Beninca CP.BULL OMI User manual

DRAFT
CP.BULL OMI
UNIONE NAZIONALE COSTRUTTORI
AUTOMATISMI PER CANCELLI, PORTE
SERRANDE ED AFFINI
IT
EN


3
14
JP1
J7
SW1
F4
M
8k2
DAS
II°Ch. Radio
L
N
GND
GND
Shield
N
L
SCA
SERVICE LIGHT
-
+24 Vdc 0.5A
BRAKE
RESISTOR
PHOTO TEST
(fig.15) OPEN/CLOSE
JP1 BAR
Open
DAS N.C.
JP1 BAR
Close
DAS 8K2
U1
LD1
LD2
MOT
MOT
COM
15AT 250Vac
5A
P3
J6
J8
CON1
5A
/DAS
10mm
MAX
RG 58

4
15
16
COM
NCNO
RX2
TX2
24 Vdc
PHOTC
COM
PHOTO
TEST
COM
NCNO
RX1
TX1
24 Vdc
PHOTO
COM
PHOTO
TEST
PHOTOTEST OPEN
PHOTOTEST CLOSE
+- +- +-+-
OPEN
OPEN
LOG MINV=OFF
LOG MINV=ON
OPEN
OPEN
LOG MINV=OFF
LOG MINV=ON
17
SCA 24Vac
AUX: 0
Aux: 1
L
N
Service Light
230V
SCA
24V
+
-
MAX 16A
250Vac
MAX 16A
250Vac
LOGIC MINV
SCA
SERVICE LIGHT

5
OPEN
Open Safety Edge
COM PHOTO
Close Safety Edge
(8K2/N.O. Jumper)
DAS DAS
MOTOR
JP1
Open
DAS N.C.
JP1
Close
DAS 8K2
N.C.
19
bar:On
BAR LOGIC=ON

6
par
LOG
LOG
v1.00
8888 PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
tca
ped
tsmo
tsmc
tm
fstc
sldo
sldc
pMo
pmc
seav
40
20
20
20
240
fsto
45
25
25
70
70
1
sear 1
blo 3
45
PAR PAR
res PRG
OFF PRG
0012 3456
Nman
MACI
RES
Power ON
Display OFF
Firmware Ver. (3s)
Diagnostic
off PRG
OFF PRG
OFF PRG
OFF PRG
OFF PRG
LOG tca
IBL
IBCA
SCL
PP
OFF PRG
PRE
OFF PRG
off PRG
off PRG
OFF PRG
off PRG
off PRG
off PRG
off PRG
TCA
htr
ltca
pho1
pho2
tst1
tst2
bar
minv
PRG
blc 3
PRG
PRG
PRG
PRG
PRG
PRG
tls
tacc
tdec
60
20
50
tbr
7
spin
2
aux
0
0000 conf OK
CODE
par
9000 9C5a
AUTO OK
PUSH
RE-ENTER
CODE
Display OFF
2 Cycle
OPEN/CLOSE
tca
PRG
PRG
PRG
PRG
mot1 0 0
1
2
3
1
2
3
YAK 25
BULL 15OMI
115Vac
BULL 15OMI
230Vac
_ _ _ _ _ _
0

