manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Broyce Control
  6. •
  7. Relay
  8. •
  9. Broyce Control P9660 User manual

Broyce Control P9660 User manual

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
1
11
1
012378
Type: P9660
Type: P9660Type: P9660
Type: P9660
Earth Fault Relay
Earth Fault RelayEarth Fault Relay
Earth Fault Relay

True R.M.S. measurements

Low Set and High Set tripping thresholds

6 selectable IDMT (Inverse De inite Minimum Time) characteristic curves

Adjustable DT (De initive Time)

Measurement and live display o earth ault current

Last trip memory (last 10 trips stored and can be recalled)

Pre-de ined selectable CT ratio’s (5:5….6000:5)

Microprocessor based (sel checking) with non-volatile memory

“Ecosmart” Energy e icient power supply design

Rear mounted pluggable connectors or supply, relay contacts and current input
•OP RATION & OV RVI W
The P9660
P9660P9660
P9660 (from the P9600 series family of IDMT/DT relays) is a mi ropro essor based relay
designed to monitor and dete t an Earth fault urrent by measurement of the imbalan e of the
urrent from a urrent transformer arrangement as shown in the Conne tion Diagram on Page 6.
A lear ba klit LCD provides all the key information that the user requires for both operation and the
setting up. Setting is a hieved in a few simple steps and requires no previous knowledge of produ t
operation.
Normal operation provides the user with the a tual live earth fault urrent on one s reen. The a tual
urrent represents that of the urrent passing through the primary side of the externally onne ted
CT. This is a hieved by the setting of the ratio for the CT.
Programming mode allows the user to assign the operation of both internal relays for either Auto or
Manual resetting. Relay 2 has the added option of being allowed to energise at the start or end of a
time out period. If assigned to energise at the start, the Relay an be used to operate a buzzer or
lamp giving early warning before a system a tually shuts down.
Low-set and High-set thresholds an be programmed for the Earth fault dete tion. The time urrent
hara teristi of the low-set units are sele table between Normal Inverse urve 3/10, Normal
Inverse urve 1.3/10, Long Time Inverse urve, Very Inverse urve, Extremely Inverse urve,
Extremely Inverse 0.65 urve and Definite Time. High-set units are the Definitive Time type.
Instantaneous tripping is possible by setting the time to minimum.
A simple Summary s reen is displayed on e the programming is omplete. The same s reen an also
be displayed by subsequent presses of the “R S T” button. This allows the user to a ess key
information with the tamperproof transparent over losed and sealed.
A Test mode is provided (also a essible with the tamperproof transparent over losed) to onfirm
the orre t operation of the internal relays. The relays will energise when the “T ST” button is
pressed and de-energise when the button is released (AUTO Reset) or when the “R S T” button is
pressed (MAN reset).
Following a trip ondition, the information about the trip is then stored. This an then be re alled
later if required using the “R S T” button to a ess the information. The P9660
P9660P9660
P9660 has the ability to
store up to 10 trips and using the “Up” and “Down” buttons, allows ea h trip to be displayed
individually. Ea h trip is also marked with a time stamp showing the time from power up as well as
the time from the previous trip. This feature is very useful for establishing a pattern knowing when
tripping o urred and how frequent!
•FUNCTION OV RVI W
Programming mode.
Programmable parameters
User settings summary mode
1
Displaying of the Summary s reen during normal operation is a hieved via subsequent
presses of the “RESET” button. See Se tion 7. QUICK VIEW OF USER SETTINGS for further
information.
•PR S NTATION
1. LCD (Liquid Crystal Display) for user information 5. “MOD ” button*
2. “R S T” button 6. Parameter in rement button*
3. “T ST” button 7. Parameter de rement button*
4. “Power supply” green LED indi ation 8. “Trip status” red LED indi ation
* a essible only when the front over is open
START
TOROID RATIO
Set ratio of externally
onne ted toroid
N TWORK
FR QU NCY
Set for 50 or 60Hz
onne ted toroids
R LAY 1 S TTING
Set reset mode
method
R LAY 2 S TTING
Assign relay a tivation and
reset mode methods
ARTH FAULT
CURR NT S TTING
Set Low-set and High-set
tripping parameters
SUMMARY
1
List all parameter and
fun tion settings
START
Display live
earth fault
urrent
SUMMARY
1
List all parameter and
fun tion settings
Dims:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (main body)
L. 100mm







