Bender EDS440 Instruction manual

ISOSCAN® EDS440 and EDS441
Insulation fault locator to locate insulation faults in
ungrounded DC, AC and three-phase power supplies
EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS441 Insulation fault locator to locate insulation faults in
ungrounded DC AC and three-phase power supplies
System properties
•Universal system design
•Modular design, therefore easily
adjustable to the given circumstances
•Measuring current transformers
available in various sizes and versions
•CT connection monitoring
•Twelve measuring channels for series
W…, WR…, WS… measuring current
transformers
•Optional extension by twelve relay
channels
•Fault memory behaviour selectable
•Up to 50 EDS insulation fault locators in
the system, 600 measuring channels
•Response sensitivity:
– EDS440…: 2… 0 mA
– EDS44 …: 0.2… mA
•AC residual current measurement with
configurable response value
•Two alarm relays with one n/o contact
each
•n/o or n/c operation selectable
•External test/reset button
•Central display of faulty outgoing
circuits
•Serial interface RS-485, BS bus address
range 2…79
•Connection to higher-level control and
visualisation systems possible.
Intended use
The insulation fault locators ISOSCAN® EDS440 and EDS44 are used to locate insulation
faults in unearthed DC, AC and three-phase power supply systems (IT systems).
Depending on the locating current injector, AC and three-phase systems can be
monitored within the range from AC 42 to 000 V; DC systems, within the range from
DC 24 to 500 V.
An AC residual current can be indicated in these ranges:
•EDS440: 42… 000 Hz, 0. …20 A
•EDS44 : 42…60 Hz, 0. …2 A
An EDS system (insulation fault location system) consists of an EDS44x insulation
fault locator and a locating current injector. EDS44… insulation fault locators detect
locating current signals generated by the locating current injector via measuring current
transformers and evaluate them accordingly.
Intended use also implies
•the observation of all information in the operating manual and
•compliance with test intervals.
In order to meet the requirements of the applicable standards, customised parameter
settings must be made on the equipment in order to adapt it to local equipment and
operating conditions. Please heed the limits of the range of application indicated in the
technical data.
Do not make any unauthorised changes to the device. Only use spare parts and optional
accessories sold or recommended by the manufacturer.
The messages of the device must be perceptible even if it is installed in a control cabinet.
The devices is not designed for use in residential areas and may not provide sufficient
protection for radio reception there.
Any other use than that described in this manual is regarded as improper.
Areas of application
•Insulation fault location in AC, 3(N)AC and DC IT systems
•Main circuits and control circuits in industrial plants and ships
•Diode-decoupled DC IT systems in power plants
•Systems for medical locations
Standards
The standard for unearthed power supplies (IT systems)
DIN VDE 0100-410 (VDE 0100- 410):2018-10 (IEC 60364-4-41:2005, modified + A1:2017,
modified)
requires that the first insulation fault is to be eliminated with the shortest practicable
delay. EDS systems enable fast localisation of this insulation fault.
2 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Operating principle of the EDS system
When an insulation monitoring device detects an insulation fault,
it starts the insulation fault location.
In the event of a first insulation fault, an undefined residual
