manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Broyce Control
  6. •
  7. Relay
  8. •
  9. Broyce Control EcoSmart P9670 User manual

Broyce Control EcoSmart P9670 User manual

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
1
11
1
01
3377
P
Type: P967
Type: P967Type: P967
Type: P9670
00
0
Overcurrent
OvercurrentOvercurrent
Overcurrent
Relay
RelayRelay
Relay

True R.M.S. measurements

Low Set and High Set tripping thresholds

6 selectable IDMT (Inverse De inite Minimum Time) characteristic curves

Adjustable DT (De initive Time)

Measurement and live display o individual phase currents

Last trip memory (last 10 trips stored and can be recalled)

Pre-de ined selectable CT ratio’s (5:5….6000:5)

Microprocessor based (sel checking) with non-volatile memory

“Ecosmart” Energy e icient power supply design

Rear mounted pluggable connectors or supply, relay contacts and current input
•OP RATION & OV RVI W
The P9670
P9670P9670
P9670 (from the P9600 series family of IDMT/DT relays) is a micro rocessor based relay
designed to monitor and detect Overcurrent on individual hases in a 3- hase a lication. Ty ically
the P9670
P9670P9670
P9670 is wired in conjunction with external current transformers of the feeder to be rotected.
A clear backlit LCD rovides all the key information that the user requires for both o eration and the
setting u . Setting is achieved in a few sim le ste s and requires no revious knowledge of roduct
o eration.
Normal o eration rovides the user with actual live individual hase currents all on one screen. The
actual hase current re resents that of the current assing through the rimary side of the externally
connected CT’s. This is achieved by the setting of the ratio for the CT.
Programming mode allows the user to assign the o eration of both internal relays for either Auto or
Manual resetting. Relay 2 has the added o tion of being allowed to energise at the start or end of a
time out eriod. If assigned to energise at the start, the Relay can be used to o erate a buzzer or
lam giving early warning before a system actually shuts down.
Low-set and High-set thresholds can be rogrammed for the Overcurrent detection. The time
current characteristic of the low-set units are selectable between Normal Inverse curve 3/10,
Normal Inverse curve 1.3/10, Long Time Inverse curve, Very Inverse curve, Extremely Inverse
curve, Extremely Inverse 0.65 curve and Definite Time. High-set units are the Definitive Time ty e.
Instantaneous tri ing is ossible by setting the time to minimum.
A sim le Summary screen is dis layed once the rogramming is com lete. The same screen can also
be dis layed by subsequent resses of the “R S T” button. This allows the user to access key
information with the tam er roof trans arent cover closed and sealed.
A Test mode is rovided (also accessible with the tam er roof trans arent cover closed) to confirm
the correct o eration of the internal relays. The relays will energise when the “T ST” button is
ressed and de-energise when the button is released (AUTO Reset) or when the “R S T” button is
ressed (MAN reset).
Following a tri condition, the information about the tri is then stored. This can then be recalled
later if required using the “R S T” button to access the information. The P9670
P9670P9670
P9670 has the ability to
store u to 10 tri s and using the “U ” and “Down” buttons, allows each tri to be dis layed
individually. Each tri is also marked with a time stam showing the time from ower u as well as
the time from the revious tri . This feature is very useful for establishing a attern on articular
in uts, knowing when they occurred and how frequent!
•FUNCTION OV RVI W
Programming mode.
Programmable arameters
User settings summary mode
1
Dis laying of the Summary screen during normal o eration is achieved via subsequent
resses of the “RESET” button. See Section 7. QUICK VIEW OF USER SETTINGS for further
information.
•PR S NTATION
1. LCD (Liquid Crystal Dis lay) for user information 5. “MOD ” button*
2. “R S T” button 6. Parameter increment button*
3. “T ST” button 7. Parameter decrement button*
4. “Power supply” green LED indication 8. “Trip status” red LED indication
* accessible only when the front cover is o en
START
TOROID RATIO
Set ratio of externally
connected toroid
N TWORK
FR QU NCY
Set for 50 or 60Hz
connected toroids
R
LAY 1 S TTING
Set reset mode
method
R LAY 2 S TTING
Assign relay activation and
reset mode methods
OV R
CURR NT
S TTING
Set Low-set and High-set
tri ing arameters
SUMMARY
1
List all arameter and
function settings
START
Dis lay live
Phase
currents
SUMMARY
1
List all arameter and
function settings
Dims:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (main body)
L. 100mm