I
O
0.00
A

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
2
22
2
012378
•PROGRAMMING
Programming/setting of the P966
P966P966
P9660
00
0 is arried out using the 3 buttons lo ated
behind the transparent over.
The button sele ts the required parameter to be hanged. The
buttons either in rement or de rement a value a ordingly.
Any adjustments made are stored by the pressing and holding of the button
until the LCD shows the word “Saved!
Saved!Saved!
Saved!” See Se tion 6. SAVING OF SETTINGS.

Please read the “Notes during programming” before commencing with the
following.
1A. TOROID RATIO

Setting the Toroid Ratio will allow the “actual” Earth fault current (Io) to be
displa ed on the LCD which represents that of the current flowing through the parallel
connected, external CT’s. If no CT’s are used, the parameter should be set to 5/5 (i.e.
1:1). Use this if the fault current is likel to be <5A.

Default setting is “5/5”
•Press and hold the button. The LCD displays a s reen showing the
hara ters “User Settings
User SettingsUser Settings
User Settings” then the following s reen appears…
•Press either or to set the primary value of the external CT’s.

The digit after the forward slash “/” cannot be changed.
1B. N TWORK FR QU NCY

Default setting is “50Hz”
•Whilst in the same s reen as that for the Toroid Ratio (see 1A.), press
the button to display the options for NETWORK FREQUENCY
NETWORK FREQUENCYNETWORK FREQUENCY
NETWORK FREQUENCY.
•Press either or to sele t between 50Hz or 60Hz. This should be
set to suit the frequen y of the network being monitored.
•Press and hold the button to set the options for “
““
“Relay
RelayRelay
Relay
1
11
1”
” ”
” as des ribed
in the next se tion.
2. R LAY 1 S TTING

Default setting for Rela 1 is Manual resetting mode.
•The LCD displays the following s reen.
A tual LCD presentation when adjustable parameters are displayed.
•Press either or to sele t between AUTO
AUTOAUTO
AUTO resetting or MAN
MANMAN
MANUAL
resetting (after a fault has o urred).
•Press and hold the button to set the options for “Relay 2”
Relay 2” Relay 2”
Relay 2” as des ribed
in the next se tion.
continued on next page…
•INSTALLATION
•B FOR INSTALLATION, ISOLAT TH SUPPLY. THIS PRODUCT IS
D SIGN D TO CONN CT TO S V RAL TYP S OF CIRCUITS.
NSUR ALL AR ISOLAT D^
•Remove the P966
P966P966
P9660
00
0 from the pa kaging.
•Lift the raised part of the side lip in order to withdraw from the housing.
Carry this out on ea h side.
•Insert the P966
P966P966
P9660
00
0 into the panel ut-out and fit the side lips ba k on to the
housing.
•Slide the lips towards the front of the unit until they ome in to onta t with
the reverse of the panel. The unit is now se ured in pla e.
•Wire the supplied female pluggable onne tors as required.
•Plug the onne tors into the relevant so kets on the rear of the unit.
•The P966
P966P966
P9660
00
0 is now ready for powering and programming.