7
Legenda
Premere il tasto (-) / Press key (-) / Die Taste (-) drücken
Appuyez sur la touche (-) / Presionar la tecla (-) / Wcisnąć przycisk (-)
Premere simultaneamente (+) e (-) / Press simultaneously keys (+) and (-)
Gleichzeitig (+) und (-) drücken / Presser simultanément (+) et (-)
Presionar simultáneamente (+) y (-) / Naciskać jednocześnie (+) i (-)
Premere il tasto (+) / Press key (+) / Die Taste (+) drücken
Appuyez sur la touche (+) / Presionar la tecla (+) / Wcisnąć przycisk (+)
Selezionare il valore desiderato con i pulsanti (+) e (-)
Increase/decrease the value with keys (+) and (-)
Mit den Tasten (+) und (-) kann man eingerichtete Werte ändern
Régler la valeur désirée avec les touches (+) et (-)
Establecer con las teclas (+) y (-) el valor deseado
Nastawia przyciskami (+) i (-) obraną wartoś
Premere il tasto (PG) / Press key (PG) / Die Taste (PG) drücken
Appuyez sur la touche (PG) / Presionar la tecla (PG )/ Wcisnąć przycisk
(PG)
Selezionare il pulsante del trasmettitore da associare alla funzione
Press the transmitter key, which is to be assigned to function
Taste des Sendegeräts drücken, dem diese Funktion zugeteilt werden soll.
Appuyer sur la touche du transmetteur qu’e l’on désire affecter à cette
fonction.
Presionar la tecla del transmisor que se desea asignar a esta función.
Wcisnąć przycisk nadajnika, który zamierza się skojarzyć z tą funkcją.
par
LOG
LOG
v1.00
8888 PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
tca
ped
tsmo
tsmc
tm
fstc
sldo
sldc
pMo
pmc
seav
40
20
20
20
240
fsto
45
25
25
70
70
1
sear 1
blo 3
45
PAR PAR
res PRG
OFF PRG
0012 3456
Nman
MACI
RES
Power ON
Display OFF
Firmware Ver. (3s)
Diagnostic
off PRG
OFF PRG
OFF PRG
OFF PRG
OFF PRG
LOG tca
IBL
IBCA
SCL
PP
OFF PRG
PRE
OFF PRG
off PRG
off PRG
OFF PRG
off PRG
off PRG
off PRG
off PRG
TCA
htr
ltca
pho1
pho2
tst1
tst2
bar
minv
PRG
blc 3
PRG
PRG
PRG
PRG
PRG
PRG
tls
tacc
tdec
60
20
50
tbr
7
spin
2
aux
0
0000 conf OK
CODE
par
9000 9C5a
AUTO OK
PUSH
RE-ENTER
CODE
Display OFF
2 Cycle
OPEN/CLOSE
tca
PRG
PRG
PRG
PRG
mot1 0 0
1
2
3
1
2
3
YAK 25
BULL 15OMI
115Vac
BULL 15OMI
230Vac
_ _ _ _ _ _
0

28
ENG WARNING
The product shall not be used for purposes or in ways other than those for which the product is intended for and as described
in this manual.
Incorrect uses can damage the product and cause injuries and damages.
The company shall not be deemed responsible for the non-compliance with a good manufacture technique of gates as well
as for any deformation, which might occur during use. Keep this manual for further use.
This manual has been especially written to be use by qualified fitters.
Installation must be carried out by qualified personnel (professional installer, according to EN 12635), in compliance with
Good Practice and current code.
Make sure that the structure of the gate is suitable for automation.
The installer must supply all information on the automatic, manual and emergency operation of the automatic system and
supply the end user with instructions for use.
Packaging must be kept out of reach of children, as it can be hazardous.
For disposal, packaging must be divided the various types of waste (e.g. carton board, polystyrene) in compliance with re-
gulations in force. Do not allow children to play with the fixed control devices of the product.
Keep the remote controls out of reach of children.
This product is not to be used by persons (including children) with reduced physical, sensory or mental capacity, or who are
unfamiliar with such equipment, unless under the supervision of or following training by persons responsible for their safety.
Apply all safety devices (photocells, safety edges, etc.) required to keep the area free of impact, crushing, dragging and
shearing hazard.
Bear in mind the standards and directives in force, Good Practice criteria, intended use, the installation environment, the
operating logic of the system and forces generated by the automated system.
Installation must be carried out using safety devices and controls that meet standards EN 12978 and EN 12453.
Only use original accessories and spare parts, use of non-original spare parts will cause the warranty planned to cover the
products to become null and void.
All the mechanical and electrical parts composing automation must meet the requirements of the standards in force and
outlined by CE marking.
An omnipolar switch/section switch with remote contact opening equal to, or higher than 3mm must be provided on the
power supply mains.
Make sure that before wiring an adequate differential switch and an overcurrent protection is provided.
Pursuant to safety regulations in force, some types of installation require that the gate connection be earthed.
During installation, maintenance and repair, cut off power supply before accessing to live parts.
Also disconnect buffer batteries, if any are connected. The electrical installation and the operating logic must comply with
the regulations in force.
The leads fed with different voltages must be physically separate, or they must be suitably insulated with additional insulation
of at least 1 mm.
The leads must be secured with an additional fixture near the terminals.
During installation, maintenance and repair, interrupt the power supply before opening the lid to access the electrical parts
Check all the connections again before switching on the power.
The unused N.C. inputs must be bridged.
WASTE DISPOSAL
As indicated by the symbol shown, it is forbidden to dispose this product as normal urban waste as some parts might be
harmful for environment and human health, if they are disposed of incorrectly.
Therefore, the device should be disposed in special collection platforms or given back to the reseller if a new and similar
device is purchased.
An incorrect disposal of the device will result in fines applied to the user, as provided for by regulations in force.
Descriptions and figures in this manual are not binding. While leaving the essential characteristics of the product unchanged, the ma-
nufacturer reserves the right to modify the same under the technical, design or commercial point of view without necessarily update
this manual.