current flows in IT systems, which is primarily defined by the
system leakage capacitances and the value of the insulation fault.
The basic idea of insulation fault location is therefore to generate a
defined locating current IL that flows through the insulation fault.
The locating current is driven by the system voltage and can be
located in the faulty outgoing circuit using the measuring current
transformer.
The locating current is generated by the locating current injector.
It is limited in amplitude and time. The amplitude depends on the
size of the existing insulation fault and the system voltage. It is
limited depending on the settings.
The locating current flows from the locating current injector via
the live lines to the insulation fault location taking the shortest
route. From there, it flows through the insulation fault and the
earth conductor back to the locating current injector. This locating
current pulse is detected by the measuring current transformers
on the insulation fault path and signalled by the connected
insulation fault locator.
System variants
The devices ISOSCAN® EDS440 and EDS44 differ depending on their response sensitivity. EDS440 is suitable for main circuits. EDS44
can be used in control circuits and in circuits in medical locations.
-L -S -LAB-4 -LAF-4
EDS440 Channel LED
BS bus
IΔL = 2…10 mA
Main circuits
Digital in uts and out uts
No channel LED
BB bus
IΔL = 2…10 mA
Main circuits
No internal voltage su ly
Channel LED
BS bus
IΔL = 10 mA 2)
Main circuits
Digital in uts and out uts
EDS441 Channel LED
BS-Bus
IΔL = 0.2…1 mA
Control circuits
Digital in uts and out uts
No channel LED
BB bus
IΔL = 0.2…1 mA
Control circuits
No internal voltage su ly
Channel LED
BS-Bus
IΔL = 0.2…1 mA 1)
Control circuits
W…AB current transformers
Digital in uts and out uts
) High response sensitivity with large system leakage capacitances
2) In combination with CTAF...SET series measuring current transformers
EDS44x_D0020 _ _D_XXEN/ .2023 3
ISOSCAN® EDS440 and EDS44
Display elements EDS44…-S
ON
Status LED
ON Flashes: Starting rocess; hourly transformer connection test
Lights u : o erational
Operating and display elements EDS44…-L
-1
>3s
ADDR.
RESET
+1
+10
TEST
CHANNELS / ADDR.
12
11109
87
345621
+10 +20 +40
Addr. Mode
n
∆
I
ALARM
L
∆
I
ALARM
SERVICE
COM/ADDR.
ON
Status LEDs
ON Flashes: Starting rocess; hourly transformer connection
test
Lights u : o erational
COM/ADDR. Flashes quickly: device communicates via RS-485
interface
Flashes: insulation fault location (LED indicate the ulse
of the locating current injector:
ulse = on; ause = off. In LAB rocedure, the ulse can
last one minute.)
SERVICE Lights u : device error; connection fault of the measuring
current transformers; error message e.g. due to low-
frequency residual currents, external magnetic fields, etc.
ALARM IΔL Lights u : main alarm, insulation fault on one of the
measuring channels (EDS function)
ALARM IΔn Lights u : res onse value for residual currents is
exceeded.
Channel LEDs 1 to 12
CHANNELS /
ADDR.
Lights u : insulation fault on the res ective measuring
channel or residual current alarm
Flashes slowly (1 Hz): connection fault of the measuring
current transformer
Flashes quickly (2 Hz): interference during insulation fault
location
Addr. Mode Indication of the resent tens counter by means of the
channel LEDs 10, 11 and 12
Operating buttons
TEST
+10
Starts self test.
In address assignment mode: increase address in ste s of
ten.
RESET
+1
Resets the fault memory. Only ossible if the fault
memory is activated and a fault is no longer detected.