The front window of the P9660 is supplied with a clear protective film which can be
removed as and when necessar .
^ When arrying out future maintenan e on the produ t or appli ation and it
be omes ne essary to dis onne t the onne tors from the produ t, ensure for
the Current Transformer onne tor, they do not remain open ir uit
they do not remain open ir uitthey do not remain open ir uit
they do not remain open ir uit. This an
lead to high voltages being present on this onne tor.
•NORMAL OP RATION
•Apply power to the unit and the green “Power supply” LED will illuminate.
•The LCD will momentarily display a wel ome s reen as shown…
….then after a short delay reverts to indi ating the following information:
•T ST MOD
•Press and hold the button and both relays will energise. The LCD will
display the hara ters “T ST” and the produ t part number (as below). The
LCD ba klight and red “Trip” LED will flash.
•Release the button and the relay(s) will remain energised if set to Manual
reset or de-energise if set to Auto reset.
•Press the to de-energise relay(s) whi h are set to Manual reset. The
LCD will revert ba k to Normal operation. The LCD ba klight and red
“Trip” LED will stop flashing.

Testing should be carried out on a regular basis to check the integrit of the
P9660.
DO NOT use this product to provide a means of isolating circuits in
order to work on when placed in the “TEST”
“TEST”“TEST”
“TEST” mode. This should onl be
done b means of operating isolators, circuit breakers or other
methods of removing power in this application.
I
O
0.00
A
Installation work must be carried
out by qualified personnel.
A tual Earth
fault urrent
TEST
TYPE: P9660
Ver: X.X
TOROID RATIO
5 / 5
RELAY
1
CONFIG
URATION
AUTO
MAN
Digits whi h
an be adjusted
TYPE: P9660
Ver: X.X
Model No.
Version
TOROID RATIO
5 / 5
NETWOR FREQUENCY
50Hz
60Hz
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
3
33
3
012378
7. QUICK VI W OF US R S TTINGS

It is not possible to edit settings when these screens are displa ed.

This feature can also be activated with the front window closed!
•Press and hold the button to display the initial power up s reen.
•Press the same button again to display the “Last Tripped Information” s reen
(refer to the next section for further information on this feature).
•Press again to display the “Earth Fault Summary” s reen.
•Press again to display the onta t details for Broy e Control.
•Press again to revert ba k to Normal operation.
8. LAST TRIPP D INFORMATION

Refer to next page for detailed information of this feature
Notes during programming

If during programming it is necessar to abort, press the button briefl .

Pressing and holding either or for >1sec. will increment or decrement
the new value at a quicker rate.

Stepping through each User Setting screen is performed b pressing and holding
the button until the desired screen is displa ed.
Short presses of the button will allow further editable settings to be changed
within a specific screen.

If the user remains in a setting or summar screen where no adjustments or button
presses are made within a certain period, the screen will revert back to Normal
operation. Additionall , an settings that have been made but not stored will not be
saved.

“E/F” refers to Earth fault.
•TRIPPING MOD
•When an Earth fault ondition o urs, the urrent displayed on the LCD
in reased a ordingly. When the level of urrent ex eeds the Low-set setting,
the reading will be highlighted by the digits flashing.
•The LCD ba klight will flash.
•Relay 2 will energise immediately if set to energise at the start of the time out
period (See Se tion 3. RELAY 2 SETTING).
•The hara ters “Io>” will display to indi ate the Low-set has been triggered.
•If the urrent ontinues to in rease above the High-set setting, the hara ters
“Io>” will hange and display “Io>>” to indi ate the High-set has been
triggered.
•When the unit finally trips, the digits will stop flashing and remain highlighted.
This allows the user to see what urrent aused the unit to trip.
•The red “Tripped”
“Tripped”“Tripped”
“Tripped” LED will also flash.
•The relays whi h energised are also displayed on the s reen after tripping.
•Press to reset and return the unit ba k to normal operation (assuming
the fault has been leared). The LCD reverts ba k to displaying the normal
system urrents and the red “Tripped”
“Tripped”“Tripped”
“Tripped” LED stops flashing.

