
17
5.4 Rate Totaliser function: FunCtion
This function determines whether the two separate
adjustable sixteen segment linearisers, one for each
of the two flowmeter inputs, are activated. To reveal
the existing setting select FunCtion from the
configuration menu and press (.
5td Linearisers are not activated
Lin Linearisers are activated
If the function is set as required, press )to return
to the configuration menu, or press the &or *
button to change the setting, followed by the )
button to return to the FunCtion prompt in the
configuration menu.
5td Linear
Provides a linear relationship between the pulse
input and the Rate Totaliser displays for input A
and input b.
Lin 16 segment adjustable lineariser
Activates an independent sixteen segment
adjustable lineariser for each input. When Lin is
selected functions FACtor-A and FACtor-b are
expanded to allow up to 16 values to be entered
each starting at a specified input pulse frequency.
This allows FACtor-A and FACtor-b to be set to
the K-factor of each flowmeter at multiple flow
rates thus minimising errors caused by the
nonlinearity of the flowmeter’s K-factor.
Detailed information about the lineariser, including
configuration information is contained in section 6 of
this instruction manual.
5.5 Input*: inPut-A
The Input function contains two sub-functions
inP.tYPE and dEbounCE described in the following
sections which configure the Rate Totaliser input and
define the amount of input noise rejection.
5.6 Input type: inP .tYPE
inP.tYPE is a sub-menu which appears in both the
inPut-A and input-b functions. It defines the type
of flowmeter transducer or pulse that may be
connected to the input. To check or change the type
of input, select inPut-A or input-b in the
configuration menu and press (which will reveal
the inP .tYPE prompt, pressing (again will reveal
the existing input. If set as required press )twice
to return to the configuration menu, or repeatedly
press the &or *button until the required type of
input is displayed and then press )twice to return
to the configuration menu.
One of following six types may be selected for each
input:
Switching
thresholds
Low High
VoLt5 L Voltage pulse low 113V
VoLt5 H Voltage pulse high1310V
CoiL Magnetic pick-off 0 40mV
Pr .dEt Proximity detector 21.2 2.1mA
ContACt Switch contact 2100 1000
oP,CoL Open collector 2210k
Notes:
1. Maximum voltage input +30V.
2. For flowmeter transducers connected to input A
that require energising i.e. proximity detector,
switch contact and open collector, terminals 3 &
4 of the Rate Totaliser should be linked
together. Similarly for flowmeter transducers
connected to input b that require energising,
terminals 7 & 8 should be linked together.
3. To count correctly, the input pulse must fall
below the lower switching threshold and rise
above the higher switching threshold.
4. See section 5.7 for maximum counting
frequency.
5.7 Debounce*: dEbouncE
dEbouncE is an adjustable sub-menu which appears
in both the inPut-A and input-b functions.
De-bounce prevents the Rate Totaliser miscounting
when the input pulse has noisy edges, such as
those resulting from a mechanical contact closing
and bouncing. Three levels of protection may be
selected and the amount of de-bounce applied
depends upon the type of Rate Totaliser input that
has been selected in the inP.tYPE function.
The following table shows the minimum time that the
input pulse must be continuously above the upper
input switching threshold and continuously below the
lower switching threshold to ensure that the Rate
Totaliser processes the input pulse. Input switching
thresholds are shown in section 3.2.
De-bounce
level
Minimum input pulse width
Type of input
Contact All others
Default 1,600µs 40µs
Heavy 3,200µs 350µs
Light 400µs 5µs