Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Telephone:
+44
(0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: [email protected] Web: http://www.broycecontrol.com The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.
CONNECTION DIAGRAM
14
1
standard
output
positivesafety
output
test
reset
A1(+ve)
A2(-ve)
Faultleveloutput*
(i.e.lamp)
2
3 5 7 9 11 13
4 6 8 10 12
toroid
50m*max.
50m*max.
L1
L2
L3
N
E
Note:The voltage
across the faultlevel
outputMUSTNOT
exceed 240V~(For
400V~unitsused in
3-Phaseinstallations,
connectthe load between
terminal2and neutral)
The EarthMUSTNOTpass through
the toroid.
Forsinglephaseapplications,onlythe live
and neutralneed tobe passed through the
toroid.
*Cabling:
Fordistances>1m,usetwisted paircablebetween
the unitand toroid.Always ensurecablestotoroid
and remotetest/resetswitchesAREKEPTAWAY
frommainsand datacablesinthe sameinstallation.
Bothrelays areshown
inthe de-energised state
(i.e.wherepowerisnot
presenton terminals1and 3)
E
*Onlyavailableon ACsupplymodels
Type: ELRV-30
Earth Leakage Relay (Variable) -Type A
q70mm DIN rail housing
qDesigned to monitor and detect earth fault currents (up to 30A) in conjunction with a separate toroid
qDigital LED Display shows measured leakage current as well as various user settings
qMicroprocessor controlled with internal monitoring (self-checking)
qSensitivity (I∆n) and time delay (∆t) adjustable using simple 2-button operation
q“Display” push button allows user to view settings without needing to open the tamperproof cover
qSingle button operation for “Test / Reset” and connection facility for remote “Test” and “Reset” push buttons
qConnection for remote lamp facility warning user prior to a trip condition (level adjustable by user)
qToroid open circuit detection forces unit to trip
q2 x SPDT relay output 8A
qLED indication of user settings and fault condition after unit has tripped
Dims:
to DIN 43880
W. 70mm
TECHNICAL SPECIFICATION
Supply voltage Un (1, 3): 10-85V DC (85 -115% of U)
24, 115V, 230, 400V AC (85 -115% of Un)
All AC supplies are galvanically isolated between the supply and
the toroid and remote test / reset connections.
Frequency range: 50/60Hz (AC supplies)
Isolation: Over voltage cat. III
Rated impulse
withstand voltage: 800V (24V AC supplies ),
2.5kV (115V AC supplies)
(1.2 / 50µS) IEC 60664 4kV (230V, 400V AC supplies)
Power consumption (max.): 6VA (AC supplies) 5W (DC supplies)
Monitored leakage current: 0 to 30A (50/60Hz)(through external toroid with 1000:1 ratio
and connected to terminals 11 and 13)
Sensitivity I∆n: 6, 10, 30, 50, 75, 100, 300, 500, 750mA
1, 3, 5, 7.5, 10, 15, 20, 25, 30A (user selectable)
Trip level limits: 70 -80% of I∆n
Reset Value: <7% of tripped level
Time delay ∆t: inst., 50, 250, 500mS, 1, 2.5, 5, 10 sec. (user selectable)
Note: For I∆n settings of 30mA or less, the time delay is fixed
to inst. (instantaneous, <40mS) and is not adjustable.
Measured current: 0.0005 to <30A displayed on auto ranging 2 digit 7-segment
red LED display
Resolution: 100uA min. to 1A max.
Display accuracy: ±15% of actual measured leakage current
Reset time: <120mS (from supply interruption)
Self test duration: <5 secs. (operates at power on only)
Memory: storage of the leakage fault and reset with “test / reset” button
-5 to +60°C
-5 to +40°C (in accordance with IEC 755)
Relative humidity: +95%
Output : 2 x SPDT relay (4, 6, 8 / 10, 12, 14)
Output rating: AC1 250V 8A (2000VA)
AC15 250V 2.5A
DC1 25V 8A (200W)
Electrical life: ≥150,000 ops at rated load
Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated impluse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Remote “test” / “reset”
(5, 7, 9) Requires two N.O. contacts. (i.e. push buttons)
Minimum trigger time: >50mS
Fault level output (1, 2): 50% of I∆n (factory set)
User adjustable from 10 -60% in 5% increments
Load (resistive): 40mA max. @ 240V
Note: A remote lamp can only be connected when terminals 1
and 3 are being supplied with an AC supply
Housing: Grey flame retardant Lexan UL94 VO
Weight: ≈250g
Mounting option: On to 35mm symmetric DIN rail to BS5584:1978
(EN50 002, DIN 46277-3)
Terminal conductor size: ≤2.5mm2stranded
≤4mm2solid
Conforms to:
IEC 755. 50081-1, 50081-2, 50082-1 & 50082-2.
and pending. CE and Compliant.
•Options
1. For other supply voltages, alternative trip levels or time delays, please consult the sales
office.
2. The ELRV30 is available with a double-pole relay output:
ELRV30/2/P -Output relay will de-energise on fault condition
ELRV30/2/S -Output relay will energise on fault condition
3. Analogue outputs and communications based versions are also available; please refer to
separate data sheets.
•Accessories
Toroids: BZCT035 -35mm ∅, BZCT070 -70mm ∅
BZCT120 -120mm ∅, BZCT210 -210mm ∅
Note: The 120 and 210mm toroids MUST NOT be used if sensitivity settings of less than
300mA are required.
( ) Numbers in brackets shown above refer to terminal numbers on the relay housing.
FUNCTION DIAGRAM
Standard
output
fault
current
failureofconnection
totoroid
"reset" "test"
interrupted
Triplevel(In)
∆
Positivesafety
output
∆
t
Resetlevel
Terminal Protection to IP20
INSTALLATION
•BEFORE INSTALLATION, ISOLATE THE SUPPLY.
•Connect the unit as shown in the diagram below (N.B. certain features may not be required and
therefore do not need to be connected).
•Operational and setting information can be found on the reverse of this data sheet.
This unit should be installed in conjunction with the latest wiring regulations and practices (IEE, etc)
MOUNTING DETAILS
Insertscrewdriver
toreleaseclip
49.5
33
45
Installationworkmustbecarried
outbyqualifiedpersonnel.
Please state Supply
voltage when ordering.