BEKA BA567E-SS User manual

Issue: 6
9th July 2019
BA567E-SS
Rugged one input
General purpose
Counter
Issue 6

1. Description
2. Operation
2.1 Initialisation
2.2 Controls
2.3 Displays
3. System Design
3.1 Power supply
3.2 Pulse input
3.2.1 Switch contact input
3.2.2 2-wire proximity detector input
3.2.3 Open collector input
3.2.4 Magnetic pick-off input
3.2.5 Voltage pulse input
3.3 Remote reset
4. Installation
4.1 Location
4.2 Installation procedure
4.3 EMC
4.4 Counter earthing
4.5 Scale card
5. Configuration and Calibration
5.1 Configuration structure
5.2 Accessing the configuration functions
5.3 Summary of configuration functions
5.4 Input: inPut
5.5 Input type: inP.tYPE
5.6 Input debounce: dEbouncE
5.7 Input pulse counting edge: Cnt EdgE
5.8 Display update interval: uPdAtE
5.9 Upper display: di5P-1
5.10 Lower display: di5P-2
5.11 Position of the decimal points: dP
5.12 Total scale factor: 5CALE .t
5.13 Rate scale factor: 5CALE .r
5.14 Timebase: t-bA5E
5.15 Display filter: FiLtEr
5.16 Direction of count: uP or dn
5.17 Reset value: CLr VAL
5.18 Local reset: LoC CLr
5.19 Local total reset: Clr tot
5.20 Local grand total reset: Clr Gtot
5.21 Reset grand total from configuration
menu: Clr Gtot
5.22 Security code: CodE
5.23 Reset configuration to factory defaults:
r5Et dEF
5.24 Display overflow
6. Configuration example
7. Maintenance
7.1 Fault finding during commissioning
7.2 Fault finding after commissioning
7.3 Servicing
7.4 Routine maintenance
7.5 Guarantee
7.6 Customer comments
8. Accessories
8.1 Scale card
8.2 Tag information
8.3 Alarms
8.3.1 Solid state output
8.3.2 Configuration summary
8.3.3 Alarm enable: EnbL
8.3.4 Type of alarm: tYPE
8.3.5 Setpoint adjustment:
5P1x & 5P2x
8.3.6 Alarm function: Hi.Lo
8.3.7 Alarm output status: no .nC
8.3.8 Hysteresis: H5tr
8.3.9 Alarm delay: dELA
8.3.10 Alarm silence time: 5IL
8.3.11 Flash display when alarm occurs:
FL5H
8.3.12 Access Setpoint: AC5P
8.3.13 Adjusting alarm setpoints from
display mode.
8.4 Pulse Output
8.4.1 System design
8.4.2 Configuration
8.4.3 Access Pulse output sub-menu:
PuL5E oP
8.4.4 Enable pulse output: EnbL
8.4.5 Source of pulse output: 5ourCE
8.4.6 Divide output pulse frequency:
diVidE
8.4.7 Output pulse width: durAtion
8.5 4/20mA output
8.5.1 System design
8.5.2 Configuration
8.5.3 Access 4/20mA output
sub-menu: 4-20 oP
8.5.4 Enable 4/20mA output: EnbL
8.5.5 Select rate or total source:
4-20tYPE
8.5.6 Display corresponding to
4mA output: 4.000
8.5.7 Display corresponding to
20mA output: 20 .000
8.6 Display backlight
222222222222222222222222222
CONTENTS
The BA567E-SS is CE marked to show compliance with the European EMC Directive 2014/30/EU

1. DESCRIPTION
This rugged general purpose, one input Counter
may be configured to count input pulses from a wide
variety of sensors and to display the total number in
engineering units. A smaller six digit display may be
activated to show the input pulse rate in engineering
units per second, minute or per hour.
2. OPERATION
Fig 1 shows a simplified block diagram of the
BA567E-SS Counter. The instrument can be
supplied with a factory fitted internally powered
display backlight, plus one of the following three
factory fitted accessories:
Dual isolated alarms
or Isolated pulse output
or Isolated 4/20mA output
Fig 1 BA567E-SS block diagram
2.1 Initialisation
Each time power is applied to a BA567E-SS Counter
initialisation is performed. After a short delay the
following display sequence occurs:
All segments of the display are activated
Counter starts functioning, using the
configuration information stored in the
instrument’s permanent memory. Unless
total and grand total displays have been reset
to zero, new pulses will be added to the
existing totals.
2.2 Controls
The BA567E-SS Counter is controlled and
configured via four front panel push buttons. In the
display mode i.e. when the instrument is counting,
the push button functions are:
Push Button Functions
( + )Access to configuration menu
& + *If Local Total Reset CLr tot in the
instrument configuration menu has
been activated, operating the & and
*buttons simultaneously for three
seconds will reset the total display to
zero and clear any pulses stored in the
optional pulse output.
See 5.19
) + &Grand total - shows Lo followed by least
significant 8 digits of the 16 digit grand
total.
) + * Grand total - shows Hi followed by the
most significant 8 digits of the 16 digit
grand total.
If Local Grand Total Reset CLr Gtot in
the instrument configuration menu has
been activated, operating the ) and
*buttons simultaneously for ten
seconds will result in Clr .no being
displayed with the no flashing.
Operating the *or &button will
change the display to Clr .YE5, the )
button will then reset the grand total to
zero which will be confirmed by a brief
display of Gt Clrd. See 5.20
(+ &Shows firmware version
Note: When optional alarms are fitted, the
BA567E-SS Counter may be configured to provide
direct access to the alarm setpoints from the display
mode when the (and * buttons are operated
simultaneously. See 8.3.13
3