In address assignment mode: increase address in ste s of
one.
ADDR.
–1
Long ress (>3 s): activates the address assignment
mode.
In address assignment mode: decrease address in ste s of
one.
4 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Connection to the voltage supply
A1 A2
12 3 4 5 6 7 8 9 10 11 12
L
Us =AC/DC 24...240 V
A1/+ A2/–
L1/+
L2/–
Voltage supply back-up fuse
If the device is supplied via an external power supply unit,
the back-up fuse Fback-up at connection “A /+ A2/−” must be
selected in such a way that the feeding power supply unit is
able to trip the DC-compatible back-up fuse.
Example:
A back-up fuse of 650 mA/T is recommended when using a
24 V power supply unit (min. A).
Connection of the X1 interface (I1 I2 A B M+ ...)
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
I1
I2 A B
A B
M+
I1 In ut 1 M+ dig. current out ut
I2 In ut 2 Ground
ARS-485 A (in ut) ARS-485 A (out ut)
BRS-485 B (in ut) BRS-485 B (out ut)
The EDS44…-L is connected via the X plug.
The EDS44…-S does not feature an X interface and can
only be connected via the BB bus.
Connection of the relays
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
23 24
13 14
13 23
Alarm relay 1 14 n/o contact Alarm relay 2 24 n/o contact
BS bus termination
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
OFF ON
R
Activating a terminating resistor to define the first and the last
device in the bus system.
OFF All devices between the first
and the last device in the bus
ON First and last device in a bus
Connection of the X2 interface (k1-12/l1-12)
A1 A2
12 3 4 5 6 7 8 9 10 11 12
L
l 1 l 12l 11l 2 l 10l 9l 8l 7l 6l 5l 4l 3
k 1 k12k11k 2 k10k 9k 8k 7k 6k 5k 4k 3
l1 Measuring current
transformer 1
k1
l2 Measuring current
transformer 2
k2
l3 Measuring current
transformer 3
k3
l4 Measuring current
transformer 4
k4
………
l12 Measuring current
transformer 12
k12
Cable lengths of the measuring current transformers
In tall the mea uring current tran former according to the
in truction in the re pective data heet of the mea uring
current tran former. When connecting, ob erve the maximum
cable length .
EDS44x_D0020 _ _D_XXEN/ .2023 5
ISOSCAN® EDS440 and EDS44
Connection of CTAC… series measuring current transformers
For insulation fault location, the measuring current transformers
of the CTAC… series are used.
A1/+ A2/-
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
Type A
CTAC 1
kl
CTAC 2
kl
l1 k1 l2 k2
l k l k
CTAC… series measuring current transformers
Terminals and 2 as well as terminals 3 and 4 of the
measuring current transformer are bridged internally.
The connections k and l must not be interchanged on the
EDS44….
Live conductors and measuring current transformers
Ensure that all live conductors are routed through the
measuring current transformer. Do not route any existing
PE conductors or shields of shielded cables through the
measuring current transformer! Standard measuring
current transformers are not suitable for the EDS44…
system and must not be used. An accurate measurement
result can only be obtained when these instructions are
observed.
For further information regarding measuring current
transformers, refer to the respective data sheets.
Connection of CTAF…SET series measuring current
transformers to EDS440-LAF-4
For insulation fault location, the measuring current transformers
of the CTAF…SET series are used.
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
l1 k1 l2
Typ A
k2
2
1
1
2
Locating current
The EDS440-LAF-4 operates exclusively with a locating
current > 0 mA.
Connection of measuring current transformer CTBC… to
EDS441-LAB-4
CTXS…
CTBC…