I
L1
0.00
A
I
L2
0.00
A
I
L3
0.00
A

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
2
22
2
01
3377
P
•PROGRAMMING
Programming/setting of the P967
P967P967
P9670
00
0 is carried out using the 3 buttons located
behind the trans arent cover.
The button selects the required arameter to be changed. The
buttons either increment or decrement a value accordingly.
Any adjustments made are stored by the ressing and holding of the button
until the LCD shows the word “Save
SaveSave
Saved!
d!d!
d!” See Section 6. SAVING OF SETTINGS.

Please read the “Notes during programming” before commencing with the
following.
1A. TOROID RATIO

Setting the Toroid Ratio will allow the “actual” Phase currents (IL1, IL , IL3)
displayed on the LCD to represent that of the currents flowing through the external
CT’s. If no CT’s are used, the parameter should be set to 5/5 (i.e. 1:1). The setting
applies to all CT’s.

Default setting is “5/5”
•Press and hold the button. The LCD dis lays a screen showing the
characters “User Settings
User SettingsUser Settings
User Settings” then the following screen a ears…
•Press either or to set the rimary value of the external CT’s.

The digit after the forward slash “/” cannot be changed.
1B. N TWORK FR QU NCY

Default setting is “50Hz”
•Whilst in the same screen as that for the Toroid Ratio (see 1A.), ress
the button to dis lay the o tions for NETWORK FREQUENCY
NETWORK FREQUENCYNETWORK FREQUENCY
NETWORK FREQUENCY.
•Press either or to select between 50Hz or 60Hz. This should be
set to suit the frequency of the network being monitored.
•Press and hold the button to set the o tions for “
““
“Relay
RelayRelay
Relay
1
11
1”
” ”
” as described
in the next section.
2. R LAY 1 S TTING

Default setting for Relay 1 is Manual resetting mode.

The same screen is used for setting both Relay 1 and Relay ”
•The LCD dis lays the following screen. The o tions under “R LAY 1:” are
dis layed and the default setting highlighted.
Actual LCD resentation when adjustable arameters are dis layed.
•Press either or to select between AUTO
AUTOAUTO
AUTO resetting or MAN
MANMAN
MANUAL
resetting (after a fault has occurred).
•Press and hold the button to set the o tions for “Relay 2”
Relay 2” Relay 2”
Relay 2” as described
in the next section.
continued on next page…
•INSTALLATION
•B FOR INSTALLATION, ISOLAT TH SUPPLY. THIS PRODUCT IS
D SIGN D TO CONN CT TO S V RAL TYP S OF CIRCUITS.
NSUR ALL AR ISOLAT D^
•Remove the P967
P967P967
P9670
00
0 from the ackaging.
•Lift the raised art of the side cli in order to withdraw from the housing.
Carry this out on each side.
•Insert the P967
P967P967
P9670
00
0 into the anel cut-out and fit the side cli s back on to the
housing.
•Slide the cli s towards the front of the unit until they come in to contact with
the reverse of the anel. The unit is now secured in lace.
•Wire the su lied female luggable connectors as required.
•Plug the connectors into the relevant sockets on the rear of the unit.
•The P967
P967P967
P9670
00
0 is now ready for owering and rogramming.