29
EN
2) CP.BULL 15 OMI CONTROL UNIT
2.1) INPUT/OUTPUT FUNCTIONS
N° Terminals Function Description
L-N-GND Power Supply
Single-phase power input.
L: Phase - N: Neutral - GND: Ground connection to the motor housing.
Note: the ground connection must be done as shown in the diagram at page ???
U-V-W Single-phase motor Single-phase motor connection Phase-Common-Phase.
Lamp Blinker Blinker connection 230Vac 40W max or 115Vac 40W max (BULL 15 OMAI).
24 Vdc 24 Vdc Auxiliary output power supply 24Vdc/500mA max.
SCA SCA N.O. Clean Contact (voltage free contact) to be used as open gate indicator 24 Vac 0.5 A
max, configurable through the logic SCA.
Phototest Photo-test Photocell test output, see figure 15
COM COMMON Common for all the input command.
OPEN OPEN COMMAND OPEN Input (N.O. contact).
CLOSE CLOSE COMMAND CLOSE Input (N.O. contact)
P.P. STEP BY STEP COM-
MAND STEP BY STEP Input (N.O. contact)
PED PEDESTRIAN PEDESTRIAN Input (N.O. contact)
STOP STOP STOP Input (N.C. contact)
PHOTO OPEN PHOTOCELL PHOTOCELL Input active only during opening phase
PHOTC CLOSE PHOTOCELL PHOTOCELL Input active only during closing phase
COM COMUNE COMMON for the limit switch
SWC CLOSE LIMIT SWITCH CLOSE Limit Switch Input (N.C. contact)
SWO OPEN LIMIT SWITCH OPEN Limit Switch Input (N.C. contact)
DAS/8K2 SAFETY EDGE
SAFETY EDGE Input
Resistive Edge (8K2): JP1 “DAS” close
Mechanical Edge (N.C.): JP1 “DAS” OPEN
The activation of the Safety Edge stops and reverses the movement of the leaf for 3s.
RADIO RADIO RECEIVER
Plug-in connection for radio receiver ONE, to be used with the cable provided, see picture
18.
2CH SECOND CHANNEL Second radio channel output. N.O. contact (max 24Vac/dc 1A)
BRAKE BRAKE RESISTOR Brake resistor Input for the braking current dissipation.
P3 Not used
COM1 Not used
J7 Not used
J8 Not used
SW1 Dip1, Dip2 Keep in ON position
2.2) HOW TO CHECK CONNECTIONS
1) Cut off power supply.
2) Manually release the door/gate and push it for about half stoke. Lock the door again.
3) Restore power supply.
4) Send a step-by-step command through push-button <-> on the control unit (LCD display off). To stop the door/gate press <-> once
more.
5) The door/gate should open. If not, use the MINV logics to change the opening direction.
3) PROGRAMMING
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software
release.