24V GND
k
l
1 m
2.5 m
5 m
10 m
50 mm
250 mm
EDS441-LAB STEP-PS
power supply
CTUB102
24V
GND
S1(k)
S2(l)
Locating current
The EDS44 -LAB-4 operates exclusively with a locating
current of max. 25 mA. Therefore, selecting the current
range >500 mA on the current transformer is not suitable
for measuring locating currents <25 mA.
6 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Connection to a 3(N)AC system
A BA B
iso685-D-P EDS44…-L/-S
Un
L1
L2
L3
N
PE
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
EDS44x_D0020 _ _D_XXEN/ .2023 7
ISOSCAN® EDS440 and EDS44
Connection to a DC system
A BA B
iso685-D-P EDS44…-L/-S
L+
L–
PE
Un
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
8 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Connection to an AC system
A BA B
iso685-D-P EDS44…-L/-S
Un
L1
L2
PE
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
EDS44x_D0020 _ _D_XXEN/ .2023 9
ISOSCAN® EDS440 and EDS44
Connection example: ISOMETER® iso685-D-P EDS440-S IOM441-S and EDS440-L
A BA B
A1/+ A2/-
RX2 11 12 14 21 22 24
L1/+
L2 L3/- KE E
X1
l1 l2 l3 A B
iso685
ISOMETER
®
EDS440
ISOSCAN
®
I
ΔL
I
Δn
X1
l1 l2 A B
13 14 23 24
A1/+ A2/-
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
Us
IOM441
123144 124104103 1139384 947473 83
6354 644443 533324 341413 23
13 14
L1
L2
L3
N
PE
UsUs
Un
iso685-D-P EDS44…-S IOM441 EDS44…-L
KEL3/-L2 E
A1/+ L1/+A2/- A1/+ A2/-
l1 k1 l2 k2l1 k1 l2 k2
Communication between iso685-...-P and EDS44...-L runs exclusively via BS bus (RS-485).
0 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Technical data ISOSCAN® EDS440 and EDS441
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Definitions
Su ly circuit (IC1) A1, A2
Out ut circuit 1 (IC2) 13, 14
Out ut circuit 2 (IC3) 23, 24
Control circuit (IC4) (A1, A2), (13, 14) - (23, 24) - (X1, X3)
Rated voltage 1000 V
Overvoltage category III
Range of use ≤2000 m AMSL
Rated im ulse voltage
IC1/(IC2-4) 4 kV
IC2/(IC3-4) 4 kV
IC3/(IC4) 4 kV
Rated insulation voltage
IC1/(IC2-4) AC 250 V
IC2/(IC3-4) 250 V
IC3/IC4 250 V
Pollution degree outside (Un <
690 V)
3
Pollution degree outside (Un >
690 V < 1000 V)
2
Protective se aration (reinforced insulation) between
IC1/(IC2-4) Overvoltage category III, 1000 V
IC2/(IC3-4) Overvoltage category III, 300 V
IC3/IC4 Overvoltage category III, 300 V
Voltage tests (routine test) acc. to IEC 61010-1
IC2/(IC3-4) AC 2.2 kV
IC3/IC4 AC 2.2 kV
Supply voltage
Su ly voltage range Us EDS44...-L (…-LAB,
…-LAF)
AC/DC 24…240 V
Su ly voltage range Us EDS44...-S DC 24 V
Tolerance of Us−20…+15%
Frequency range of UsDC, 50…400 Hz 1) 2)
Tolerance: −5…+15 %
Power consum tion, ty ically 50 Hz (400
Hz) EDS44...-L
≤4 W / 7 VA (≤4 W, 28 VA)
Power consum tion, ty ically (DC via BB
bus) EDS44...-S
≤1 W
) At a frequency > 200 Hz, the connection of X and k - 2/l - 2 must be insulated.
Only permanently installed devices which at least have overvoltage category
CAT2 (300 V) may be connected.
2) Only 50/60 Hz are permitted for UL applications.
Response values
EDS440 EDS441
Res onse value for insulation fault
location (IΔL)
2…10 mA 0.2…1 mA
Relative uncertainty (IΔL) 3) ±30 %,
min. ±2 mA
±30 %,
min. ±0.2 mA
Res onse value for residual current
measurement (IΔn)
0.1…10 A 0.1…1 A
Relative uncertainty (IΔn) 42…60 Hz ±5 % ±5 %
Relative uncertainty (IΔn)
61…1000 Hz
−20…0 % −20…0 %
Hysteresis 20 % 20 %
3) Residual current effect of > 00 mA results in a greater relative uncertainty.
Time response
Scanning time for all channels for
insulation fault location (IΔL)
rofile-de endent, min. 6 s
Res onse time for residual current
measurement (IΔn)
≤ 400 ms