2.3 Displays
The BA567E-SS Counter has two digital displays
and associated annunciators, plus a pulse input
indicator as shown on the front page of this manual.
Total Shows the total pulse count on the
display upper eight digit display. May be
reset to zero via front panel push
buttons or by a remote reset switch.
Rate Shows the pulse rate on the lower six
Display digit display. Total and rate displays
may be reversed.
Pulse input This disc in the lower left hand corner
indicator of the display 'rotates' for two
seconds each time an input pulse is
received on either input. Appears to
rotate continuously when combined
input frequency on both inputs
exceeds 0.5Hz.
Reset Activated while the total display
annunciator is being reset via the front panel
push buttons, or the external reset
terminals.
Rate Identifies rate display
annunciator
Total Identifies total display
annunciator
RTx Retransmitted pulse
annunciator annunciator.
Depends upon the setting of 5ource
in the pulse output configuration
menu.
5caled:
Annunciator activated each time
pulse output open collector is on,
i.e. Ron is less than 60+ 3V.
direct:
Annunciator continuously
activated.
4

3. SYSTEM DESIGN
Fig 2 illustrates the basic circuit that is used for all
BA567E-SS Counter installations. For simplicity,
connections for the optional alarms, pulse output
and 4/20mA output are shown separately in section
8 this manual.
Fig 2 BA567E-SS connections
When designing a system it is important to
remember that terminals 2, 6 and RS2 are
interconnected within the BA567E-SS see Fig 1.
3.1 Power supply
The BA567E-SS Counter requires a 10 to 30V dc
supply between terminal 1 & 2 and consumes:
10mA without optional backlight
plus 6mA when terminals 3 & 4 are linked
plus 22mA for optional backlight
3.2 Pulse input
As shown in Fig 2 the BA567E-SS can count pulses
from a wide variety of sensors.
The following table shows the switching thresholds
for the various types of sensor. For reliable
counting the pulse input must fall below the lower
threshold and rise above the upper threshold.
Input sensor
Switching thresholds
Lower Upper
Switch 1001000
Proximity detector 1.2mA 2.1mA
Open collector 2k10k
Magnetic pick-off 0mV 40mV peak
Voltage pulse low 1.0V 3.0V
Voltage pulse high 3.0V 10.0V
3.2.1 Switch contact input
Any switch contact may be directly connected to
pulse input terminals 5 and 6, The BA567E-SS
contains a configurable debounce circuit to prevent
contact bounce being counted. See section 5.6
including details of the maximum counting
frequency.
3.2.2 2-wire proximity detector input
Most NAMUR 2-wire proximity detector may be
directly connected to the BA567E-SS pulse input,
providing the minimum operating voltage of the
proximity detector is less than 7.5V. The BA367E-
SS contain a configurable debounce circuit to
prevent false triggering. Three levels of debounce
protection are independently available. See section
5.6.
3.2.3 Open collector input
Sensors with an open collector output may be
directly connected to Counter input terminals 5 & 6.
Polarity of the sensor output should be observed.
The BA567E-SS contains a configurable debounce
circuit to prevent false triggering. Three levels of de-
bounce protection are independently available. See
section 5.6.
3.2.4 Magnetic pick-off input
Sensors incorporating a magnetic pick-off will have a
low level voltage output unless the sensor
incorporates an amplifier. CoiL in the BA567E-SS
input configuration menu is a low level voltage pulse
input intended for use with a magnetic pick-off. The
Counter contains a configurable debounce circuit to
prevent false triggering of the instrument. See
section 5.6.
3.2.5 Voltage pulse input
Two voltage pulse input ranges are selectable in the
BA567E-SS Counter configuration menu, VoLt5 L
and VoLt5 H as shown in section 3.2. The Counter
contains a configurable debounce circuit to prevent
false triggering of the instrument. Three levels of de-
bounce protection are independently available. See
section 5.6.
3.3 Remote reset
The Counter's total display may be remotely reset to
zero by connecting terminals RS1 and RS2 together
for more than one second. Permanent
interconnection inhibits counting.
Note: The BA367E may also be configured to
reset the total display to zero by operating
the &and *push buttons simultaneously
for more than two seconds in the totalising
mode i.e. when the instrument is displaying
flow. See 5.19
5