If either rela is set for Auto resetting, then the would have de-energised after the
fault had cleared. The corresponding rela ident (i.e. R1 and/or R2) on the displa
would also disappear. Pressing the “RESET”
“RESET”“RESET”
“RESET” button will onl clear the LCD. If either
rela is set for Manual resetting, then pressing the “RESET”
“RESET”“RESET”
“RESET” button will de-energise the
rela (s) and clear the LCD.
•PROGRAMMING (continued)
3. R LAY 2 S TTING

Default setting for Rela 2 is to energise at the end of the time out period.
Resetting mode is Auto.
•Setting of “Relay 2”
“Relay 2”“Relay 2”
“Relay 2” is arried out in a similar manner as “Relay 1”
“Relay 1”“Relay 1”
“Relay 1”; however it
is ne essary to assign the relay to either energise at the start (S) or end (E) of
the time out period.
A tual LCD presentation when adjustable parameters are displayed.
•Press and hold the button to set the options for “
““
“EARTH FAULT”
EARTH FAULT” EARTH FAULT”
EARTH FAULT” as
des ribed in the next se tion.
4. ARTH FAULT S TTING

Default settings for Earth Fault are shown in the LCD screen example in this
section.
•Settings for Earth fault are displayed in turn following subsequent presses of
the button. The Low-set trip urrent (Io>) is displayed first.
•Press either or to hange the urrent.
•Press the button to sele t the remaining settings and use the and
buttons to hange them.
A tual LCD presentation when adjustable parameters are displayed.
S reen example above also shows the default settings for OVERCURRENT.
•Press and hold the button to view the summary of settings for “
““
“EARTH
EARTH EARTH
EARTH
FAULT”
FAULT” FAULT”
FAULT” as des ribed in the next se tion.

If the Curve in selection “2:” is set to Definite Time, then selection “3:” will displa
“3: t>” and the required dela can then be set.

If High-set is set to Disable in selection “4:”, then Io>> or to>> cannot be
adjusted.
5. ARTH FAULT SUMMARY

It is not possible to edit settings when this screen is displa ed.
•Following the setting of “Earth Fault”, the LCD displays the “Earth Fault”
s reen showing a summary of the settings made during programming. All
settings are displayed. The sele ted CT ratio, Network Frequen y and Relay
operation (following a Reset) information is also displayed.
6. SAVING OF S TTINGS
•If after viewing the Summary s reen the settings are orre t, press and hold
the button until the word “
““
“Saved.
Saved.Saved.
Saved.”
””
” appears. Any new settings are now
stored.
•The s reen will revert ba k to Normal operation.
E/F
SUMMARY
Io> 2.00A
NI 3/10
ko> 0.1
Io>>10.0A
to>>0.05s
R1 = MAN R2 = AUTO (E)
CT=5:5, FREQ=50Hz
RELAY
2
CONFIG
URATION
AUTO (E)
MAN (E)
AUTO (S)
MAN (S)
E/F
SETTING
Low Set:
1: Io> 2.00A
The letter in bra kets refers to
whether Relay 2 has been set
to trigger at the start or end of
the time out period.
(E) = E
EE
End of time out
(S) = S
SS
Start of time out
Either abbreviation an appear
after the word MAN or
AUTO
See Section 3. RELAY 2
SETTING
I
O
3.60
A
Io>
I
O
13.00
A
Io>>
R1
Low-set
triggered
High-set
triggered
Relay(s) whi h
energised on
tripping
E/F
SETTING
Low Set:
1: Io> 2.00A
2: Curve NI 3/10
3: ko> 0.1
High Set:
4: Io>> 10.0A
5: t
o
>> 0.05s
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
4
44
4
012378
•PROGRAMMING (continued)
8A. LAST TRIPP D INFORMATION

This information is held in memor even if power is removed.
This feature allows the user to view and re all the key information relating to the last trip event and it an store up to 10 trip events. It is a essed as des ribed in Se tion 7
on the previous page.
The information displayed highlights the level of urrent at the time the trip o urred; the triggering method (Low-set or High-set) and whi h relays were a tivated. It also
shows the elapsed time from powering the
P966
P966P966
P9660
00
0
to the trip o urring and displayed against “Ttrip” as well as showing the time differen e between the trip displayed and
the one previous to that. This is shown against “Tdiff”.
An example of the s reen layout is shown below.