Res onse time for measuring current
transformer monitoring
max. 18 min
Measuring circuit
Nominal system voltage Un EDS440 refer to locating current injector
(e.g. ISOMETER® iso685-D-P)
Nominal system voltage Un EDS441 AC 230 V ±15 %
DC 220 V ±40 %
External measuring current
transformers for EDS440
W…, WR…, WS…
External measuring current
transformers for EDS441
W…/8000, WS…/8000
External measuring current
transformers for EDS441-LAB
CTUB102
External measuring current
transformers for EDS440-LAF
CTAF…
Load EDS440 47 Ω
Load EDS441, EDS440-LAF 1.5 kΩ
Rated insulation voltage, measuring
current transformers
800 V
Connection of EDS measuring current transformers
Single wire ≥0.75 mm² 0…1 m
Single wire, twisted ≥0.75 mm² 1…10 m
Shielded cable ≥0.5 mm² 10…40 m
Recommended cable (shielded, shield
connected to earth on one side)
J-Y(St)Y min. 2 × 0.8
EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Measuring ranges insulation fault location IΔL
Rated frequency range DC, 16.7…1000 Hz
Measuring range, insulation fault
location (IΔL) EDS440
1.5…50 mA
Measuring range, insulation fault
location (IΔL) EDS441
0.15…5 mA
Maximum ermissible residual
current
see Diagrams in the manual
Measuring range residual current measurement IΔn
Measuring range, residual current measurement
(IΔn) EDS440
0.1…20 A
Rated frequency range EDS440-… 50…1000 Hz
Measuring range, residual current measurement
(IΔn) EDS441
0.1…2 A
Rated frequency range EDS441-… 50…60 Hz
LEDs
ON (o eration LED) green
COM yellow
SERVICE yellow
ALARM IΔL yellow
ALARM IΔn yellow
1…12 channel indication yellow
Digital inputs
Number 2
O erating mode, adjustable active high, active low
Function none, test, reset
Voltage level low DC −5…5 V, high DC 11…32 V
Digital current output
Number 1
Function none, alarm IΔL, alarm IΔn, device error, current
transformer connection fault, common alarm,
BS bus malfunction
Current 0 mA DC inactive, 20 mA DC active
Tolerance ±10 %
Load
resistance
R ≤ 500 Ω / PR ≥ 0.25 W
Buzzer
Number 1
Function none, alarm IΔL, alarm IΔn, device error, CT connection
fault, insulation fault location active, common alarm
Interfaces
Interface/ rotocol RS-485 | BS-Bus | Modbus RTU
Data rate BS bus 9.6 kBd
Data rate Modbus RTU 9.6 | 19.2 | 37.4 | 57.6 | 115 kBd
Cable length ≤ 1200 m
Cable: twisted air, shield
connected to earth on one side
recommended: J-Y(St)Y min. 2 × 0.8
Connection X1.A, X1.B
Terminating resistor 120 Ω, built-in, switchable
Device address, BS bus 0, 2…79 (o tional 0, 2…159)
Schaltglieder
Switching elements 2 n/o contacts
O erating mode n/c, n/o
Function of contact 13, 14 none, alarm IΔL, alarm IΔn, device error, CT
connection fault, common alarm, BS bus
malfunction
Function of contact 23, 24 none, alarm IΔL, alarm IΔn, device error, CT
connection fault, common alarm, BS bus
malfunction
Electrical endurance under
rated o erating conditions
30,000 h
Rated o erational voltage AC 250 V
Rated o erational current 7 A
Rated insulation voltage 4 kV
Contact data acc. to IEC 60947-5-1
Utilization category AC-13 / AC-14 / DC-12 / DC-12 / DC-12 / DC-12
Rated o erational
voltage
230 V / 230 V / 24 V / 48 V / 110 V / 220 V
Rated o erational
current
5 A / 3 A / 1 A / 1 A / 0.2 A / 0.1 A
Max. switching ca acity 300 W / 2770 VA
Max. switching voltage DC 30 V / AC 277 V
Minimum contact rating 11 mA at AC/DC ≥10 V
Environment/EMC
EMC IEC 61326-2-4
Ambient tem eratures
O erating tem erature −25…+55 °C
Trans ort −40…+85 °C
Storage −25…+70 °C
Climatic conditions IEC 60721
Stationary use (IEC 60721-3-3) 3K22
Trans ort (IEC 60721-3-2) 2K11
Long-term storage (IEC 60721-3-1) 1K22