4. INSTALLATION
4.1 Location
The BA567E-SS has a stainless steel case with a
10mm thick toughened glass window. The case
provides 7J and the window 4J front of panel impact
protection. The captive silicone gasket, which seals
the joint between the instrument and the panel
enclosure, ensures IP66 front of panel ingress
protection. The rear of the Counter has IP20
protection.
Fig 3 shows the overall dimensions of the
BA567E-SS together with the recommended panel
enclosure cut-out dimensions and terminal locations.
4.2 Installation Procedure
a. Cut the aperture specified in Fig 3 in the panel
enclosure. Ensure that the edges of aperture are
de-burred.
b. Inspect the Counter's captive gasket and ensure
that it is not damaged before inserting the
Counter into the panel enclosure aperture.
c. If the enclosure panel is less than 1.0mm thick, or
is non-metallic, an optional BEKA stainless steel
support plate should be slid over the rear of the
Counter before the panel clamps are fitted to
evenly distribute the clamping force and prevent
the enclosure panel being distorted or creeping.
d. Slide a panel clamp into the two grooves at each
corner of the indicator housing with the M3 stud
protruding through the hole at the rear of the
clamp. Fit the stainless steel spring washer over
the stud and secure with the stainless steel wing
nut.
e. Evenly tighten the four clamps to secure the
instrument. The recommended minimum
tightening torque for each wing nut is 22cNm
(1.95 lbf in).
f. Connect the panel enclosure wiring to the rear
terminal blocks. To simplify installation, the
terminals are removable so that wiring can be
completed before the instrument is installed.
Cables should be mechanically secured to
ensure terminals are not damaged by vibration.
g. Finally fit a silicone rubber push-on cap to the
end of each M3 threaded rod.
Support panel wiring to prevent vibration damage
Note: Optional backlight is internally powered
Fig 3 Dimensions and terminals
6

Fig 4 Installation procedure
4.3 EMC
The BA567E-SS complies with the requirements of
the European EMC Directive 2014/30/EU. For
specified immunity all wiring should be in screened
twisted pairs, with the screens earthed at one point.
Fig 5 Terminals for field wiring
4.4 Counter earthing
The BA567E-SS has an M4 earth stud on the rear
panel which should be electrically connected to the
panel enclosure in which the instrument is mounted,
or to the plant equipotential conductor.
4.5 Scale card
The Counter’s units of measurement are shown on a
printed scale card in a window at the right hand side
of the display. The scale card is mounted on a
flexible strip that is inserted into a slot at the rear of
the instrument as shown in Fig 6. Thus the scale
card can easily be changed without removing the
Counter from the panel or opening the instrument
enclosure.
New Counters are supplied with a printed scale card
showing the requested units of measurement, if this
information is not supplied when the instrument is
ordered a blank card will be fitted.
A pack of self-adhesive scale cards printed with
common units of flow measurement is available as
an accessory from BEKA associates. Custom
printed scale cards can also be supplied.
To change a scale card, unclip the tapered end of
the flexible strip at the rear of the instrument by
gently pushing it upwards and pulling it out of the
enclosure. Peel the existing scale card from the
flexible strip and replace it with a new printed card,
which should be aligned as shown below. Do not fit
a new scale card on top of an existing card.
Install the new scale card by gently pushing the
flexible strip into the slot at the rear of the Counter,
when it reaches the internal end-stop secure it by
pushing the end of the flexible strip downwards so
that the tapered section is held by the rear panel.
Align the self-adhesive
printed scale card onto the
flexible strip and insert the
strip into the indicator as
shown below.
Fig 6 Inserting flexible strip carrying scale card into
slot at the rear of the Tachometer.
7

5.0 CONFIGURATION & CALIBRATION
The BA567E-SS Counter is configured and
calibrated via four front panel push buttons. All the
configuration functions are contained in an easy to
use intuitive menu that is shown diagrammatically in
Fig 8.
Each menu function is summarised in section 5.3 of
this manual and each summary includes a reference
to more detailed information.
When factory fitted optional dual alarms, pulse
output or a 4/20mA output are included, additional
functions appear in the configuration menu which
are described separately in section 8.
All new BA567E-SS Counters are supplied
calibrated as requested at the time of ordering. If
calibration is not requested, Counters will have
default configuration as shown in the following table,
but can easily be re-configured on-site.
Function Display Default
Input
Input type inP .tYPE oP .CoL
Debounce dEbounCE dEFAuLt
Counting edge Cnt EdGE EdGE 1
Update uPdAtE 0.5
Upper display di5p-1 totAL
Lower display di5P-2 on
Decimal point dP Rate 00000 .0
Total 00000000
Total scale factor 5CALE .t001.00
Rate scale factor 5CALE .r001.00
Timebase t-bA5E tb-01
Filter FiLter 24
Counter direction uP or dn uP
Clear value clr val 00000000
Local clear
Local total reset Clr tot oFF
Local grand total reset Clr Gtot oFF
Security code CodE 0000
Note: While the instrument is being configured
counting continues so that any input pulses
occurring during this time are recorded.
5.1 Configuration structure
Fig 7 shows the configuration structure of the
BA567E-SS Counter. The pulse input is passed to
the 5CALE.r and 5CALE.t functions allowing the
independent rate and total displays to have different
engineering units.
5CALE.t is a dividing factor that converts the input
pulses into the required total display in engineering
units. e.g. if the input is two pulses per pump stroke
and it is required to display the total number of pump
strokes in thousands of strokes, 5CALE.t should be
set to 2000.
5CALE.r is a dividing factor that converts the input
pulses into a rate display with the required
engineering units. e.g. if the input is two pulses per
pump stroke and it is required to display the pump
stroke rate, 5CALE.r should be set to 2.0.
The timebase t-bA5E is a multiplying factor that
determines if the instrument displays pulse rate per
second, per minute or per hour.
The BA567E-SS uses ‘real’ decimal points. Moving
the position of a decimal point in a scale factor will
affect the instrument calibration.
Fig 7 Calibration structure
8

