BACnet PTEC Dual Duct 2 AVS installation instructions

Data Technology 5280CRA installation guide

Data Technology

Data Technology 5280CRA installation guide

Omron E5xK-T series manual

Omron

Omron E5xK-T series manual

Pentair IntelliBrite installation guide

Pentair

Pentair IntelliBrite installation guide

Vanderbilt ACT365 VCU Installation and operating instructions

Vanderbilt

Vanderbilt ACT365 VCU Installation and operating instructions

Rice Lake 882IS Technical manual

Rice Lake

Rice Lake 882IS Technical manual

Chipkin FS-8705-12 Driver manual

Chipkin

Chipkin FS-8705-12 Driver manual

Fisher EMERSON P539 instruction manual

Fisher

Fisher EMERSON P539 instruction manual

Newport SMC100CC user manual

Newport

Newport SMC100CC user manual

HPE Aruba 7280 Product End-of-Life Disassembly Instructions

HPE

HPE Aruba 7280 Product End-of-Life Disassembly Instructions

Ascon tecnologic X33H operating instructions

Ascon tecnologic

Ascon tecnologic X33H operating instructions

Omron SYSMAC CJ1-M brochure

Omron

Omron SYSMAC CJ1-M brochure

POSEIDON Cyklon 5000 user manual

POSEIDON

POSEIDON Cyklon 5000 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.