Mechanical conditions nach IEC 60721
Stationary use (IEC 60721-3-3) 3M11
Trans ort (IEC 60721-3-2) 2M4
Long-term storage (IEC 60721-3-1) 1M12
2 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Connection
Screw- ype erminals
Tightening torque 0.5…0.6 Nm (5…7 lb-in)
Conductor sizes AWG 24-12
Stri ing length 7 mm
Rigid/flexible 0.2…2.5 mm²
Flexible with ferrule, with/without lastic
sleeve
0.25…2.5 mm²
Multi le conductor, rigid 0.2…1 mm²
Multi le conductor, flexible 0.2…1.5 mm²
Multi le conductor, flexible with ferrule
without lastic sleeve
0.25…1 mm²
Multi le conductor, flexible with TWIN ferrule
with lastic sleeve
0.5…1.5 mm²
Push-wire erminals
Conductor sizes AWG 24-12
Stri ing length 10 mm
Rigid/flexible 0.2…2.5 mm²
Flexible with ferrule, with/without lastic
sleeve
0.25…2.5 mm²
Multi le conductor, flexible with TWIN ferrule
with lastic sleeve
0.5…1.5 mm²
Push-wire erminals X1, X2
Conductor sizes AWG 24-16
Stri ing length 10 mm
Rigid/flexible 0.2…1.5 mm²
Flexible with ferrule without lastic
sleeve
0.25…1.5 mm²
Flexible with ferrule with lastic
sleeve
0.25…0.75 mm²
Other
O erating mode continuous o eration
Mounting
ambient tem erature > 55 °C vertical
ambient tem erature < 55 °C any alignment
Degree of rotection, internal
com onents
IP40
Degree of rotection, terminals IP20
DIN rail mounting IEC 60715
Screw fixing 2 × M4 with mounting cli
Enclosure material olycarbonate
Flammability class UL 94 V-0
Dimensions in mm (W × H × D) 72 × 93 × 63
Weight
EDS44…-S a rox. 122 g
EDS44…-L, …-LAB, …-LAF a rox. 242 g
“W” option data deviating from the standard version
Devices with the suffix “W” feature increased shock and vibration
resistance. The electronics is covered with a special varnish to
provide increased protection against mechanical stress and
moisture.
Ambien empera ures
O erating tem erature −40…+70 °C
Trans ort −40…+85 °C
Long-term storage −25…+70 °C
Clima ic condi ions acc. o IEC 60721
Stationary use (IEC 60721-3-3) 3K23
Mechanical condi ions acc. o IEC
60721
Stationary use (IEC 60721-3-3) 3M12
External dimensions of EDS44… and IOM441-S
93
7 ,7 48,5
62,9
66,9
45
External dimensions in mm
EDS44x_D0020 _ _D_XXEN/ .2023 3
ISOSCAN® EDS440 and EDS44
Standards and certifications
Observe the applicable national and international standards.
The EDS44… series meets the device standards:
•DIN VDE 0 00-4 0 (VDE 0 00-4 0)
•DIN EN 6 557-9 (VDE 04 3-9)
•IEC 6 557-9
•DIN EN 50 55 (VDE 0 5-200)
•DIN EN 45545-2:20 6
Subject to change! The specified standards take into account the
edition valid until 08/2 unless otherwise indicated.
The operating manuals for the individual system components
provide you with information about the standards that apply to
that particular device.
EU declaration of conformity
Hereby, Bender GmbH & Co. KG declares that the device covered
by the Radio Directive complies with Directive 20 4/53/EU. The
full text of the EU Declaration of Conformity is available at the
following Internet address:
www.bender.de/fileadmin/content/Products/CE/
CEKO_EDS44x.pdf
Ordering data
Insulation fault locators
Type Supply vol age US
(absolu e values)
Response value Ar . no.
EDS440-S-1 DC 24 V 2…10 mA B91080201
EDS440W-S-1 DC 24 V 2…10 mA B91080201W
EDS440-L-4 AC/DC 24…240 V 2…10 mA B91080202
EDS440W-L-4 AC/DC 24…240 V 2…10 mA B91080202W
EDS441-S-1 DC 24 V 0.2…1 mA B91080204
EDS441W-S-1 DC 24 V 0.2…1 mA B91080204W
EDS441-L-4 AC/DC 24…240 V 0.2…1 mA B91080205
EDS441W-L-4 AC/DC 24…240 V 0.2…1 mA B91080205W
EDS441-LAB-4 AC/DC 24…240 V 0.2…1 mA B91080207
EDS441W-LAB-4 AC/DC 24…240 V 0.2…1 mA B91080207W
EDS440-LAF-4 AC/DC 24…240 V 10 mA B91080209
