- loosen the fixing screw then turn the instrument panel
- loosen the fixing screws on the cover (F) to access the terminal board (fig. 16) 
- while the boiler is powered up, using a small screwdriver included, press 
the CO button (fig. 26) for at least 4 seconds, to check the meter has 
been reset, power down then power up the boiler; the meter reading is 
shown on the monitor after the “-C-” sign.
 Live electrical parts (230 V AC).
Note: the meter resetting procedure should be carried out after each in-
depth cleaning of the primary exchanger or if this latter is replaced. To 
check the status of the total hour meter, multiply the reading by 100 (e.g. 
reading of 18 = 1800 total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A 77
This is an automatic-reset fault, if the boiler does not restart, contact the 
Technical Assistance Centre.
Flashing yellow LED
Combustion analysis in progress. 
4.4 Alarm records
The “ALARM RECORDS” function starts automatically once the display has 
been on for 2 hours, or immediately by setting the P1 parameter to 1. 
The records include all the latest alarms, up to a maximum of 5 alarms, and 
they are displayed in sequence by pushing and releasing the P1 button on 
the display board. If the records are empty (P0=0) or if tracking the same is 
disabled (P1=0), the display function is not available. 
Alarms are displayed in reverse order compared to the order in which they 
occurred: this means that the last alarm generated is the first to be display-
ed. To delete the alarms records, simply set parameter P0 to 0. 
NOTE: To get to the P1 button the cover on the control panel must be remo-
ved and the display board must be identified (fig. 36a). 
PROGRAMMING PARAMETERS 
Functioning of the display can be personalised by programming three pa-
rameters: 
Parameter Default Description
P0 0 Deletion of alarms records 
(0 = records empty / 1 = records not empty) 
P1 0 Immediate activation of alarm record mana-
gement 
(0 = delayed records management activated / 
1 = immediate records management activated
P2 0 Do not change 
When button P1 on the display (fig. 36a) is held down for at least 10 sec, 
the programming procedure is activated. The three parameters, with their 
respective values, are shown in rotation on the display (fig. 36b). To edit a 
parameter value, simply push the P1 button again when the required para-
meter is displayed, and then hold it down until the value switches from 0 to 
1 or vice-versa (approx. 2 sec). 
The programming procedure is closed automatically after 5 minutes, or if 
there is an electrical power failure
4.5 Boiler configuration 
There is a series of jumpers (JPX) available on the electronic board which 
enable the boiler to be configured.
To access the board, proceed as follows:
- turn off the main switch on the system
- loosen the fixing screws on the housing, move the base of the housing 
forwards and then upwards to unhook it from the chassis
- undo the fixing screws (E) from the instrument panel (fig. 14) 
- loosen the screws (F - fig. 16) to remove the cover of the terminal board 
(230V)
JUMPER JP7 - fig. 37: 
preselection of the most suitable heating temperature adjustment field ac-
cording to the installation type. 
Jumper not inserted - standard installation
Standard installation 40-80°C
Jumper inserted - floor installation
Floor installation 20-45°C.
In the manufacturing phase, the boiler is configured for standard installations.
JP1 
Calibration (Range Rated)
JP2 Reset heating timer
JP3 Calibration (see paragraph on “Adjustments”)
JP4 Do not use
JP5 
Heating only function with a predisposition for external storage tank 
with thermostat (JP8 inserted) or probe (JP8 not inserted)
 
JP6 Enable night-time compensation function and continuous pump (only 
with external sensor connected)
JP7 Enable management of low temperature/standard installations (see 
above) 
JP8 
Management of an external storage tank with thermostat enabled 
(jumper inserted)/ management of an external storage tank with pro-
be (jumpers not inserted) fig. 37.
The boiler foresees jumpers JP5 and JP8 inserted as standard (heating 
only version arranged for storage tank with thermostat); if the use of an 
exterior storage tank with probe is required, jumper JP8 must be removed. 
 
4.6 Setting the thermoregulation (graphs 1-2-3)
The thermoregulation only operates with the external sensor connected; 
once installed, connect the external sensor (accessory available on request) 
to the special terminals provided on the boiler terminal board (fig. 5).
This enables the THERMOREGULATION function.
Selecting the compensation curve
The compensation curve for heating maintains a theoretical temperature of 
20°C indoors, when the external temperature is between +20°C and -20°C. 
The choice of the curve depends on the minimum external temperature 
envisaged (and therefore on the geographical location), and on the delivery 
temperature envisaged (and therefore on the type of system). It is carefully 
calculated by the installer on the basis of the following formula:
Tshift = 30°C standard installations 
 25°C floor installations 
If the calculation produces an intermediate value between two curves, you 
are advised to choose the compensation curve nearest the value obtained.
Example: if the value obtained from the calculation is 1,3 this is between 
curve 1 and curve 1,5. Choose the nearest curve, i.e. 1,5.
Select the KT using trimmer P3 on the board (see multiwire wiring diagram).
To access P3:
- remove the housing, 
- loosen the fixing screw on the instrument panel
- turn the instrument panel towards you
- loosen the fixing screws on the terminal board cover
- unhook the board casing
 Live electrical parts (230 V AC). 
The KT values which can be set are as follows:
standard installation: 1,0-1,5-2,0-2,5-3,0
floor installation 0,2-0,4-0,6-0,8 
and these are displayed for approximately 3 seconds after rotation of the 
trimmer P3.
TYPE OF HEAT REQUEST
Boiler connected to room thermostat (JUMPER 6 not inserted)
The heat request is made by the closure of the room thermostat contact, 
while the opening of the contact produces a switch-off. The delivery tem-
perature is automatically calculated by the boiler, although the user may 
modify the boiler settings. Using the interface to modify the HEATING, you 
will not have the HEATING SET-POINT value available, but a value that you 
can set as preferred between 15 and 25°C. The modification of this value 
will not directly modify the delivery temperature, but will automatically affect 
the calculation that determines the value of that temperature, altering the 
reference temperature in the system (0 = 20°C).
Boiler connected to a programmable timer (JUMPER JP6 inserted)
With the contact closed, the heat request is made by the delivery sensor, on 
the basis of the external temperature, to obtain a nominal indoor tempera-
ture on DAY level (20°C). With the contact open, the boiler is not switched 
off, but the weather curve is reduced (parallel shift) to NIGHT level (16°C). 
This activates the night-time function.
The delivery temperature is automatically calculated by the boiler, although 
the user may modify the boiler settings. 
Using the interface to modify the HEATING, you will not have the HEAT-
ING SET-POINT value available, but a value that you can set as preferred 
between 25 and 15°C. 
The modification of this value will not directly modify the delivery tempera-
ture, but will automatically affect the calculation that determines the value 
of that temperature, altering the reference temperature in the system (0 = 
20°C for DAY level, and 16°C for NIGHT level). 
4.7 Adjustments
The boiler has already been adjusted by the manufacturer during produc-
tion. If the adjustments need to be made again, for example after extraordi-
nary maintenance, replacement of the gas valve, or conversion from meth-
ane gas to LPG, observe the following procedures.
The adjustment of the maximum and minimum output, and of the maximum 
envisaged delivery T. - Tshift
KT= 20- min. envisaged external T.