manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Control System
  8. •
  9. Carrier SYSTXCCSMS01-A User manual

Carrier SYSTXCCSMS01-A User manual

Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency or your
distributor or branch for information or assistance. The qualified
installer or agency nmst use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings and cautions
included in literature and attached to the unit. Consult local
building codes and the current edition of the National Electrical
Code (NEC) NFPA 70. In Canada, refer to the current editions of
the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol /_ on
the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words DANGER,
WARNING, and CAUTION. These words are used with the
safety-alert symbol. DANGER identifies the most serious hazards,
which will result in severe personal injury or death. WARNING
signifies hazards, which could result in personal injury or death.
CAUTION is used to identify unsafe practices, which may result
in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
INTRODUCTION
Carrier's Infinity ® Smart Sensors are optional replacements for
Remote Room Sensors used with Infinity ® Zoning systems. It
provides a temperature display and buttons to adjust the desired
temperature within the zone. It also displays outdoor temperature
and indoor humidity. When used with an Infinity ® Touch Control
wall control- FAN, HOLD and HOLD UNTIL features are
available. When used with an Infinity ® User Interface (UIZ) wall
control- FAN, HOLD, OVERRIDE, UNOCCUPIED features are
available.
INSTALLATION CONSIDERATIONS
Any zone may use an Infinity Smart Sensor. The Infinity Smart
Sensor can be "home run" wired directly to the Damper Control
Module, or "daisy chained" from the wall control or another Smart
Sensor via 4-wire ABCD communication bus. Ordinary thermostat
wire is recommended; however, solid conductor, stranded, or
shielded wire may be used. Use 22 AWG or larger for normal
wiring applications. Continuous wire lengths over 100 ft. should
use 20 AWG or larger. Plan the connection of each Smart Sensor to
provide easiest wiring route.
NOTE: Whenever possible, it is suggested to always "home run"
wires back to the Damper Control Module for convenience of
troubleshooting. Using a "pig-tailed" connection, or a field
supplied terminal block may be helpful in achieving proper wire
termination at the Damper Control Module.
An Infinity Smart Sensor may now be used to control Zone 1. In
addition, a Remote Room Sensor may also be used in the same
zone. If a Remote Room Sensor is applied in the same zone, the
Remote Room Sensor has temperature priority over the Smart
Sensor.
Fig. 1 - Infinity Smart Sensor
SYSTXCCSMSO1-A
A04147
INSTALLATION
Step 1 -- Select Smart Sensor Location
Sensor should be mounted:
• Approximately 5 ft. (1.5m) from floor.
• Close to center of zone, preferably on inside partitioning wall.
• On section of wall without pipes or ductwork.
• Where wiring can be routed to it within wall. Avoid running
directly next to other AC power.
Sensor should NOT be mounted:
• Close to a window, on outside wall, or next to a door leading to
the outside.
• Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature radiating object which may cause a false
reading.
• Close to or in direct airflow from supply registers and return-air
grilles.
• In areas with poor air circulation, such as behind a door or in an
alcove.
• Do not run wires next to AC power lines.
Outside Temp /
Fan Status
Humidity/OAT
Hold/Unoccupied
Control
Temperature
Setpoint
3OOL /HEAT
Time (+/-) Temp (+/-)
Fig. 2 -Smart Sensor Functions
A04136
Step 2 -- Install Infinity Smart Sensor
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing sensor, turn off all power to unit. There may
be more than 1 power disconnect.
1. Turn OFF all power to unit.
2. If an existing thermostat or sensor is being replaced:
a. Remove existing device from wall.
b. Disconnect wires from existing device, I at a time. Be care-
ful not to allow wires to fall back into wall.
c. Discard or recycle old device.
d. If 4 wires exist in wall, they may be used. If not, plan and
route wiring to connect with either the Damper Control
Module, or User Interface. Multiple Infinity Smart Sensors
may be daisy chained together, but somewhere chain nmst
connect to either Damper Control Module or the Infinity
Touch Control/Infinity User Interface wall control. (Smart
Sensor daisy chain wire linfit is 100 ft.)