The front window of the P9670 is supplied with a clear protective film which can be
removed as and when necessary.
^ When carrying out future maintenance on the roduct or a lication and it
becomes necessary to disconnect the connectors from the roduct, ensure for
the Current Transformer connector, they do not rem
they do not remthey do not rem
they do not remain o en circuit
ain o en circuitain o en circuit
ain o en circuit. This can
lead to high voltages being resent on this connector.
•NORMAL OP RATION
•A ly ower to the unit and the green “Power supply” LED will illuminate.
•The LCD will momentarily dis lay a welcome screen as shown…
….then after a short delay reverts to indicating the following information:
•T ST MOD
•Press and hold the button and both relays will energise. The LCD will
dis lay the characters “T ST” and the roduct art number (as below). The
LCD backlight and red “Trip” LED will flash.
•Release the button and the relay(s) will remain energised if set to Manual
reset or de-energise if set to Auto reset.
•Press the to de-energise relay(s) which are set to Manual reset. The
LCD will revert back to Normal o eration. The LCD backlight and red
“Trip” LED will sto flashing.

Testing should be carried out on a regular basis to check the integrity of the
P9670.
DO NOT use this product to provide a means of isolating circuits in
order to work on when placed in the “TEST”
“TEST”“TEST”
“TEST” mode. This should only be
done by means of operating isolators, circuit breakers or other
methods of removing power in this application.
I
L1
0.00
A
I
L2
0.00
A
I
L3
0.00
A
Installation work must be carried
out by qualified personnel.
Actual hase
currents
TEST
TYPE: P9670
Ver: X.X
TOROID RATIO
5 / 5
RELAY
CONFIG
RATION
RELAY 1:
A TO
MAN
Digits which
can be adjusted
TYPE: P9670
Ver: X.X
Model No.
Version
TOROID RATIO
5 / 5
NETWORK FREQ ENCY
50Hz
60Hz
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
3
33
3
01
3377
P
7. QUICK VI W OF US R S TTINGS

It is not possible to edit settings when these screens are displayed.

This feature can also be activated with the front window closed!
•Press and hold the button to dis lay the initial ower u screen.
•Press the same button again to dis lay the “Last Tri ed Information” screen
(refer to the next section for further information on this feature).
•Press again to dis lay the “Overcurrent Summary” screen.
•Press again to dis lay the contact details for Broyce Control.
•Press again to revert back to Normal o eration.
8. LAST TRIPP D INFORMATION

Refer to next page for detailed information of this feature
Notes during programming

If during programming it is necessary to abort, press the button briefly.

Pressing and holding either or for >1sec. will increment or decrement
the new value at a quicker rate.

Stepping through each User Setting screen is performed by pressing and holding
the button until the desired screen is displayed.
Short presses of the button will allow further editable settings to be changed
within a specific screen.

If the user remains in a setting or summary screen where no adjustments or button
presses are made within a certain period, the screen will revert back to Normal
operation. Additionally, any settings that have been made but not stored will not be
saved.

“O/C” refers to Overcurrent.
•TRIPPING MOD
•A fault which develo s on a hase will be indicated by an increase in current
reading on the LCD. When the level of current exceeds the Low-set setting,
the hase at fault will be highlighted by the digits flashing.
•The LCD backlight will flash.
•Relay 2 will energise if assigned to Overcurrent and set to energise at the start
of the time out eriod (See Section 3. RELAY 2 SETTING).
•The characters “I>” will dis lay to indicate the Low-set has been triggered.
•If the current continues to increase above the High-set setting, the characters
“I>” will change and dis lay “I>>” to indicate the High-set has been
triggered.
•When the unit finally tri s, the digits of the hase at fault will sto flashing and
remain highlighted. This allows the user to see which hase was at fault and
caused the unit to tri .
•The red “Tri ed”
“Tri ed”“Tri ed”
“Tri ed” LED will also flash.
•The relays which energised are also dis layed on the screen after tri ing.
•Press to reset and return the unit back to normal o eration (assuming
the fault has been cleared). The LCD reverts back to dis laying the normal
system currents and the red “Tri ed”
“Tri ed”“Tri ed”
“Tri ed” LED sto s flashing.