30
4) TO ACCESS PROGRAMMING
1 – Press the button <PG>, the display goes to the first menu, Parameters “PAR”.
2 – With the <+> or <-> button, select the menu you want.
3 – Press the button <PG>, the display shows the first function available on the menu.
4 – With the <+> or <-> button, select the function you want.
5 – Press the button <PG>, the display shows the value currently set for the function selected.
6 – With the <+> or <-> button, select the value you intend to assign to the function.
7 – Press the button <PG>, the display shows the signal “PRG” which indicates that programming has been completed.
12.1) RUN SELF-LEARNING AND ANTI-CRUSHING DEVICE SETTING
When operator assembly and wiring is completed, parameters and logic are programmed, self learning allows the operator to learn the
stroke and torque.
Enter menu Auto and press the button < PGM >, PUSH will be displayed.
Press again the button < PGM >: self-learning is beginning: PRG will be displayed, and the control panel completes some opening/
closing cycles.
When the procedure is completed OK will be displayed.
This procedure can be followed from any position of the gate/door leaf and can be stopped at any moment by pressing keys <+> and
<-> at the same time, or through the activation of STOP/PHO/PHA/DAS/PP/PED inputs.
If the procedure is not successful, the wording ERR appears. Check that no obstacles or frictions are present.
After the AUTOSET procedure it is necessary to check the value of the operating forces according to the European Standards EN12445
and EN12453. If the value of the force is too high it is mandatory to install a safety edge which complies to the standard EN12978.
Notes:
Pressing <-> with the display turned off means an impulse of P.P.
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any chang-
es.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 30s the control unit quits programming mode and switches off the display.
5) PARAMETERS, LOGIC AND SPECIAL FUNCTIONS
The tables below describe the individual functions available in the control unit.
PARAMETERS (PAR)
MENU FUNCTION MIN-MAX-(Default) MEMO
TCA Automatic closure time. It is activated only with “TCA” logics :ON
At the end of the preset time, the control unit starts a new closing operation. 1-240-(40s)
Tped The passage left open by the door/gate leaf during the partial opening controlled
by the pedestrian inoput, is adjusted.
The value is expressed in percentage on the aggregate value of the stroke.
5-100-(20%)
tsmO Braking during OPENING is adjusted.
The value is expressed in percentage on the aggregate value of the stroke.
See section “Speed and slowdown settings”*.
10-100-(20%)
tsmc Braking during CLOSURE is adjusted.
The value is expressed in percentage on the aggregate value of the stroke.
See section “Speed and slowdown settings”*.
10-100-(20%)
FSTo
The OPENING speed is adjusted.
IMPORTANT: Change the values of this parameter only by keeping to the
weight limits shown in Table 1.
See section “How to adjust speed and braking”.
20-120-(45)
FSTc
The CLOSURE speed is adjusted.
IMPORTANT: Change the values of this parameter only by keeping to the
weight limits shown in Table 1.
See section “How to adjust speed and braking”.
20-120-(45)
sldo Adjusts the slowdown speed during the opening phase.
See section “Speed and slowdown settings”*. 10-40-(25)
sldc Adjusts the slowdown speed during the closing phase.
See section “Speed and slowdown settings”*. 10-40-(25)
PMO The torque applied to motor 2 in the opening* phase is adjusted. 1-99-(70%)
PMC The torque applied to motor 2 in the closing* phase is adjusted. 1-99-(70%)
sEav
The trigger time of the anti-crash device (Amperometric) is adjusted during the
normal speed phase*.
0:Off-99: maximum sensibility - 1: minimum sensitivity
0-90-(1%)

