manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Bender
  6. •
  7. Relay
  8. •
  9. Bender cme420 Manual

Bender cme420 Manual

T M
Document NAE1038030 • 10.2012 • © Bender Inc. • Page 1/1 • Side 1/2Bender Inc. • USA: 800.356.4266 / 610.383.9200 / info@bender.org • Canada: 800.243.2438 / 905.602.9990 / [email protected] • www.bender.org
CME420
Installation Bulletin / Reference Guide
This document is intended as a reference guide for installing and using a BENDER CME420 AC cur-
rent relay. This document includes installation, setup, and usage instructions. For complete details,
including installation, setup, settings, and troubleshooting, refer to the CME420 user manual, docu-
ment number TGH1400en. This document is intended as a supplement and not a replacement to the
complete user manual.
Only qualied maintenance personnel shall operate or service this equipment. These instructions
should not be viewed as sucient for those who are not otherwise qualied to operate or service this
equipment. This document is intended to provide accurate information only. No responsibility is as-
sumed by BENDER for any consequences arising from use of this document.
Installation
Mounting
CME420 series devices may be DIN rail mounted, or screw mounted using the black clips lo-
cated on the top and bottom of the device. Screw mounting requires an extra black clip (article
number B98060008, sold separately).
!DANGER
• Disconnect all power before servicing.
• Observe all local, state, and national
codes, standards, and regulations.
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Wiring - General
Refer to gure 1 for wiring the CME420. For systems less
than 16 A, the device may be directly wired in series with
the circuit, or utilize an external x/5 ratio current trans-
former. For systems greater than 16 A, an external x/5 ra-
tio current transformer is required. Use minimum AWG
24, maximum AWG 12 size wire. Refer to CME420 series
user manual for complete technical details.
1. External supply voltage; 5A fuse
required for internal device pro-
tection
2. Direct system connection with no
current transformer (less than 16
A)
3. System connection with current
transformer
4. Alarm relay K1: SPDT contact
5. Alarm relay K2: SPDT contact
Figure 1 - CME420 wiring diagram
Front Panel Display
1. LED “ON” (green): Illuminates when
power is applied to the device. Flashes
when the CT connection alarm is active.
2. LED “AL1” (yellow): Illuminates when
the prealarm is activated. Flashes when
the CT connection alarm is active.
3. LED “AL2” (yellow): Illuminates when
the main alarm is activated. Flashes
when the CT connection alarm is active.
4. Backlit LCD display
5. TEST / UP button: Activates self-test /
scrolls up inside main menu.
6. RESET / DOWN button: Resets device /
scrolls down inside main menu.
7. MENU / ENTER button: Activates main
menu / Confirms (momuntary push) or
goes back a step (held > 1.5 s) inside
main menu.
1 2 3
4
5 6 7
Figure 2 - CME420 front display
1
2
3
4
Menu Flow Chart for Common Settings
Figure 4 through gure 8 on the reverse side of this document contain ow charts for modify-
ing commonly used features and settings in the CME420’s main menu. Not all available fea-
tures are listed in this document. For more information, consult the CME420 user manual.
R
T
Menu Legend
MENU / ENTER button
DOWN ARROW button
UP ARROW button
Momuntary button push
< 1.5 s
Hold button for at least 1.5 s,
then release
> 1.5 s
Wiring - Contacts
Using a normally closed or normally open contact utilizes two factors: wiring out of the proper
terminal, and setting the respective contact to normally energized or deenergized operation.
Refer to the chart below for relay conditions. For changing the energized state of the contact,
refer to “Figure 7 - Contact operation” on the reverse side of this document.
The factory default for the CME420 is normally deenergized operation for relays K1 and K2.
5
Dimensions
Dimensions in inches (mm).
1.42” (36)
2.78”
(70.5)
1.87”
(47.5)
1.22” (31.1)
2.66” (67.5)
1.77” (45)
3.54” (90)
Normally energized mode (N/E)
Failsafe mode
“N/C”in device settings menu
Energized in the normal state
Relay will switch when the alarm is