5.2 Accessing configuration functions
Throughout this manual the instrument front panel
push buttons are shown as &, *, (and )and
legends displayed by the instrument are shown in a
seven segment font as displayed by the Counter
e.g. FiLtEr and 5CALE .r.
Access to the configuration menu is obtained by
operating the (and )push buttons
simultaneously. If the instrument is not protected by
a security code the first parameter inPut will be
displayed. If a security code other than the default
code 0000 has already been entered, the instrument
will display CodE. Press (to clear this prompt and
enter the security code for the instrument using the
&or *push button to adjust the flashing digit,
and the (push button to transfer control to the
next digit. If the correct code has been entered
pressing )will cause the first parameter inPut to
be displayed. If an incorrect code is entered, or a
push button is not operated within ten seconds, the
instrument will automatically return to the display
mode.
All configuration functions and prompts are shown
on the upper eight digit display.
Once within the configuration menu the required
function can be selected by scrolling through the
menu using the &and *push buttons. The
configuration menu is shown diagrammatically in
Fig 8.
When returning to the display mode following
reconfiguration, the BA567E-SS Counter will display
dAtA followed by 5AVE while the new information is
stored in permanent memory.
If after accessing the configuration menu the interval
between operating any front panel push button
exceeds one minute, the BA567E-SS will
automatically return to the display mode and any
configuration changes will not be stored in
permanent memory. When making changes to
multiple configuration functions, it is therefore
sensible to occasionally return to the display mode
to save the changes that have already been made.
5.3 Summary of configuration functions
This section summarises all the configuration
functions. When read in conjunction with Fig 8 it
provides a quick aid for configuring the Counter. If
more detail is required, each section contains a
reference to a full description of the function.
Display Summary of function
inPut Contains sub-menu with two
functions:
inP .tYPE Select Input type
dEbounCE Set debounce
See section 5.4
inP .tYPE
Configures input to accept one of six
types of input:
oP .CoL Open collector *
VoLt5 L Voltage pulse <1 >3V
VoLt5 H Voltage pulse <3 >10V
CoiL Magnetic pick-off
Pr .dEt Proximity detector *
ContACt Switch contact *
*Link terminals 3 & 4
See section 5.5
dEbounCE [[
Defines level of input debounce
applied to the pulse input to prevent
false counting:
dEFAuLt
HEAVY
LiGHt
See section 5.6
Cnt EdGE Input pulse counting edge
Defines whether the Counter is
incremented/decremented on the
leading or trailing edge of an input
pulse.
See section 5.7
updAtE Display update interval
Defines the interval between display
updates between 0.5 and 5
seconds.
See section 5.8
9

Display Summary of function
di5P-1 Upper display
Defines whether rAtE or totAL are
shown on the upper display. The
other variable will be shown on the
lower display, providing the lower
display is on in function dI5P-2.
See section 5.9
di5P-2 Lower display
Turns the lower display, which
normally shows rate, on or oFF.
See section 5.10
dP Position of decimal points
Defines the position of the decimal
point in both the total and rate
displays.
See section 5.11
5CALE .tTotal Scale Factor
5CALE .T is a dividing factor that
converts the number of input pulses
into the required total display in
engineering units. 5CALE .tmay be
adjusted between 0.0001 & 99999.
e.g. if one input pulse represents 1
centimetre of dispensed cable and
the total display is required in
metres, 5CALE .tshould be set to
100.0 which is the number of
centimetres in a metre.
The total display is independent of
the rate display.
See section 5.12
5CALE .rRate scale factor
5CALE .ris a dividing factor that
converts the input pulse rate into the
required rate display in engineering
units. 5CALE .rmay be adjusted
between 0.0001 and 99999. e.g. if
one pulse represents 2 pump
strokes and the rate display is
required in pump strokes, 5CALE .r
should be set to 2.0.
The rate display is independent of
the total display.
See section 5.13
Display Summary of function
t-bA5E Timebase
Selectable multiplier allowing rate to
be displayed in units per second, per
minute or per hour.
Select:
tb-01 for rate / second
tb-60 for rate / minute
tb-3600 for rate / hour
See section 5.14
FiLtEr Display filter
Is an adjustable digital filter to
reduce the noise on the rate display.
The filter has two parameters each
represented by a digit adjustable
between 0 and 9. The first digit
defines the amount of filtering
applied to the display, the second
digit the deviation from the displayed
rate at which the filter will be
overridden and the rate display will
move rapidly to the new value.
See section 5.15
uP or dn Direction of count
Determines whether input pulses
increment or decrement the total
display.
See section 5.16
CLr VAL Reset value
Defines a preset number to which
the total display will be set when the
BA567E-SS Counter is locally or
remotely reset. Enables the
instrument to count down from a
preset number.
See section 5.17
10

