N° Code Range U.M. Description
35 c9 0...1 Flag Enable autostart function in PD
36 c10 0...1 Flag Select Pump down by time or pressure
37 c11 0...250 Seconds Second compressor delay
DEFROST MANAGEMENT PARAMETERS
38 d0 0...4 Flag Type of defrost
40 dI 0…250 Hours Interval between defrosts
41 dt1 -50…200 °C/°F End defrost temperature, evaporator
42 dt2 -50…200 °C/°F End defrost temperature, aux evap.
43 dtP 0...200 °C/°F Defrost end temperature when defrost has done
with compressor OFF and fans ON
44 dP1 1…250 Minutes Maximum defrost duration, evaporator
45 dP2 1…250 Minutes Maximum defrost duration, aux evap.
46 d3 0...250 Minutes Defrost start delay
47 d4 0/1 Flag Enable defrost on start-up
48 d5 0…250 Minutes Defrost delay on start-up
49 d6 0...2 -- Display on hold during defrost
50 dd 0…15 Minutes Dripping time after defrost
51 d8 0…15 Hours Alarm bypass after defrost
52 d8d 0…250 Hours Alarm bypass after door open
53 d9 0/1 Flag Defrost priority over compressor protectors
54 d/1 - °C/°F Defrost probe 1 read
55 d/2 - °C/°F Defrost probe 1 read
56 dC 0/1 Flag Time base (0=h/m;1=m/s)
57 d10 0...250 Hours Compressor running time for defrost
58 d11 -20...20 °C/°F Running time temperature for defrost
59 d12 0...3 -- Advanced defrost
60 dn 1...100 % Nominal defrost duration
61 dH 0...100 -- Proportional factor, variation in dI
ALARM MANAGEMENT PARAMETERS
62 A0 0.1…20.0 °C/°F Alarm (fan) differential
63 A1 0/1 Flag Relative or Absolute Alarm
64 AL -50…200 °C/°F Low temperature alarm threshold
65 AH -50…200 °C/°F High temperature alarm threshold
66 Ad 0…250 Minutes Low and high temperature signal delay
67 A4 0…15 Flag Digital input 1 configuration
68 A5 0…15 Flag Digital input 1 configuration
69 A6 0…100 Minutes Stop compressor from external alarm
70 A7 0…250 Minutes External alarm detection delay
71 A8 0/1 Flag Enable alarms ‘Ed1’ and ‘Ed2’