activated, or when supply voltage
to the device is lost.
Power ON, normal state (no alarms)
Power OFF
Power ON, alarm state
11-12 OPEN
11-14 CLOSED
11-12 CLOSED
11-14 OPEN
11-12 CLOSED
11-14 OPEN
21-22 OPEN
21-24 CLOSED
21-22 CLOSED
21-24 OPEN
21-22 CLOSED
21-24 OPEN
Normally deenergized mode (N/D)
Non-failsafe mode
“N/O”in device settings menu
Energized in the alarm state
Relay will switch when the alarm is
activated.
Power ON, normal state (no alarms)
Power OFF
Power ON, alarm state
11-12 CLOSED
11-14 OPEN
11-12 CLOSED
11-14 OPEN
11-12 OPEN
11-14 CLOSED
21-22 CLOSED
21-24 OPEN
21-22 CLOSED
21-24 OPEN
21-22 OPEN
21-24 CLOSED
Relay Operation Setting Device Alarm State K1 STATE K2 STATE
Device Relay Conditions
T M
Document NAE1038030 • 10.2012 • © Bender Inc. • Page 1/1 • Side 2/2Bender Inc. • USA: 800.356.4266 / 610.383.9200 / info@bender.org • Canada: 800.243.2438 / 905.602.9990 / [email protected] • www.bender.org
CME420
Installation Bulletin / Reference Guide
Figure 5 - Changing Time Delays
Four separate time delays are available:
• ton1 - Response delay, prewarning
• ton2 - Response delay, main alarm
• t - Startup delay
• toff - Delay on release
= Flashing Symbol
T R
ton1 Adjustment
0...10 seconds
> 1.5 sec
< 1.5 sec
< 1.5 sec
< 1.5 sec
R
Press:
1 x for ton2
2 x for t
0...10 sec
3 x for toff
0...99 sec
OR
R
Press Twice
> 1.5 sec
> 1.5 sec
Figure 6 - Latching behavior (fault memory)
Changing this setting to “ON” will cause the CME420 to latch in the event of an alarm, and re-
quire a manual reset if the alarm clears. Changing this setting to “OFF” will cause the CME420
to automatically reset if the alarm clears.
= Flashing Symbol
T R
> 1.5 sec
Press Once
Fault Memory
ON/OFF Select
> 1.5 sec
> 1.5 sec
< 1.5 sec
< 1.5 sec
< 1.5 sec
R
= Flashing Symbol
T R
Failsafe
ON/OFF Select
> 1.5 sec
Press Once
R
Press Once
R
> 1.5 sec
> 1.5 sec
< 1.5 sec
< 1.5 sec
< 1.5 sec
Figure 7 - Contact operation
Use this option to change the behavior of the contacts between normally deenergized (non-
failsafe) mode and normally energized (failsafe) mode. The two SPDT contacts may be changed
individually. Note that the CME420 labels normally deenergized operation as “N/O” and nor-
mally energized operation as “N/C”; utilzing a normally open or normally closed contact only
depends on which contact output is wired.
Figure 4 - Setting alarm type and CT ratio (if used)
The recommended rst step is to set the type of alarm that will be used. Set this option to “HI”
for undercurrent, “LO” for undercurrent, or “In” for both.
If a current transformer is being used, the ratio must be changed as well, in order to be able
to program correct values seen on the primary (no calculations are required when setting trip
values after this step is completed). Note that while an X/5 ratio CT is required for use with this
device, the ratio is entered in as if it were an X/1. For example, if a 50:5 CT is being used, enter
a value of “10”for the CT ratio value.
If the device is being directly connected to the system, leave the ratio set to 1.
= Flashing Symbol
> 1.5 sec
< 1.5 sec
< 1.5 sec
Press nothing for
overcurrent (HI)
otherwise:
R
1x for both (In)
2x for undercurrent (Lo)
T R
Ratio Adjustment
> 1.5 sec
To quit
R
OR
To set CT
ratio
x 2
Rx 3
< 1.5 sec
> 1.5 sec
> 1.5 sec
> 1.5 sec
> 1.5 sec
To quitx 2
Figure 5 - Setting Alarm Values
The CME420 has two alarm values that may be set. Use the following guidelines for setting
these numbers:
• UsingonlyovercurrentORundercurrent: Only one value is required. The value I2is the
explicit alarm value that is set. The value I1is an optional prewarning that may be acti-
vated, which is a percentage value based on the previously set trip value.
• UsingbothovercurrentANDundercurrent: Both values are required. The value I2is the
overcurrent value, entered as an explicit number. The value I1is the undercurrent value,
entered as a percentage of the previously entered overcurrent value. EXAMPLE: For an
overcurrent alarm of 20 A and an undercurrent alarm of 10 A, enter “20” for I2, and enter
“50%” for I1.
= Flashing Symbol
> 1.5 sec
T R
Setpoint
Adjustment
R
< 1.5 sec
< 1.5 sec
< 1.5 sec
< 1.5 sec
T R
Setpoint
Adjustment
< 1.5 sec
> 1.5 sec
> 1.5 sec