Display Summary of function
LoC CLr Local clear
Contains sub-menu with two
functions enabling the total and the
grand total to be reset via the front
panel push buttons while the
Counter is in the display mode.
See section 5.18
Clr tot
When on is selected total display is
reset when &and *buttons are
operated simultaneously for more
than three seconds in the display
mode.
See section 5.19
Clr Gtot
When on is selected the grand total
may be reset when )and *
buttons are operated simultaneously
for more than 10 seconds in the
display mode - see section 2.2 for
details.
Note: Once reset, the grand total
can not be restored.
See section 5.20
Clr Gtot Resets grand total to zero from
within configuration menu.
This function resets the grand total
to zero from within the configuration
menu when CLr YE5 is selected.
Note: Once reset, the grand total
can not be recovered.
See section 5.21
Display Summary of function
CodE Access code
Defines a four digit alphanumeric
code that must be entered to gain
access to the configuration menu.
Default code 0000 disables the
security function and allows
unrestricted access to all
configuration functions.
See section 5.22
r5Et dEF Reset to factory defaults
Returns the BA567E-SS Counter to
the factory defaults shown in section
6.0 To prevent accidental use the
request must be confirmed by
entering 5urE before the reset will
be executed.
See section 5.23
11

12

13

5.4 Input: inPut
The Input function contains two sub-functions
inP .tYPE and dEbounCE that define the type of input
and the amount of input noise rejection.
5.5 Input type: inP.tYPE
inP .tYPE is a sub-menu in the inPut function which
defines the type of input sensor or input pulse that
the instrument will count. To check or change the
type of input, select inPut in the configuration menu
and press (which will reveal the inP.tYPE prompt,
pressing (again will show the existing Input
setting. If set as required press )twice to return to
the configuration menu, or repeatedly press the &
or *button until the required type of input is
displayed and then press )twice to return to the
configuration menu.
One of following six types of input may be selected:
Switching
thresholds
Low High
oP .CoL Open collector 2210k
VoLt5 L Voltage pulse low 113V
VoLt5 H Voltage pulse high1310V
CoiL Magnetic pick-off 0 40mV
Pr .dEt Proximity detector 21.2 2.1mA
ContACt Switch contact 2100 1000
Notes:
1. Maximum voltage input +30V.
2. For sensors connected to the input that
require energising i.e. proximity detectors,
switch contacts or open collector sensors,
terminals 3 & 4 of the BA567E-SS should be
linked together.
3. To count correctly, the input pulse must fall
below the lower switching threshold and rise
above the higher switching threshold.
4. See section 5.6 for maximum counting
frequency.
5.6 Input debounce: dEbouncE
dEbouncE is an adjustable sub-menu in the inPut
function which prevents the input miscounting when
the input pulse has noisy edges, such as those
resulting from a mechanical contact closing and
bouncing.
Three levels of protection may be selected. The
amount of debounce applied depends upon the type
of Counter input that has been selected in the
inP .tYPE function.
Select inPut in the configuration menu and press
(which will reveal the inP .tYPE prompt, press the
&or *button to select dEbouncE followed by (
to reveal the existing setting. Pressing the &or *
button will scroll through the three levels. When the
required level has been selected, pressing )twice
will enter the selection and return the display to the
configuration menu.
The following table shows the minimum time that the
input pulse must be continuously above the upper
input switching threshold and continuously below the
lower switching threshold to ensure that the Counter
processes the input pulse. Input switching
thresholds are shown in section 5.5.
debounce
level
Min input pulse width
Type of Input
Contact All others
Default 1600µs 40µs
Heavy 3200µs 350µs
Light 400µs 5µs
The maximum counting frequency of the
BA567E-SS depends upon the debounce level
selected, the shape of the input pulse and its
amplitude. The following table assumes a square
wave input and is included for guidance. The
maximum counting frequency will be lower if the
input pulses have sloping edges and the pulse
amplitude only slightly exceeds the input switching
thresholds.
ONLY FOR GUIDANCE
debounce
level
Max counting frequency
Type of input
Contact All others
Default 250Hz 12kHz
Heavy 120Hz 2kHz
Light 1000Hz 100kHz
The minimum counting frequency is 0.01Hz. Below
this frequency the rate display is forced to zero.
14