31
EN
sEar
The trigger time of the anti-crash device (Amperometric) is adjusted during the
braking phase*.
0:Off-99: maximum sensibility - 1: minimum sensitivity
0-90-(1%)
blo Adjusts the braking space after the limit switch in open position. Value expressed
in cm.
See section “Speed and slowdown settings”*.
1-10-(3)
blc Adjusts the braking space after the limit switch in close position. Value expressed
in cm.
See section “Speed and slowdown settings”*.
1-10-(3)
TLS It is activated with AUX parameter only, preset to value 1.
The activation time of the service light is adjusted. 1-240-(60s)
TACC Ramp during acceleration.
See section “How to adjust speed and braking”. 1-25-(20)
TDEC Ramp during deceleration.
See section “How to adjust speed and braking”. 5-99-(50)
Tbr Emergency braking, after the activation of PHOT/BAR/STOP inputs, the value is
expressed in tenths of seconds.
See Table 1.
1-20-(7)
SPIN
Adjusts the inversion space of the leaf after a safety edge intervention. During the
inversion phase the intervention of the safety edge stops the leaf. If during the
inversion (on the OPEN and CLOSE direction) one of the related photocell (PHO-
TO or PHOTC) is activated, the parameter is ignored and the inversion space is
minimum (10 cm).
The minimum value 1 corresponds to about 20 cm, the maximum value 4 corre-
sponds to about 60 cm.
1-4 (1)
AUX
It selects the operating mode of the SCA output:
0: SCA
1: Service light. The contact closes for the time preset with TLS parameter. The
countdown starts at the inception of the opening operation.
2: Area light. The contact closes in the opening phase and remains closed for the
entire TCA time. It opens only with closed door.
See wiring shown in figure 17.
0-2-(0)
LOGIC (LOG)
MENU FUNCTION ON-OFF-(Default) MEMO
TCA
Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled
(OFF)
IBL
Enables or disables multi-flat function.
On: multi-flat function enabled. The step-by-step and perdestrian commands have
no effect during the opening phase.
Off: multi-flat function disabled.
(OFF)
IBCA
During the TCA phase, the PP controls are enabled or disabled.
On: PP controls are disabled.
Off: PP controls are enabled.
(OFF)
SCL
The rapid closure is enabled or disabled. It can be activated only if TCA:ON
On: enabled rapid closure. With open gate, the photocell activation causes the
automatic closure after 3 s.
If the photocell is activated during the opening phase, the operation is completed
and closure starts after 3s
Off: disabled rapid closure.
(OFF)
PP
The operating mode of “P.P. Push button” and of the transmitter are selected.
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
(OFF)
PRE
Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s before the
starting of the motor.
Off: disabled forewarning flashing light.
(OFF)