If either relay is set for Auto resetting, then they would have de-energised after the
fault had cleared. The corresponding relay ident (i.e. R1 and/or R ) on the display
would also disappear. Pressing the “R
“R“R
“RESET”
ESET” ESET”
ESET” button will only clear the LCD. If either
relay is set for Manual resetting, then pressing the “RESET”
“RESET”“RESET”
“RESET” button will de-energise the
relay(s) and clear the LCD.
•PROGRAMMING (continued)
3. R LAY 2 S TTING

Default setting for Relay is to energise at the end of the time out period.
Resetting mode is Auto.
•Setting of “Relay 2”
“Relay 2”“Relay 2”
“Relay 2” is carried out in a similar manner as “Relay 1”
“Relay 1”“Relay 1”
“Relay 1”; however it
is necessary to assign the relay to either energise at the start (S) or end (E) of
the time out eriod.
Actual LCD resentation when adjustable arameters are dis layed.
•Press and hold the button to set the o tions for “
““
“OVERCURRENT”
OVERCURRENT” OVERCURRENT”
OVERCURRENT” as
described in the next section.
4. OV RCURR NT S TTING

The description for the Curves is abbreviated when displayed on the screen. Refer
to “IDMT Characteristic Curves” for further explanation.

Default settings for Overcurrent are shown in the last LCD screen example in this
section.
•Settings for Overcurrent are dis layed in turn following subsequent resses of
the button. The Low-set tri current (I>) is dis layed first.
•Press either or to change the current.
•Press the button to select the remaining settings and use the and
buttons to change them.
Actual LCD resentation when adjustable arameters are dis layed.
Screen exam le above also shows the default settings for OVERCURRENT.
•Press and hold the button to set the o tions for “
““
“EARTH FAULT”
EARTH FAULT” EARTH FAULT”
EARTH FAULT” as
described in the next section.

If the Curve in selection “ :” is set to Definite Time, then selection “3:” will display
“3: t>” and the required delay can then be set.

If High-set is set to Disable in selection “4:”, then I>> or t>> cannot be
adjusted.
5. OV RCURR NT SUMMARY

It is not possible to edit settings when this screen is displayed.
•Following the setting of “Overcurrent”, the LCD dis lays the “Overcurrent”
screen showing a summary of the settings made during rogramming. All
settings are dis layed. The selected CT ratio, Network Frequency and Relay
o eration (following a Reset) information is also dis layed.
6. SAVING OF S TTINGS
•If after viewing the Summary screen the settings are correct, ress and hold
the button until the word “
““
“Saved.
Saved.Saved.
Saved.”
””
” a ears. Any new settings are now
stored.
•The screen will revert back to Normal o eration.
O/C
S MMARY
I> 5.00A
NI 3/10
k> 0.1
I>>50.00A
t>>0.05s
R1 = MAN R2 = A TO (E)
CT=5:5, FREQ=50Hz
RELAY
CONFIG
RATION
RELAY 1: RELAY 2:
A TO A TO (E)
MAN MAN (E)
A TO (S)
MAN (S)
O/C SETTING
Low set
1: I> 5.00A
The letter in brackets refers to
whether Relay 2 has been set
to trigger at the start or end of
the time out eriod.
(E) = E
EE
End of time out
(S) = S
SS
Start of time out
Either abbreviation can a ear
after the word MAN or
AUTO
See Section 3. RELAY
SETTING
I
L1
20.70
A
I>
I
L2
40.00
A
I
L3
27.50
A
I
L1
20.70
A
I>>
I
L2
89.00
A R1 R2
I
L3
27.50
A
Low-set
triggered
High-set
triggered
Relay(s) which
energised on
tri ing
O/C SETTING
Low Set:
1: I> 5.00A
2: Curve NI 3/10
3: k> 0.1
High Set:
4: I>> 50.00A
5: t>> 0.05s
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
4
44
4
01
3377
P
8C
.
CL ARING TH
LAST TRIPP D INFORMATION
HISTORY

Once the information has been deleted, it will not be possible to recall this.