4 EDS44x_D0020 _ _D_XXEN/ .2023
ISOSCAN® EDS440 and EDS44
Accessories
Descrip ion Ar . no.
EDS440/441 mechanical accessories com rising:
terminal cover and 2 mounting cli s (sco e of delivery)
B91080903
EDS440/441 lug kit, screw terminals (sco e of delivery) B91080901
EDS440/441 lug kit, ush-wire terminals B91080902
BB bus 4TE lug connection
(sco e of delivery EDS44x(W)-S-1)
B98110002
Type Supply vol age USAr . no.
DI-1 PSM
(RS-485 re eater)
AC/DC 24 V
±20 %
B95012044
DI-2 USB (interface con-
verter RS-485/USB)
with USB cable
Su lied by USB interface B95012045
IOM441-S (in ut/
out ut module)
12-way relay module B95012057
AC, 100…250 V
50/60 Hz, DC ±12 V
B74053100AN420 (PSU for W...AB
current transformers)
DC, 100…250 V, DC ±12 V B94053100
AN471 (PSU for
DI-1 or DI-2)
AC 230 V 50/60
Hz AC, DC 20 V
B924189
Sna -on mount-
ing W20…/35…
B98080501
Sna -on mounting W60… B98080502
Measuring current transformers
For further information regarding the measuring current
transformers, refer to the data sheets.
Measuring current transformers for EDS440
Recommended Bender measuring current transformers
Type In ernal diame er
in mm
Design ype Ar . no.
CTAC20 ø20 circular B98110005
CTAC35 ø35 circular B98110007
CTAC60 ø60 circular B98110017
CTAC120 ø120 circular B98110019
CTAC120 ø210 circular B98110020
Alternative measuring current transformers from the Bender
program
Type Dimensions / in er-
nal diame er in
mm
Design ype Ar . no.
CTAS50 ø50 s lit-core B98110009
CTAS80 ø80 s lit-core B98110010
CTAS120 ø120 s lit-core B98110011
W10/600 ø10 circular B911761
W0-S20 ø20 circular B911787
W1-S35 ø35 circular B911731
W2-S70 ø70 circular B911732
W3-S105 ø105 circular B911733
W4-S140 ø140 circular B911734
W5-S210 ø210 circular B911735
WR 70x175S 70 × 175 rectangular B911738
WR
115x305S
115 × 305 rectangular B911739
WR
150x350S
150 × 350 rectangular B911740
WR
200x500S
200 × 500 rectangular B911763
WR
70x175SP
70 × 175 rectangular B911790
WR
115x305SP
115 × 305 rectangular B911791
WR
150x350SP
150 × 350 rectangular B911792
WR
200x500SP
200 × 500 rectangular B911793
WS 50x80S 50 × 80 s lit-core B911741
WS 80x80S 80 × 80 s lit-core B911742
WS 80x120S 80 × 120 s lit-core B911743
WS 80x160S 80 × 160 s lit-core B911755
EDS44x_D0020 _ _D_XXEN/ .2023 5
Measuring current transformers for EDS441
Recommended Bender measuring current transformers
Type In ernal diame er
in mm
Design ype Ar . no.
CTAC20/01 ø20 circular B98110006
CTAC35/01 ø35 circular B98110008
Alternative measuring current transformers from the Bender
program
Type Dimensions / in er-
nal diame er in
mm
Design ype Ar . no.
CTAS50/01 ø50 s lit-core B98110012
CTAS80/01 ø80 s lit-core B98110013
CTAS120/01 ø120 s lit-core B98110014
W10/8000 ø10 circular B911759
W1-35/8000 ø35 circular B911756
WS20x30/8000 20 × 30 s lit-core B911764
WS50x80/8000 50 × 80 s lit-core B911757
W10/8000-6 ø10 circular, 6-fold B911900
Measuring current transformers for EDS441-LAB
Bender measuring current transformers
Type In ernal diame er
in mm
Design ype Ar . no.
CTUB102-
CTBC20P
ø20 circular B78120021
CTUB102-
CTBC35P
ø35 circular B78120023
CTUB102-
CTBC60P
ø60 circular B78120025
Measuring current transformers for EDS440-LAF
Bender measuring current transformers
Typ Dimensions in mm Design ype Ar . no.
CTAF500SET 500 flexible B98110022
CTAF1000SET 1000 flexible B98110023
Bender GmbH & Co. KG
Londorfer Straße 65
35305 Grünberg
Germany
Tel.: +49 640 807-0
[email protected]
www.bender.de
© Bender GmbH & Co. KG, Germany
Subject to change!
The specified standards take into account the
edition valid until .2023 unless otherwise
indicated.