32
HTR
The Service Man function is enabled or disabled.
On: Service Man operation. The OPEN/CLOSE push buttons should be kept
pressed for the entire operating time.
Off: Automatic operation.
(OFF)
LTCA
During the TCA time, the blinker is enabled or disabled.
On: Enables blinker.
Off: Disables blinker.
(OFF)
Pho1
The PHOT O input is enabled or disabled in the opening phase.
On: Photocell 1 activated only in the closing phase.
Off: Photocell 1 activated in both opening and closing phases.
(OFF)
Pho2
The PHOT C input is enabled or disabled in the opening phase.
On: Photocell 1 activated only in the closing phase.
Off: Photocell 1 activated in both opening and closing phases.
(OFF)
tst1
The check on the photocell connected to PHOTO input is activated or deactivated
The test must be done after every command (PP, OPEN, CLOSE, RADIO, TCA) with
the motor not in movement and before to start the maneuver (also in case of partial
maneuver). The test is not made when the motor is already in movement, it must
stop and reverse after a safety edge or photocell intervention.
If the checks are not successful, the door/gate will not move.
On: activated check on photocell.
Off: deactivated check on photocell.
(OFF)
tst2 As for TST1, but referred to PHOTC input (OFF)
bar
Modifies the functioning mode of the inputs PHOTO (OPEN PHOTOCELL) and DAS
in case that safety edges are installed on the front and back of the leaf.
On: the input PHOTO assumes the same function of the input DAS but it reverses
the movement of the leaf only for the space set by the parameter SPIN if the safety
edge to which is connected is activated during the OPENING phase (if a CLOSE
PHOTOCELL input is given the motor stops and reverses only for 10 cm). The safety
edge connected to the DAS input is enabled only during the CLOSING PHASE.
Off: The intervention of the safety edge connected to the DAS input stops and
reverses the movement of the leaf for the space set by means of the parameter
spin (if the photocell in the opposite direction is activated, the leaf reverses only for
10cm) , both during OPENING and CLOSING phase.
The input PHOT OPEN resumes the functioning of the photocell enabled only during
the OPENING.
OFF
MINV
The opening direction of the motor is selected (see Fig. 4):
On: Right side motor mount
Off: Left side motor mount
(OFF)
NUMBER OF CYCLES (Nman)
The number of cycles (open+close) completed by the system is displayed.
When the push-button <PG> is pressed once, the first 4 digits are displayed, if the push-button is pressed once more, the last 4 dig-
its are displayed.
E.g. <PG> 0012 >>> <PG> 3456: 123.456 cycles were performed.
MAINTENANCE (maci)
This function allows to activate the indication of maintenance required after a certain number of operations, preset by the installer.
To activate and select the number of operations, proceed as follows:
Press the <PG> button, OFF is displayed, indicating that the function is disabled (default).
Select one of the numbers shown (from OFF to 100) by using the <+> and <-> keys . The figures express the value of hundreds of
cycles (e.g.: the number 50 means 5000 operations).
Press OK to activate the function. The PROG message is displayed.
When the flashing light flashes for around 10 sec at end of operation, this means that maintenance operations are needed.
RESET (RES)
RESET of the control unit. WARNING: Returns the control unit to the default values.
When the <PG> push-button is pressed once, the RES wording begins to flash, if the push-button<PG> is pressed once more, the
control unit is reset.
Note: neither the transmitter codes nor the position and stroked of the gate leaf will be erased from the receiver.

33
EN
AUTOSET (AUTO)
The automatic system stroke is self learned. See section “STROKE SELF-LEARNING”
PASSWORD (CODE)
It allows to type in an access protection code to the programming of the control unit.
A four-character alphanumeric code can be typed in by using the numbers from 0 to 9 and the letters A-B-C-D-E-F.
The default value is 0000 (four zeros) and shows the absence of a protection code.
While typing in the code, this operation can be cancelled at any moment by pressing keys + and – simultaneously. Once the password
is typed in, it is possible to act on the control unit by entering and exiting the programming mode for around 10 minutes in order to
allow adjustments and tests on functions.
By replacing the 0000 code with any other code, the protection of the control unit is enabled, thus preventing the access to any other
menu. If a protection code is to be typed in, proceed as follows:
- select the Code menu and press OK.
- the code 0000 is shown, also in the case a protection code has been previously typed in.
- the value of the flashing character can be changed with keys + and -.
- press OK to confirm the flashing character, then confirm the following one.
- after typing in the 4 characters, a confirmation message “CONF” appears.
- after a few seconds, the code 0000 appears again
- the previously stored protection code must be reconfirmed in order to avoid any accidental typing in.
If the code corresponds to the previous one, a confirmation message “OK” appears.
The control unit automatically exits the programming phase. To gain access to the Menus again, the stored protection code must be
typed in.
IMPORTANT: TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations.
To remove the code from a protected control unit, enter the programming mode with the password and reset the
code to the 0000 default value.
IF YOU LOOSE THE CODE, PLEASE CONTACT THE AUTHORISED SERVICE CENTER FOR THE TOTAL RESET OF
THE CONTROL UNIT.
12.8) MOTOR TYPE SELECTION (MOT1)
Allows to select the setting of the control unit according to the type of motor to be used.
Normally the right value is set by default and it does not need to be changed by the end user.
Only in case of control unit replacement is necessary to set the right value. Every number correspond to a defined type of motor, as
shown in the list below.
0: YAK25
1: BULL 15 OMI 230Vac
2: BULL 15 OMAI 115Vac
3: NOT USED
For convenience the screen shows always the message MOT followed by the number of the motor currently set
(eg. MOT.1,MOT.2)
TAB. 1 BULL 15 OMI
Kg Max. FSTO/ FSTC Min. TBR Min. TSMO/TSMC PMO/PMC V (m/1’)
1500 120 4 45 99/99 24
1000 100 3 35 99/99 20
600 85 2 30 99/99 17,5
According to the motor type and weight of the leaf, set the value of the speed during the opening and closing phase (FSTO/FSTC), the
maximum value of the braking TBR and the slowdown space values TSMO/TSMC.
The PMO/PMC parameters must be at 99.
BRAKE RESISTOR MUST be connected.
Exceed the recommended values may cause damage and malfunctioning. The manufacturer does not assume liability resulting from
improper setting of values FSTO/FSTC/TBR/TSMO/TSMC.
THE REPORTED VALUES ARE APPROXIMATE AND REFERED TO A STANDARD INSTALLATION, IN ANY CASE THE INSTALLATION
MUST BE DONE ACCORDING TO THE REGULATIONS IN FORCE (MACHINERY DIRECTIVE 2006/42/CE AND THE EUROPEAN
STANDARDS EN 13241-1, EN 12453, EN 12445).

