
PMSTR-4000
Quick Start Tips
September 15, 2021
Pa
e 2
CONFIGURATION OF PMSTR-4000
Option parameters are used to configure the PMSTR-4000. To access the option
parameters, press the gear icon. Enter 903 when prompted for a passcode.
The recommended first step when configuring a new installation is to apply the
default settings by setting option 12.0 to 1. This will apply the default settings and
then reset to 0 when complete.
Next, refer to bulletin PMSTR-4001 and go through the option parameters group by
group. This is important so that the sensor can be set up correctly, as well as any other
options such as pump control or outside air reset. The bulletin has a more complete
description of more advanced option groups such as rotation order and unit skipping.
ONLINE STATUS OF UNITS
Once the units are wired and powered, if communication is okay the firing rate should
appear if the unit is running, even if it shows as OFFLINE. Several conditions must be
true before a unit can be recognized as ONLINE (STANDBY, STARTING or
RUNNING):
Communication must be active
Sequencing must be properly enabled on the unit (described earlier)
Virtual HAND-OFF-AUTO switch must be set for AUTO
Unit must not be locked out
Unit must have operating limit input satisfied (voltage on terminal P15.4)
Unit must have burner control input on (from keypad or digital input)
If the unit is running when placed in AUTO, this ensures that all the conditions are met,
and the unit should be assigned a role as lead or lag and should then be controlled by
the PMSTR-4000 immediately.
If a unit is operated in HAND mode, it will show as OFFLINE, but the actual firing rate
will be displayed. This is because the unit is only OFFLINE relative to the PMSTR-4000.
This simply means that the PMSTR-4000 can’t remotely command the unit to help
satisfy the load.
If the unit is running and the firing rate is not being displayed, it is possible that the
Modbus communication is not set up at the units properly or that there is a wiring issue.