Other manuals for cme420

2

Other Bender Relay manuals

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Bender RCM470LY User manual

Bender

Bender RCM470LY User manual

Bender LINETRAXX VMD461 User manual

Bender

Bender LINETRAXX VMD461 User manual

Bender VME421H User manual

Bender

Bender VME421H User manual

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Bender LINETRAXX VMD258 User manual

Bender

Bender LINETRAXX VMD258 User manual

Bender EDS44 L-CN Series User manual

Bender

Bender EDS44 L-CN Series User manual

Bender cme420 User manual

Bender

Bender cme420 User manual

Bender CMD420 User manual

Bender

Bender CMD420 User manual

Bender cme420 User manual

Bender

Bender cme420 User manual

Bender EDS440 Instruction manual

Bender

Bender EDS440 Instruction manual

Bender UMS420 User manual

Bender

Bender UMS420 User manual

Popular Relay manuals by other brands

PickData SEM One manual

PickData

PickData SEM One manual

Viessmann 5551 Operation manual

Viessmann

Viessmann 5551 Operation manual

F&F BIS-404 quick start guide

F&F

F&F BIS-404 quick start guide

Aqara T1 quick start guide

Aqara

Aqara T1 quick start guide

Moeller NZM-XDMI 612 installation instructions

Moeller

Moeller NZM-XDMI 612 installation instructions

Schweitzer Engineering Laboratories SEL-321-2 instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-321-2 instruction manual

GE Masoneilan 469 Series Communications guide

GE

GE Masoneilan 469 Series Communications guide

Omron ZEN Communications manual

Omron

Omron ZEN Communications manual

elco SSRSMC3/32 Series quick start guide

elco

elco SSRSMC3/32 Series quick start guide

Siemens SIRIUS 3RT161 1A 3 Series Original operating instructions

Siemens

Siemens SIRIUS 3RT161 1A 3 Series Original operating instructions

PickData ACTIO 24 quick start guide

PickData

PickData ACTIO 24 quick start guide

EUCHNER ESM-2H2 Series operating instructions

EUCHNER

EUCHNER ESM-2H2 Series operating instructions

GE B90 instruction manual

GE

GE B90 instruction manual

Danfoss Link BR installation guide

Danfoss

Danfoss Link BR installation guide

Broyce Control P9600 Series quick start guide

Broyce Control

Broyce Control P9600 Series quick start guide

Crydom DC60 Series Installation sheet

Crydom

Crydom DC60 Series Installation sheet

EVA Logik ZW11 manual

EVA Logik

EVA Logik ZW11 manual

Chenzhu CZ3047T user manual

Chenzhu

Chenzhu CZ3047T user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.