This manual suits for next models

12

Other Bender Relay manuals

Bender cme420 User manual

Bender

Bender cme420 User manual

Bender LINETRAXX VMD461 User manual

Bender

Bender LINETRAXX VMD461 User manual

Bender RCM470LY User manual

Bender

Bender RCM470LY User manual

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Bender LINETRAXX VMD258 User manual

Bender

Bender LINETRAXX VMD258 User manual

Bender EDS44 L-CN Series User manual

Bender

Bender EDS44 L-CN Series User manual

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Bender CMD420 User manual

Bender

Bender CMD420 User manual

Bender cme420 Manual

Bender

Bender cme420 Manual

Bender VME421H User manual

Bender

Bender VME421H User manual

Bender cme420 User manual

Bender

Bender cme420 User manual

Bender UMS420 User manual

Bender

Bender UMS420 User manual

Bender IOM441-S User manual

Bender

Bender IOM441-S User manual

Popular Relay manuals by other brands

Sven OVP-17P user manual

Sven

Sven OVP-17P user manual

Pilz PNOZ X4 operating instructions

Pilz

Pilz PNOZ X4 operating instructions

Stahl 9174/10-14-00 operating instructions

Stahl

Stahl 9174/10-14-00 operating instructions

Davin DV-12K manual

Davin

Davin DV-12K manual

COQON UPSPFMB1 manual

COQON

COQON UPSPFMB1 manual

Schrack LSD6 Series operating instructions

Schrack

Schrack LSD6 Series operating instructions

ABB REM 610 Product guide

ABB

ABB REM 610 Product guide

Pilz PST 4 operating instructions

Pilz

Pilz PST 4 operating instructions

Pickering PXI 40-780A user manual

Pickering

Pickering PXI 40-780A user manual

System Sensor R-10TA Installation and maintenance instructions

System Sensor

System Sensor R-10TA Installation and maintenance instructions

Zamel exta PBM-07 Manual instruction

Zamel

Zamel exta PBM-07 Manual instruction

Siemens SIRIUS 3UG4617 operating instructions

Siemens

Siemens SIRIUS 3UG4617 operating instructions

ABB REM 610 installation manual

ABB

ABB REM 610 installation manual

Crouzet MWS manual

Crouzet

Crouzet MWS manual

Schrack LSD3 Series operating instructions

Schrack

Schrack LSD3 Series operating instructions

TECO SG2 PLR user manual

TECO

TECO SG2 PLR user manual

Taco SR502-4 instruction sheet

Taco

Taco SR502-4 instruction sheet

Plejd REL-02 installation manual

Plejd

Plejd REL-02 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.