5.7 Input pulse counting edge: Cnt EdgE
This function defines whether the BA567E-SS
Counter is incremented/decremented on the leading
or trailing edge of an input pulse.
To check or change the input pulse edge on which
the count occurs select Cnt EdGE from the
configuration menu and press (which will reveal
EdGE 1 or EdGE 2. If required press the &or *
button to change the setting, followed by the )
button to return to the configuration menu.
EdGE 1
Type of input Counting edge
Voltage Low to high
Switch contact Closed to open
Open collector Closed to open
Proximity detector High to low current
EdGE 2
Type of input Counting edge
Voltage High to low
Switch contact Open to closed
Open collector Open to closed
Proximity detector Low to high current
5.8 Display update interval: uPdAtE
If either the rate or the total display is likely to
change rapidly, a longer interval between display
updates may simplify reading. This function allows
one of six different display intervals between 0.5 and
5 seconds to be selected. The selected display
update interval does not affect the update time of
any other instrument function.
To adjust the update interval select uPdAtE from the
configuration menu and press (to reveal the
current update interval. Pressing the &or *
button will scroll through the six times. When the
required interval has been selected press )to
enter the selection and return to the configuration
menu.
5.9 Upper display: di5P-1
Usually the total count is shown on the larger upper
eight digit display, but this function reverses the
display locations allowing rate to be shown on the
larger upper display and total on the smaller lower
display.
To check the setting for the display, select dI5P-1
from the configuration menu and press (which will
reveal if the display is showing rAtE or totAL. The
setting can be changed by pressing the &or *
button followed by the )button to enter the
selection and return to the configuration menu.
5.10 Lower display: di5P-2
This function turns the lower display on or off.
When turned off, the BA367E-SS will only have one
eight digit display which may be configured in the
di5P-1 function to show the total count or rate.
To check the setting for the lower display, select
di5P-2 from the configuration menu and press
(that will reveal if the lower display is on or oFF.
The setting may be changed by pressing the &or
*button followed by the )button to enter the
selection and return to the configuration menu.
5.11 Position of the decimal points: dP
The upper and lower displays have eight and six
digits respectively. This function enables the
position of the decimal point in both displays to be
independently positioned as shown below.
Upper display
Total 000.0.0.0.0.0 1 of 5 positions or absent
Rate 00.0.0.0.01 of 4 positions or absent
Lower display
Total 0.0.0.0.0.0 1 of 5 positions or absent
Rate 00.0.0.0.01 of 4 positions or absent
To adjust the position of the decimal points select dP
from the configuration menu and press (. The
upper display defined as the rate or total display by
function di5P-1 (section 5.9) will be activated and
identified by the display annunciator as Rate or
Total. The decimal point, which may be positioned
as shown in the table above, is moved by operating
the &or *push button. The &button moves
the position of the decimal point to the left and the
*button moves the decimal point position to the
right.
When the decimal point in the upper display has
been positioned pressing the (button will transfer
control to the lower display variable, but it will be
shown and annunciated on the larger upper display.
The position of the decimal point may be positioned
in the same way by operating the &and *push
buttons. When both decimal points are positioned
as required, enter the settings and return to the
configuration menu by operating the )button.
Note:
Adjustment of a decimal point position will
disable the following outputs which must be
re-enabled after the adjustment is complete:
Optional Pulse output
Optional Alarm outputs
Optional 4/20mA output
15

5.12 Total scale factor: 5CALE .t
5CALE .t is a dividing factor adjustable between
0.0001 and 99999 that enables the total to be
displayed in engineering units. e.g. if one input
pulse represents 1 centimetre of dispensed cable
and the total display is required in metres, 5CALE .t
should be set to 100.0 which is the number of
centimetres in a metre. If a display of the total
number of input pulses is required, 5CALE .tshould
be set to 1.0. The total display is independent of the
rate display.
To check or change the total scale factor select
5CALE .tfrom the configuration menu and press (
which will reveal the existing value with one digit
flashing. The value of the flashing digit may be
changed by pressing the &or *button. When
this digit has been adjusted as required, pressing (
will transfer control to the next digit. When all the
digits have been adjusted pressing (will transfer
control to the decimal point that may be positioned
between any of the digits, or may be omitted by
moving it to the right of the least significant digit.
When the total scale factor has been entered, press
(to return to the 5CALE .T prompt in the
configuration menu.
Note:
Adjustment of 5cale .twill disable the
following outputs which must be re-enabled
after the adjustment is complete:
Optional Pulse output
Optional Alarm outputs
Optional 4/20mA output
5.13 Rate scale factor: 5CALE .r
5CALE .ris a dividing factor adjustable between
0.0001 and 99999 that enables the rate display to be
in engineering units. e.g. if one input pulse
represents 2 pump strokes and the rate display is
required in pump strokes, 5CALE .rshould be set to
2.0. If just the rate of input pulses is required,
5CALE .rshould be set to 1.0. The rate display is
independent of the total display.
The units of the rate display are counts per unit of
time. The unit of time is the timebase of the
instrument which is determined by t-bA5E
described in section 5.14.
To check or change the rate scale factor select
5CALE .rfrom the configuration menu and press (
which will reveal the existing value with one digit
flashing. The value of the flashing digit may be
adjusted by pressing the &or *button.
When this digit has been adjusted as required,
pressing (will transfer control to the next digit.
When all the digits have been adjusted pressing
(will transfer control to the decimal point that may
be positioned between any of the digits, or may be
omitted by moving it to the right of the least
significant digit. When the required rate scale factor
has been entered, press )to return to the 5CALE .r
prompt in the configuration menu.
Note:
Adjustment of 5cale .R will disable the
following outputs which must be re-enabled
after the adjustment is complete:
Optional Pulse output
Optional Alarm outputs
Optional 4/20mA output
5.14 Timebase: t-bA5E
The timebase multiplies the rate display by 1, 60 or
3,600 depending upon whether the BA567E-SS
Counter is required to display rate per second, per
minute or per hour. See Fig 7.
To check or change the timebase, select t-bA5E
from the configuration menu and press (which will
reveal the current setting. Pressing the &or *
button will scroll through the three options:
tb-1 for pulses / second
tb-60 for pulses / minute
tb-3600 for pulses / hour
When the required multiplier is displayed press )
to return to the t-bA5E prompt in the configuration
menu.
5.15 Display filter: FiLtEr
The digital display filter has two independent
adjustable parameters enabling the rate display
response to be tailored for optimum performance.
The filter parameters are controlled by a two digit
number. The first digit defines the amount of filtering
applied to the display as shown below.
First digit Filter time constant
Seconds
0X 0
1X 1.3
2X 4.3
3X 6.5
4X 8.7
5X 11.3
6X 15.7
7X 20.9
8X 25.2
9X 31.5
16