“Ttrip” information is still retained but won’t be displayed after the carrying out this
operation (See 8D)
•Press the button to access the relevant screen.
•Press the and buttons simultaneously to delete the information.
When this is com lete, the screen will show:
•Press the button again to exit.
No previous trip info
8D
.
CL ARING
“Ttrip” INFORMATION

If the tripping history hasn’t been deleted, previous information will be displayed
from the last time the unit was powered up.
•The “Ttri ” information will still be held in memory after deleting the tri
history is made and also if ower is removed and re-a lied. However,
when ower is re-a lied, the internal counter will reset and start from zero
•Only when a new tri condition occurs will the “Ttri ” information get
u dated and be dis layed on the most recent screen.
•PROGRAMMING (continued)
8A. LAST TRIPP D INFORMATION

This information is held in memory even if power is removed.
This feature allows the user to view and recall the key information relating to the last tri event and it can store u to 10 tri events. It is accessed as described in Section 7
on the revious age.
The information dis layed highlights the cause of the tri (i.e. which hase for exam le), the level of current at the time the tri occurred; the triggering method (Low-set
or High-set) and which relays were activated. It also shows the ela sed time from owering the
P967
P967P967
P9670
00
0
to the tri occurring and dis layed against “Ttri ” as well as showing
the time difference between the tri dis layed and the one revious to that. This is shown against “Tdiff”.
An exam le of the screen layout is shown below.

If there is only one
tri
event
stored in the memory, the dis lay will show
“Tdiff:
----
d
--
h
--
m
--
s” when viewed.
Phase which
caused the tri
to occur
(i.e. L2)
Level of current
on other in uts
at time of tri
Tri number
(1…10)
Relays that were
activated at tri
IL1
20.70A
I>>
1
…
IL2 89.00A R1 R2
IL3 27.50A
Ttrip: 0000d00h00m00s
Tdiff: 0000d00h00m00s
Level which was
triggered (i.e. High-set)
Ttri :
The ela sed time from
a lying ower to the
current tri
Tdiff:
The time difference
between the current tri
and the revious tri
8
B. R CALLING TH LAST TRIPP D INFORMATION

If the unit has logged the maximum number of trips which can be stored, then the display will show “Tdiff: ----d--h--m--s” when trip screen 10 is viewed.

The screen will revert back to Normal operation after 1 minute if no further button presses are made.