If there is only one
trip
event
stored in the memory, the display will show
“Tdiff:
----
d
--
h
--
m
--
s” when viewed.
Trip number
(1…10)
Relays that were
a tivated at trip
1
…
I
O
3.60
A
Io>
R1 R2
Ttrip: 0000d00h00m00s
Tdiff: 0000d00h00m00s
Level whi h was
triggered (i.e. Low-set)
Ttrip:
The elapsed time from
applying power to the
urrent trip
Tdiff:
The time differen e
between the urrent trip
and the previous trip
8
B. R CALLING TH LAST TRIPP D INFORMATION

If the unit has logged the maximum number of trips which can be stored, then the displa will show “Tdiff: ----d--h--m--s” when trip screen 10 is viewed.

The screen will revert back to Normal operation after 1 minute if no further button presses are made.

If a trip condition occurs whilst in this mode, the screen will automaticall change to displa the information relating to the current status.
•As des ribed in Se tion 7, use the to gain a ess to the Last Tripped Information s reen. The display will show the most re ent trip information as follows:
•If more than one trip event is stored, use the and buttons to sele t the s reens a ordingly.
•Press the button to exit the s reen information when finished or allow to time out automati ally.
1
…
Io 5.70A Io>
R1 R2
Ttrip: 0001d13h15m04s
Tdiff: - - - -d - -h - -m - -s
1
…
Io 6.20A Io>
R1 R2
Ttrip: 0001d19h24m56s
Tdiff: 0000d06h09m52s
2
…
Io 5.70A Io>
R1 R2
Ttrip: 0001d13h15m04s
Tdiff: - - - -d - -h - -m - -s
The example on the left shows the level of urrent re orded
on both trip events. The differen e between the first
re orded trip and se ond was 6h 09m
6h 09m6h 09m
6h 09m and 52s
52s52s
52s.
8C
.
CL ARING TH
LAST TRIPP D INFORMAT
ION
HISTORY

Once the information has been deleted, it will not be possible to recall this.

“Ttrip” information is still retained but won’t be displa ed after the carr ing out this
operation (See 9D)
•Press the button to a ess the relevant s reen.
•Press the and buttons simultaneously to delete the information.
When this is omplete, the s reen will show:
•Press the button again to exit.
No previous trip info
8D
.
CL ARING “Ttrip” INFORMATION