The second digit defines the deviation from the
displayed rate at which the filter will be overridden
and the rate display will move rapidly to the new
value.
Second
digit
Magnitude of step
change which will
produce a rapid
response
X0 Off
X1 1%
X2 2%
X3 4%
X4 8%
X5 12%
X6 16%
X7 24%
X8 32%
X9 64%
By careful adjustment of the two parameters a stable
display with an acceptable input step response can
be obtained for most applications.
During commissioning it is recommend that initially
the second digit is set to 0 (off) and the first digit is
adjusted to provide acceptable rate display stability.
The second digit should then be increased until the
selected step size is greater than the noise on the
display signal, at which setting the rate display will
become stable. These will be the optimum filter
parameters for acceptable rate display stability and a
fast response to a large rate signal change.
To check or change the filter select FiLtEr in the
configuration menu and press (which will reveal
the current settings with the first digit flashing.
Pressing the &or *button will adjust the flashing
digit and (will transfer control to the second digit.
While making adjustments the filtered rate display is
shown on the lower display so that stability can be
assessed while adjustments are being made. When
set as required, press the )button to enter the
revised parameters and return to the FiLtEr prompt
in the configuration menu.
5.16 Direction of count: uP or dn
This function defines whether input pulses increment
or decrement the total display. i.e. whether the
BA567E-SS is an up-counter or a down-counter.
When configured as a down-counter with a non-zero
number entered for the reset value CLr VAL, the
BA567E-SS will count down from the reset value to
zero.
To check or change the count direction select
uP or dn from the configuration menu and press
(which will reveal the present setting. uP
indicates that the instrument is an up-counter and dn
that it is a down counter. Pressing the &or *
buttons will toggle the instrument between the two
settings. When set as required, press the )button
to enter the setting and return to the configuration
menu.
5.17 Reset value: CLr VAL
This function defines the value to which the total
display is reset when the local or remote reset are
operated. This allows the BA567E-SS to be used as
a preset down-counter.
When the instrument is used as an up-counter,
Clr VAL is normally set to zero.
To check or change the reset value select CLr VAL
from the configuration menu and press (which will
reveal the current setting with one digit flashing. The
flashing digit may be adjusted by pressing the &or
*button. When this digit is correct, pressing
(will transfer control to the next digit.
When all the digits have been adjusted press the )
button to enter the revised number and return to the
configuration menu.
5.18 Local reset: LoC CLr
The Local reset function contains two sub-functions
Clr tot and Clr Gtot which when enabled allow the
total display and grand total to be reset via the
instrument front panel push buttons while the
BA567E-SS Counter is in the display mode.
17

5.19 Local total reset: Clr tot
Clr tot is a sub-menu in the LoC CLr function. When
activated it allows an operator to reset the total
display to the reset value [see section 5.17] while
the BA567E-SS Counter is in the display mode by
operating the &and *push buttons
simultaneously for more than three seconds.
To check or change the setting select LoC CLr in the
configuration menu and press (which will reveal
the Clr tot prompt, operating (again will show if
the local total reset is on or oFF. If set as required
operate the )button twice to return to the
configuration menu, or the &or *button to
change the setting followed by the )button twice
to enter the change and return to the LoC CLr prompt
in the configuration menu.
Note:
The total display may also be remotely reset
to the reset value by connecting terminals
RS1 and RS2 together for more than one
second. See sections 3.3 of this manual.
6.20 Local grand total reset: Clr Gtot
The grand total is a separate sixteen digit counter
which is incremented or decremented in parallel with
the total display, but is not reset when the total
display is reset. The grand total may be viewed in
the display mode in two eight digit sections as
described in section 2.2 of this manual.
Clr Gtot is a sub-menu in the LoC CLr function
which when activated allows the operator to reset
the grand total display to zero from the display mode
by operating the )and *push buttons
simultaneously for more than ten seconds.
To check or change setting select LoC CLr in the
configuration menu and press (which will reveal
Clr tot. Using the &or *button select Clr Gtot
and press (which will show if local grand total
reset is on or oFF. If set as required operate the )
button twice to return to the configuration menu, or
the &or *button to change the setting followed
by the
)button twice to enter the change and
return to the LoC CLr prompt in the configuration
menu.
Note:
Once reset, the grand total can not be
recovered.
5.21 Reset grand total from configuration menu:
Clr Gtot
The grand total is a separate sixteen digit counter
which is incremented or decremented in parallel with
the total display, but is not reset when the total
display is reset. The grand total may be viewed in
the display mode in two eight digit sections as
described in section 2.2 of this manual.
To zero the grand total from within the configuration
menu select CLr Gtot and press (which will cause
the instrument to display Clr .no with no flashing.
Using the &or *push button change Clr no to
clr ye5, pressing (will result in the instrument
displaying 0000 with the first digit flashing. This is a
request to confirm the reset instruction by entering
5urE. Using the &or *button set the first
flashing digit to 5and press (to transfer control to
the second digit which should be set to u. When
5urE has been entered pressing the )button will
reset the grand total which will be confirmed by a
brief display of Gt Clrd, the instrument will
automatically return to the Clr Gt prompt in the
configuration menu.
Note:
Once reset, the grand total can not be
recovered.
5.22 Security code: CodE
Access to the instrument configuration menu may be
protected by a four digit security code which must be
entered to gain access. New instruments are
configured with the default security code 0000 which
allows unrestricted access to all configuration
functions.
To enter a new security code select CodE from the
configuration menu and press (which will cause
the BA567E-SS Counter to display 0000 with one
digit flashing. The flashing digit may be adjusted
using the &and *push buttons, when set as
required operating the (button will transfer control
to the next digit. When all the digits have been
adjusted press )to return to the CodE prompt. The
revised security code will be activated when the
BA567E-SS Counter is returned to the display mode.
Please contact BEKA associates sales department if
the security code is lost.
18