If a trip condition occurs whilst in this mode, the screen will automatically change to display the information relating to the current status.
•As described in Section 7, use the to gain access to the Last Tri ed Information screen. The dis lay will show the most recent tri information as follows:
•If more than one tri event is stored, use the and buttons to select the screens accordingly.
•Press the button to exit the screen information when finished or allow to time out automatically.
IL1
1.65
A
I>
1
…
IL2 15.00A R1 R2
IL3 8.40A
Ttrip: 0001d13h15m04s
Tdiff: - - - -d - -h - -m - -s
IL1
1.65
A
I>
1
…
IL2 15.00A R1 R2
IL3 8.40A
Ttrip: 0001d19h24m56s
Tdiff: 0000d06h09m52s
IL1
1.8
0A
I>
2
…
IL2 21.35A R1 R2
IL3 9.20A
Ttrip: 0001d13h15m04s
Tdiff: - - - -d - -h - -m - -s
The exam le on the left shows the roblem on hase L2 on
both tri events. The difference between the first recorded
tri and second was 6h 09m
6h 09m6h 09m
6h 09m and 52s
52s52s
52s.
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
5
55
5
01
3377
P
•IDMT CHARACT RISTIC CURV S
*
Abbreviations used in the LCD screen for the selected IDMT characteristic curve.
The sequence of curves that are resented to the user when rogramming is shown below
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
Normal Inverse 1.3/10
Normal Inverse 1.3/10Normal Inverse 1.3/10
Normal Inverse 1.3/10
(NI
(NI(NI
(NI
1.3/10 *
1.3/10 *1.3/10 *
1.3/10 *
1 10 20
I/I>
I/I>I/I>
I/I>
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
t
t
t
t
(s)
(s)
(s)
(s)
10
1
0.1
0.01
t
t
t
t (s)
(s)
(s)
(s)
Normal Inverse
Normal InverseNormal Inverse
Normal Inverse
3/10
3/103/10
3/10
(NI
(NI(NI
(NI
3/10 *
3/10 *3/10 *
3/10 *
t
t
t
t
(s)
(s)
(s)
(s)
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
10
1
0.1
1 10
20
I/I>
I/I>I/I>
I/I>
Long Time Inverse
Long Time InverseLong Time Inverse
Long Time Inverse
(LTI
(LTI(LTI
(LTI *
**
*
.
200
100
10
1
0.1
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
t
t
t
t (s)
(s)
(s)
(s)
1 10 20
I/I>
I/I>I/I>
I/I>
Very Inverse
Very InverseVery Inverse
Very Inverse
(VI
(VI(VI
(VI *
**
*
1 10 20
I/I>
I/I>I/I>
I/I>
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
10
1
0.1
0.01
t
t
t
t (s)
(s)
(s)
(s)
Extremely Inverse
Extremely InverseExtremely Inverse
Extremely Inverse
(EI
(EI(EI
(EI *
**
*
k
kk
k
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
100
10
1
0.1
0.01
t
t
t
t
(s)
(s)
(s)
(s)
1.0
0
0.1
0.05
1 10 20
I/I>
I/I>I/I>
I/I>
Extremely Inverse
Extremely Inverse Extremely Inverse
Extremely Inverse
(EI 0.65 *
(EI 0.65 *(EI 0.65 *
(EI 0.65 *
k
kk
k
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 10 20
I/I>
I/I>I/I>
I/I>
1000
100
10
1
0.1
0.01
1.0
0
NI 1.3/10
NI 3/10
LTI
EI
EI 0.65
VI
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9670-2-A
6
66
6
01
3377
P
Electrical life:
≥
150,000 o s at rated load
Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated im ulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Max. DC Load Breaking Ca acity Electrical Endurance
Housing: Flame retardant Lexan
Protection: IP55 / IP20 (rear)
Weight: ≈ 520g
Mounting: Panel mounting. Cut-out = 91 x 91mm (± 0.5mm)
Max. anel thickness: 12mm
Terminal ty e: UL94-V0 rated luggable and re-wireable female
connectors com rising:
2-way (Power su ly 1, 2)
6-way (Relay contacts 3….8)
8-way (Phase current in uts 9….14)
Note that terminals 15 and 16 are not used on this
model and should be left unconnected.
Terminal conductor size: 0.05 - 2.5mm
2
(30 - 12AWG)
Recommended tightening
torque: 4.4in lb (0.5Nm)
Wire stri ing length: 0.24 – 0.30in (6 – 7.5mm)
A rovals: Conforms to IEC. CE and and RoHS Com liant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generic: IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
( ) Bold digits in brackets refer to terminal numbers on the rear of the unit.
Options:
The P9600 range also includes combined Overcurrent or Earth fault relays
available with either IDMT or DT characteristics. Additionally, a voltage, ower
and frequency monitoring only roduct is also available. Please refer to se arate
data sheets.
•T CHNICAL SP CIFICATION
Aux. Su ly voltage Un (1, 2): 85 – 265VAC/85 - 370VDC
1
18 – 55VAC/18 – 72VDC*
(Voltage range should be specified at time of
ordering)
Rated frequency: 50/60Hz (AC Su lies)
Isolation: Over voltage cat. III
Rated im ulse
withstand voltage:
1
4kV (1.2 / 50µS) IEC 60664
Power consum tion: 3W max.
* If connecting a fuse externally, a Time Delay ty e is recommended with a rating of 0.5A or
higher.
Rated current in ut In: 5A (directly connected)
Rated frequency: 50/60Hz
Burden: <0.4VA @ In
Overload: 4 x In (continuous)
External CT (15,16): Class P recommended. (with 5A secondary)
Maximum CT rimary
current rating: 6000A
Overcurrent settings:
Low-set tri (I>): 0.50 – 10.00A (10 – 200%)
Low-set time multi lier (k>): 0.05 – 1.00
Low-set definite time (t>): 0.05 – 100s
High-set tri (I>>): 0.5 – 100A (10 – 2000%) or disable
High-set definite time (t>>): 0.05 – 2.5s
Pick u value: +2% of tri setting
Accuracy:
Protection threshold: ± 5%
Time delay (DT): ± 5% (with a minimum of 50mS)
Time delay (IDMT): ± 5% (with a minimum of 50mS and I > 1.2 x
set-tri )
Actual Earth fault current: ± 1% of rated current In
Dis lay u date time: <1 sec.
Re eat accuracy: ± 0.5% @ constant conditions
Ambient tem erature: -10 to +60°C
Relative humidity: +95%
Out ut:
(RL1 - 3, 4, 5): 1 x SPDT relay
(RL2 - 6, 7, 8): 1 x SPDT relay
Out ut rating: AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
•CONN CTION DIAGRAM
L1
L2
L3
N
A1 A2
RL1
RL2
Aux.
1 2 3 4 5 6 7
9
8
10 11 12 13 14
16
15
I
L1
I
L2
I
L3
•DIM NSIONS
96
96
MADE IN U.K.
10
100
89.5
96
Front view Side view
All dimensions are in mm.