34
6) HOW TO ADJUST SPEED AND BRAKING
The door/gate stroke is shown in the following scheme:
V
T
FSTo/fstc
sldo/SldC
BLo/blc
TAcc Tdec
TSMo/tsmc
SWO (SWC) SWC (SWO)
V
T
tbr
stop
phot
bar
The V axis is the gate/door speed, T axis is the time required by the door/gate to move from a limit switch to the other. The parameters
govern both the opening and the closing phases.
At gate/door stopped on any SWO (SWC) limit switch, when a control key is pressed the gate/good starts moving and reaches the
standard operating speed, which can be adjusted by FSTO/FSTC parameter.
The TACC time sets how rapidly the gate/door should reach the standard speed.
Before meeting the SWX (SWO) stop limit switch, braking preset by TSM time will start.
Braking leads the gate/door from standard speed (FSTO/FSTC) to braking speed, adjusted by SLDO/SLDC parameter.
The TDEC time sets how rapidly the gate/door should reach the braking speed.
The TDEC time is theoretical by reason of the fact that as soon as the speed reaches the value preset by SLDS, braking at constant
speed starts until reaching the SWC (SWO) limit switch.
Once the limit switch is reached, the gate/door continues its movement for a period of time adjusted by BLC parameter, until entire stop.
The following diagram shows graphically the stroke of the leaf in case that one of the safety input is activated (STOP/PHOT/BAR):
V
T
FSTo/fstc
sldo/SldC
BLo/blc
TAcc Tdec
TSMo/tsmc
SWO (SWC) SWC (SWO)
V
T
tbr
stop
phot
bar
The safety input intervention causes an immediate slowing-down of the leaf, the time in which the leaf switches from the standard speed
to the slowdown one is adjustable though the value TBR and it must respect the values indicated on the Table 1.
IMPORTANT:
- For the correct operation of parameters it is mandatory that the AUTOSET be carried out correctly (see STROKE LEARNING).
- If the FSTO/FSTC speed is increased, TSMO/TSMC, TACC and TDEC values must be increased proportionally in order to avert any
mechanical stress to the gear motor.
- The TBR value must be set as shown on the Table 1. A value of TBR too short on a leaf with a lot of inertia can damage the automa-
tion.
A TSMO/TSMC value, which is too short, combined with a TDEC value, which is too high, might result in the cancellation of the SLDO/
SLDC braking phase due to the gate leaf friction and the triggering of the limit switches when the speed is still high.
This situation must be absolutely avoided.
- The AUTO function does not change the default values of the above-mentioned parameters. The latter must be preset by the installer
according to the gate/door specifications.
- On the BAR input will be cabled in series to the SAFETY EDGE (or SAFETY EDGES) also a N.C. contact which opens every time that
the motor is released or the cover is removed. Thus, in case that 1. Control unit powered, 2. Motor not in movement, 3. SWO and
SWC not engaged (motor not on the limit switch), if the input BAR is activated and afterwards reactivates (motor not in movement
and cover on ready to start the maneuver), to the next command of PP/OPEN/CLOSE (also radio command) it is necessary force a
slow speed maneuver.
7) AUTOSET
The stroke learning is essential for the good setting of the slowdown function, this is done by means of the AUTO function described
above and also when the first complete maneuver is performed (without interruptions) from SWO to SWC) (or vice versa).