If the tripping histor hasn’t been deleted, previous information will be displa ed
from the last time the unit was powered up.
•The “Ttrip” information will still be held in memory after deleting the trip
history is made and also if power is removed and re-applied. However,
when power is re-applied, the internal ounter will reset and start from zero
•Only when a new trip ondition o urs will the “Ttrip” information get
updated and be displayed on the most re ent s reen.
Current
re orded at the
time of tripping
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
5
55
5
012378
•IDMT CHARACT RISTIC CURV S
*
Abbreviations used in the LCD s reen for the sele ted IDMT hara teristi urve.
The sequen e of urves that are presented to the user when programming is shown below
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
Normal Inverse 1.3/10
Normal Inverse 1.3/10Normal Inverse 1.3/10
Normal Inverse 1.3/10
(NI
(NI(NI
(NI
1.3/10 *
1.3/10 *1.3/10 *
1.3/10 *
1
10 20
I/I>
I/I>I/I>
I/I>
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
t
t
t
t
(s)
(s)
(s)
(s)
10
1
0.1
0.01
t
t
t
t (s)
(s)
(s)
(s)
Normal Inverse
Normal InverseNormal Inverse
Normal Inverse
3/10
3/103/10
3/10
(NI
(NI(NI
(NI
3/10 *
3/10 *3/10 *
3/10 *
t
t
t
t
(s)
(s)
(s)
(s)
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
10
1
0.1
1 10 20
I/I>
I/I>I/I>
I/I>
Long Time Inverse
Long Time InverseLong Time Inverse
Long Time Inverse
(LTI
(LTI(LTI
(LTI *
**
*
.
200
100
10
1
0.1
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
t
t
t
t (s)
(s)
(s)
(s)
1
10 20
I/I>
I/I>I/I>
I/I>
V
VV
V
ery Inverse
ery Inverseery Inverse
ery Inverse
(VI
(VI(VI
(VI *
**
*
1 10 20
I/I>
I/I>I/I>
I/I>
k
kk
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
10
1
0.1
0.01
t
t
t
t (s)
(s)
(s)
(s)
Extremely Inverse
Extremely InverseExtremely Inverse
Extremely Inverse
(EI
(EI(EI
(EI *
**
*
k
kk
k
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
100
10
1
0.1
0.01
t
t
t
t
(s)
(s)
(s)
(s)
1.0
0
0.1
0.05
1
10 20
I/I>
I/I>I/I>
I/I>
Extremely Inverse
Extremely Inverse Extremely Inverse
Extremely Inverse
(EI 0.65 *
(EI 0.65 *(EI 0.65 *
(EI 0.65 *
k
kk
k
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1
10 20
I/I>
I/I>I/I>
I/I>
1000
100
10
1
0.1
0.01
1.0
0
NI 3/10
NI 1.3/10
LTI
EI
EI 0.65
VI
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9660-2-A
6
66
6
012378
Ele tri al life:
≥
150,000 ops at rated load
Diele tri voltage: 2kV AC (rms) IEC 60947-1
Rated impulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Max. DC Load Breaking Capa ity Ele tri al Enduran e
Housing: Flame retardant Lexan
Prote tion: IP55 / IP20 (rear)
Weight: ≈ 410g
Mounting: Panel mounting. Cut-out = 91 x 91mm (± 0.5mm)
Max. panel thi kness: 12mm
Terminal type: UL94 V-0 rated pluggable and re-wireable female
onne tors omprising:
2-way (Power supply 1, 2)
6-way (Relay onta ts 3….8)
8-way (CT input 15, 16)
Note that terminals 9 to 14 are not used on this
model and should be left un onne ted.
Terminal ondu tor size: 0.05 - 2.5mm
2
(30 - 12AWG)
Re ommended tightening
torque: 4.4in lb (0.5Nm)
Wire stripping length: 0.24 – 0.30in (6 – 7.5mm)
Approvals: Conforms to IEC. CE and and RoHS Compliant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generi : IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
( ) Bold digits in bra kets refer to terminal numbers on the rear of the unit.
Options:
The P9600 range also in ludes ombined Over urrent or Earth fault relays
available with either IDMT or DT hara teristi s. Additionally, a voltage, power
and frequen y monitoring only produ t is also available. Please refer to separate
data sheets.
•T CHNICAL SP CIFICATION
Aux. Supply voltage Un (1, 2): 85 – 265VAC/85 - 370VDC
1
18 – 55VAC/18 – 72VDC*
(Voltage range should be specified at time of
ordering)
Rated frequen y: 50/60Hz (AC Supplies)
Isolation: Over voltage at. III
Rated impulse
withstand voltage:
1
4kV (1.2 / 50µS) IEC 60664
Power onsumption: 3W max.
* If onne ting a fuse externally, a Time Delay type is re ommended with a rating of 0.5A or
higher.
Rated urrent input In: 5A (dire tly onne ted)
Rated frequen y: 50/60Hz
Burden: <0.4VA @ In
Overload: 4 x In ( ontinuous)
External CT (15,16): Class P re ommended. (with 5A se ondary)
Maximum CT primary
urrent rating: 6000A
Earth fault settings:
Low-set trip (I
o
>): 0.10 – 5.00A (2 – 100%)
Low-set time multiplier (k
o
>): 0.05 – 1.00
Low-set definite time (t
o
>): 0.05 – 100s
High-set trip (I
o
>>): 0.10 – 50.0A (2 – 1000%) or disable
High-set definite time (t
o
>>): 0.05 – 2.5s
Pi k up value: +2% of trip setting
A ura y:
Prote tion threshold: ± 5%
Time delay (DT): ± 5% (with a minimum of 50mS)
Time delay (IDMT): ± 5% (with a minimum of 50mS and I > 1.2 x
set-trip)
A tual Earth fault urrent: ± 1% of rated urrent In
Display update time: <1 se .
Repeat a ura y: ± 0.5% @ onstant onditions
Ambient temperature: -10 to +60°C
Relative humidity: +95%
Output:
(RL1 - 3, 4, 5): 1 x SPDT relay
(RL2 - 6, 7, 8): 1 x SPDT relay
Output rating: AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
•CONN CTION DIAGRAM
L1
L2
L3
N
A1 A2
RL1
RL2
Aux.
1 2 3 4 5 6 7
9
8
10 11 12 13 14
16
15
I
N
•DIM NSIONS
96
96
MADE IN U.K.
10
100
89.5
96
Front view Side view
All dimensions are in mm.