Other Broyce Control Relay manuals

Broyce Control P9650 User manual

Broyce Control

Broyce Control P9650 User manual

Broyce Control P50ELR Series User manual

Broyce Control

Broyce Control P50ELR Series User manual

Broyce Control P9660 User manual

Broyce Control

Broyce Control P9660 User manual

Broyce Control P9690 User manual

Broyce Control

Broyce Control P9690 User manual

Broyce Control P9640 User manual

Broyce Control

Broyce Control P9640 User manual

Broyce Control ELRV-30 User manual

Broyce Control

Broyce Control ELRV-30 User manual

Broyce Control P9680 User manual

Broyce Control

Broyce Control P9680 User manual

Broyce Control P9620 User manual

Broyce Control

Broyce Control P9620 User manual

Broyce Control P9680C User manual

Broyce Control

Broyce Control P9680C User manual

Broyce Control P50EFR User manual

Broyce Control

Broyce Control P50EFR User manual

Broyce Control P9625 User manual

Broyce Control

Broyce Control P9625 User manual

Broyce Control P9600 Series User manual

Broyce Control

Broyce Control P9600 Series User manual

Broyce Control ELR01PN User manual

Broyce Control

Broyce Control ELR01PN User manual

Broyce Control ELRV-30 User manual

Broyce Control

Broyce Control ELRV-30 User manual

Popular Relay manuals by other brands

Mastervolt MLI Ultra Series Quick start installation guide

Mastervolt

Mastervolt MLI Ultra Series Quick start installation guide

Carrier HN72ZA001 installation instructions

Carrier

Carrier HN72ZA001 installation instructions

Chenzhu CZSR8001-3A1B user manual

Chenzhu

Chenzhu CZSR8001-3A1B user manual

VAMP 257 Operation and configuration instructions

VAMP

VAMP 257 Operation and configuration instructions

Viessmann 5551 Operation manual

Viessmann

Viessmann 5551 Operation manual

Stelpro SBB Series Installation

Stelpro

Stelpro SBB Series Installation

GE GCX51A instructions

GE

GE GCX51A instructions

BEA LO-21K user guide

BEA

BEA LO-21K user guide

BERNSTEIN SCR 2-W22-2.5-S Installation and operating instructions

BERNSTEIN

BERNSTEIN SCR 2-W22-2.5-S Installation and operating instructions

Ice NPM800R user guide

Ice

Ice NPM800R user guide

ERL B-PRO user manual

ERL

ERL B-PRO user manual

ABB TRB Series Instruction leaflet

ABB

ABB TRB Series Instruction leaflet

Westinghouse RS instructions

Westinghouse

Westinghouse RS instructions

Sygonix SY-4699842 operating instructions

Sygonix

Sygonix SY-4699842 operating instructions

Immergas 3.031943 quick start guide

Immergas

Immergas 3.031943 quick start guide

Pavotek DEMA DigiLine 400 Series quick start guide

Pavotek

Pavotek DEMA DigiLine 400 Series quick start guide

NetPing Input+Relay R404 user guide

NetPing

NetPing Input+Relay R404 user guide

Siemens SIRIUS 3SK1 Equipment manual

Siemens

Siemens SIRIUS 3SK1 Equipment manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.