35
EN
The motor starts in SLOWDOWN mode until it finds SWO then it stops and changes direction always in SLOWDOWN mode until it
finds SWC (the stroke is learned). After this the motor performs the first maneuver at regural speed from SWC to SWO (ramps, speeds,
slowdowns defined from the parameters TSMo/TSMc/FSTo/FSTc/SLDo/SLDc pre-set) and then it performs the second maneuver at
regular speed from SWO to SWC.
However, these values can be manually modified at a second time.
If it is modified manually a parameter which needs a new AUTOSET, the control unit will perform a complete cycle (OPEN + CLOSE) and
on the screen will appear the message “PRG”. At the end of this operation the actuator will go back to the previous setting.
It is not possible to do the AUTOSET with the logic HTR:ON
9) ERROR MESSAGES
Hereafter are listed some messages which are shown on the screen in case of fault or error in the setting:
err AUTOSET ERROR
If the error shows up during the stroke learning phase, check the status of the inputs
PP/STOP/PED/PHOTO/PHOTC/DAS/OPEN/CLOSE and check also that the leaf runs
smoothly without friction points.
F00
F02
---
F015
INVERTER ERROR
All the errors which are included between F00 and F015 concern the inverter and in-
volve the block of the control panel.
Take note of the error and contact the technical support.
10) DISPLAY LCD
The LCD display can be turned by 180°.
- Cut off mains power supply
- Press PGM
- While keeping PGM pressed, reset the mains power supply
- Keep PGM pressed (around 5 sec) until the software version appears, turned by 180°.
Normally proceed with programming.
11) DIAGNOSTICS
In the event of malfunctions, by pressing key + or - the status of all inputs (limit switches, control and safety) can be displayed. One
segment of the display is linked to each input. In the event of failure it switches on according to the following scheme.
PHOTO
SWC
STOP
SWO
PHOTC DAS
PHO4PHO3
P.P. PED
OPEN
CLOSE
LD1 LED: Power Supply indicator
LD2 LED: + 5V indicator
Table of contents
Other Beninca Control Unit manuals

Beninca
Beninca START-I User manual

Beninca
Beninca THINK-I User manual

Beninca
Beninca CP.B24-SW User manual

Beninca
Beninca DREAMY User manual

Beninca
Beninca KER User manual

Beninca
Beninca CORE User manual

Beninca
Beninca BRAIN 24 User manual

Beninca
Beninca BRAINY User manual

Beninca
Beninca KT3 User manual

Beninca
Beninca Brain 24 MBE User manual

Beninca
Beninca DA.SO4 User manual

Beninca
Beninca Logica 230 User manual

Beninca
Beninca DREAM User manual

Beninca
Beninca MBE User manual

Beninca
Beninca SA.02 User manual

Beninca
Beninca CP.BISON OTI User manual

Beninca
Beninca CP.MS4 User manual

Beninca
Beninca SA02M User manual

Beninca
Beninca RI.624 User manual

Beninca
Beninca CELL.P User manual