5.23 Reset configuration to factory defaults:
r5Et dEF
This function returns the BA567E-SS Counter to the
factory defaults shown in section 5.0. To prevent
accidental use the request must be confirmed by
entering 5urE before the configuration change will be
executed.
Select r5Et dEF from the configuration menu and
press (the instrument will display 0000 with the
first digit flashing. To confirm the instruction to reset
all the configuration functions to factory defaults
5urE must be entered. Using the &or *button
set the first flashing digit to 5and press (to
transfer control to the second digit which should be
set to u. When 5urE has been entered pressing the
)button will reset all the configuration functions to
the factory default settings and zero both the total
display and the grand total. While resetting the
BA567E-SS Counter will display - - - - - - - -
before automatically returning to the display mode
when the operation is complete.
5.24 Display overflow
The BA567E-SS Counter total has a maximum
display range of -9999999 to 99999999 when shown
on the eight digit upper display. If this range is
exceeded the display will be as shown below with all
of the decimal points flashing:
Underrange -9.9.9.9.9.9.9
Overrange 9.9.9.9.9.9.9.9
When the total is shown on the lower six digit display
the maximum display range is -99999 to 999999.
When a total overflow occurs the actual total may be
obtained from the instrument's grand total display
which has sixteen digit - see 2.3.
To prevent future total display overflows occurring
the total scale factor 5CALE .tand the position of the
decimal point in the total display dP should be
reviewed.
19

6. CONFIGURATION EXAMPLE
A BA567E-SS Counter is required to display the total
number of strokes that a reciprocating pump makes
in thousands of strokes on the larger upper display
and to show the speed of pumping in strokes per
hour on the lower display. The stroke sensor is a
proximity detector which produces four pulses per
stroke. The total display is only to be resettable by
an external contact, not from the BA567E-SS
Counter front panel. Similarly the grand total is not
to be resettable from the BA567E-SS Counter front
panel. To simplify reading the BA567E-SS display is
to be updated every 3 seconds and to prevent
tampering the instrument configuration menu is to be
protected by security code 1209.
The BA567E-SS may be configured on-site without
disconnection from the power supply or from the
proximity detector. This example assumes that the
BA567E-SS initially has default factory configuration.
If after accessing the configuration menu the interval
between operating any front panel push button
exceeds one minute the BA567E-SS will
automatically return to the display mode and any
configuration changes will not be stored in
permanent memory. When making multiple
changes it is therefore sensible to occasionally
return to the display mode to save the changes that
have already been made.
Step 1 Enter the configuration menu
Put the BA567E-SS Counter in the
configuration mode by simultaneously
pressing the (and )push buttons.
Assuming a security code has not
already been entered the instrument will
respond by displaying inPut which is the
first parameter in the configuration menu.
See Fig 8.
Step 2 Select the type of inputs
With InPut displayed; press ( to reveal
the inPut .tYPE submenu and press
(again to enter the function. Using the
&or *button select Pr.dEt, the input
for a 2-wire proximity detector and then
return to the inPut prompt in the
configuration menu by pressing )
twice. A proximity detector requires
energising therefore terminals 3 and 4 of
the BA567E-SS should be linked
together.
Step 3 Select display update
To aid reading the display the
BA567E-SS is only to be updated every
3 seconds.
Select uPdAtE from the configuration
menu and press (. Using the &or *
button select 3and press )to return to
the uPdAtE prompt in the configuration
menu.
Step 4 Define function of upper display
In the example the total number of
strokes is required on the larger eight
digit upper display.
Select dI5P-1 from the configuration
menu and press (which will reveal if
the upper display is showing rAtE or
totAL. Using the &or *button select
totAL followed by the )button to enter
the selection and return to the
configuration menu.
Step 5 Activate lower rate display
A rate display is required so the lower
display must be activated.
Select di5PLAY .2 from the main menu
and press ( to show the existing
setting. Using the &or *button
select on followed by )to enter the
selection and return to the configuration
menu.
Step 6 Position of decimal point
In this example the BA567E-SS is
required to display total and rate with no
decimal points.
Select d.P. from the configuration menu
and press (. The BA567E-SS will
show and identify the total display with all
the digits activated. Using the &or *
button position the decimal point to the
right of the least significant digit i.e. not
visible.
Operating the (button will show and
identify the rate display with all the digits
activated, Again using the &or *
button position the decimal point to the
right of the least significant digit i.e. not
visible.
Finally press )to return to the
configuration menu.
20
Table of contents
Other BEKA Cash Counter manuals