The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9680[C]-5-A.DOCX
3
33
3
6. MODBUS S TTING (P9680C only)
•Here there s the opt on to set the Address, Baud rate and Par ty. Use the e
button to select the d fferent parameters.
Actual LCD presentat on when adjustable parameters are d splayed.
•Press e ther or to change the parameter values.
•Press and hold the button to see a summary of the “OVERCURRENT”
“OVERCURRENT”“OVERCURRENT”
“OVERCURRENT”
then “EARTH FAULT”
“EARTH FAULT”“EARTH FAULT”
“EARTH FAULT” sett ngs as descr bed n the next sect on.
7. OV RCURR NT & ARTH FAULT SUMMARY
It is not possible to edit settings when these screens are displayed.
•Follow ng the sett ng of “Earth Fault”, the LCD d splays the “Overcurrent
Summary” screen show ng a summary of the sett ngs made dur ng
programm ng. All sett ngs are d splayed. The selected CT rat o, Network
Frequency and Relay operat on (follow ng a Reset) nformat on s also
d splayed.
•Press and hold the button to d splay the
“Earth Fault Summary” screen.
8. SAVING OF S TTINGS
•If after v ew ng the Summary screens the sett ngs are correct, press and hold
the button unt l the word “Saved.”
“Saved.”“Saved.”
“Saved.” appears. Any new sett ngs are now
stored.
•The screen w ll revert back to Normal operat on.
8. QUICK VI W OF US R S TTINGS
It is not possible to edit settings when these screens are displayed.
This feature can also be activated with the front window closed!
Press and hold the button to d splay the n t al power up screen.
•Press the same button aga n to d splay the “Last Tr pped Informat on” screen
(refer to the next page for further information on this feature).
Press aga n to d splay the “Overcurrent Summary” screen.
Press aga n to d splay the “Earth Fault Summary” screen.
Press aga n to d splay the contact deta ls for Broyce Control.
Press aga n to revert back to Normal operat on.
9. LAST TRIPP D INFORMATION
Refer to next page for detailed information of this feature
Notes during programming
If during programming it is necessary to abort, press the button briefly.
Pressing and holding either or for >1sec. will increment or decrement
the new value at a quicker rate.
Stepping through each User Setting screen is performed by pressing and holding
the button until the desired screen is displayed.
Short presses of the button will allow further editable settings to be changed
within a specific screen.
If the user remains in a setting or summary screen where no adjustments or button
presses are made within a certain period, the screen will revert back to Normal
operation. Additionally, any settings that have been made but not stored will not be
saved.
”O/C” refers to Overcurrent and “E/F” refers to Earth fault.
•PROGRAMMING (continued)
•Press and hold the button to set the opt ons for “Relay 2”
Relay 2” Relay 2”
Relay 2” as descr bed
n the next sect on.
3. R LAY 2 S TTING
Default setting for Relay is linked to “O/C & E/F” and energising at the end of the
time out period. Resetting mode is Auto.
•Sett ng of “Relay 2” s carr ed out n a s m lar manner as “Relay 1”, however t
s necessary to ass gn the relay to e ther energ se at the start (S) or end (E) of
the t me out per od.
Actual LCD presentat on when adjustable parameters are d splayed.
•Press and hold the button to set the opt ons for “OVERCURRENT”
“OVERCURRENT” “OVERCURRENT”
“OVERCURRENT” as
descr bed n the next sect on.
4. OV RCURR NT S TTING
The description for the Curves is abbreviated when displayed on the screen. Refer
to “IDMT Characteristic Curves” for further explanation.
Default settings for Overcurrent are shown in the last LCD screen example in this
section.
•Sett ngs for Overcurrent are d splayed n turn follow ng subsequent presses of
the button. The Low-set tr p current (I>) s d splayed f rst.
•Press e ther or to change the current.
•Press the button to select the rema n ng sett ngs and use the and
buttons to change them.
Actual LCD presentat on when adjustable parameters are d splayed.
Screen example above also shows the default sett ngs for OVERCURRENT.
•Press and hold the button to set the opt ons for “EARTH FAULT”
“EARTH FAULT” “EARTH FAULT”
“EARTH FAULT” as
descr bed n the next sect on.
If the Curve in selection “ :” is set to Definite Time, then selection “3:” will display
“3: t>” and the required delay can then be set.
If High-set is set to Disable in selection “4:”, then I>> or t>> cannot be
adjusted.
5. ARTH FAULT S TTING
Default settings for Earth Fault are shown in the LCD screen example in this
section.
•Sett ngs for Earth Fault are carr ed out the same as descr bed for Overcurrent.
Screen example show ng the default sett ngs for EARTH FAULT.
•Press and hold the button for e ther:
•Summary of the “OVERCURRENT”
“OVERCURRENT”“OVERCURRENT”
“OVERCURRENT” then “EARTH FAULT”
“EARTH FAULT”“EARTH FAULT”
“EARTH FAULT” sett ngs
(Model: P9680)
•Opt on to change the MODBUS sett ngs (Model: P9680C)
If the Curve in selection “ :” is set to Definite Time, then selection “3:” will display
“3: to>” and the required delay can then be set.
If High-set is set to Disable in selection “4:”, then Io>> or to>> cannot be
adjusted.
Low set
1: I> 5.00A
1: 2:
O/C A TO (E)
E/F MAN (E)
O/C & E/F A TO (S)
MAN (S)
Low Set:
1: I> 5.00A
2: Curve NI 3/10
3: k> 0.1
High Set:
4: I>> 50.00A
Low Set:
1: Io> 2.00A
2: Curve NI 3/10
3: k> 0.1
High Set:
4: Io>> 10.00A
I> 5.00A
NI 3/10
k> 0.1
I>>50.00A
t>>0.05s
R1 = MAN R2 = A TO (E)
Io> 2.00A
NI 3/10
ko> 0.1
Io>>10.00A
to>>0.05s
R1 = MAN R2 = A TO (E)
The letter n brackets refers to
whether Relay 2 has been set
to tr gger at the start or end of
the t me out per od.
(E) = E
EE
End of t me out
(S) = S
SS
Start of t me out
E ther abbrev at on can appear
after the word MAN or AUTO
See Section 3. RELAY
SETTING
ADDR 1
BA D 9600
PARITY None