Other Broyce Control Relay manuals

Broyce Control P50ELR Series User manual

Broyce Control

Broyce Control P50ELR Series User manual

Broyce Control P9680 User manual

Broyce Control

Broyce Control P9680 User manual

Broyce Control P9600 Series User manual

Broyce Control

Broyce Control P9600 Series User manual

Broyce Control P9620 User manual

Broyce Control

Broyce Control P9620 User manual

Broyce Control P9640 User manual

Broyce Control

Broyce Control P9640 User manual

Broyce Control P9690 User manual

Broyce Control

Broyce Control P9690 User manual

Broyce Control P50EFR User manual

Broyce Control

Broyce Control P50EFR User manual

Broyce Control ELRV-30 User manual

Broyce Control

Broyce Control ELRV-30 User manual

Broyce Control P9680C User manual

Broyce Control

Broyce Control P9680C User manual

Broyce Control P9650 User manual

Broyce Control

Broyce Control P9650 User manual

Broyce Control EcoSmart P9670 User manual

Broyce Control

Broyce Control EcoSmart P9670 User manual

Broyce Control ELRV-30 User manual

Broyce Control

Broyce Control ELRV-30 User manual

Broyce Control P9625 User manual

Broyce Control

Broyce Control P9625 User manual

Broyce Control ELR01PN User manual

Broyce Control

Broyce Control ELR01PN User manual

Popular Relay manuals by other brands

Bailey Infi 90 6642016 2 Series Instruction

Bailey

Bailey Infi 90 6642016 2 Series Instruction

F&F EPP-618 manual

F&F

F&F EPP-618 manual

Siemens SIRIUS 3RQ1 Original operating instructions

Siemens

Siemens SIRIUS 3RQ1 Original operating instructions

GROTHE MISTRAL FTR Instructions for installation and operation

GROTHE

GROTHE MISTRAL FTR Instructions for installation and operation

CRE Technology SCR2.0 user manual

CRE Technology

CRE Technology SCR2.0 user manual

Datakom DPR-05 quick start guide

Datakom

Datakom DPR-05 quick start guide

Elko CRM-2HE manual

Elko

Elko CRM-2HE manual

LynTec NPAC Instruction bulletin

LynTec

LynTec NPAC Instruction bulletin

Leuze MC3 Series Original operating instructions

Leuze

Leuze MC3 Series Original operating instructions

Vemer CLIP-485 user manual

Vemer

Vemer CLIP-485 user manual

Basler BE1-51 manual

Basler

Basler BE1-51 manual

VAMP VAMP 130 Operation and configuration instructions

VAMP

VAMP VAMP 130 Operation and configuration instructions

Micom ALSTOM P341 Documentation

Micom

Micom ALSTOM P341 Documentation

Pilz PLID d1 operating manual

Pilz

Pilz PLID d1 operating manual

Pilz P2HZ X1 operating instructions

Pilz

Pilz P2HZ X1 operating instructions

C&S Electronics CSMPA22-2S manual

C&S Electronics

C&S Electronics CSMPA22-2S manual

Omron K8AB-VW Series quick start guide

Omron

Omron K8AB-VW Series quick start guide

CTI FB800E instruction manual

CTI

CTI FB800E instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.