Recommended connection is:
A - Green = Data A
B - Yellow = Data B
C - White = 24vac (corn)
D - Red = 24vac (hot)
NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently.
3. To mount Smart Sensor, remove rear mounting base. Route
wires through hole in mounting base and level base against
wall.
4. Mark wall through 2 mounting holes and drill two 3/16-in.
holes. Secure assembly to wall with 2 anchors and screws
provided, making sure all wires properly extend through
opening.
5. Adjust length and routing of thermostat wire to reach each
ternfinal entry on the connector. Strip 1/4-in. of insulation
from each wire and properly connect to A-B-C-D.
6. Push any excess wire into the wall. Seal hole in wall to pre-
vent any air leaks. Leaks can affect Smart Sensor operation.
7. Attach Infinity Smart Sensor to the mounting base by lining
up the plastic guides and gently snapping assembly togeth-
er.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Improper wiring or installation may damage the Smart Sensor.
Check to make sure wiring is correct before proceeding with
installation or turning on unit.
Step 3-- Setup and Checkout
NEW INFINITY SMART SENSOR SETUP
Upon initial power up, the Infinity Smart Sensor will need to be
properly addressed. "ZONE" will be displayed and default zone
number "2" will be shown in the temperature display. The word
"SETUP" will also appear in the lower left text area. Use the
TEMP (+/-) button to select the correct zone address number 1
through 8. If only one Damper Control Module exists, the zone
address selection will only be 1 through 4. Once the zone number
is selected, press the FAN button to store the zone address and exit
the setup menu. The Infinity Smart Sensor is ready to operate.
CHANGING ZONE ADDRESS
To change an existing zone address, enter the setup menu by
pressing the FAN button for 10 seconds until "ZONE" is
displayed. Use the TEMP (+/-) button to select the correct zone
address and then press the FAN button once to automatically save
and exit the setup menu. If no buttons are pressed for
approximately 3 nfinutes, the screen will automatically save and
exit back to a normal display.
To ensure that all changes are recognized by the main control,
perform the "Full Installation" flmction in the Installation &
Service Menu of the Infinity Touch Control after zone addresses
are changed.
BACKLIGHTING
The LCD backlighting will energize whenever a button is pressed.
The backlighting will de-energize after 10 seconds of no push
button or activity, To enable constant backlighting, press the FAN
button for 10 seconds to enter setup menu. Use the HOLD button
to toggle between "LIGHT OFF" and "LIGHT ON" which will
enable a fixed low intensity backlight. Press the FAN button to
save all settings and exit the setup menu. If no buttons are pressed
for approximately 3 minutes, the screen will automatically save and
exit back to a normal display.
FAN BUTTON
When used with an Infinity Touch Control wall control, pressing
the FAN button momentarily will scroll through: OFF, LOW,
MED, and HIGH speed continuous fan operation. If used with an
Infinity User Interface wall control, pressing the FAN button
momentarily will scroll through: AUTO, LOW, MED, and HIGH
speed continuous fan operation. When connected to either type of
wall control, the FAN button is used to enter into the setup mode
by holding the FAN button for 10 seconds.
HUMIDITY/OAT BUTTON
Pressing the HUMIDITY/OAT button will toggle between the
Outside Temperature and Indoor Relative Humidity reading
(humidity reading at wall control). The LCD will revert back to the
outside temperature after 5seconds.
COOL/HEAT BUTTON
Use the COOL/HEAT button to change between "COOL AT" and
"HEAT AT" setpoints.
TEMPERATURE UP/DOWN BUTTON
Use the TEMP (+/-) button to change a zone temperature setpoint.
Depending on the active heating/cooling mode, the "HEAT AT" or
the "COOL AT" setpoint will appear and will increment or
decrement accordingly. If not in a "HOLD" mode, changing the
setpoint, when used with an Infinity User Interface wall control,
will cause the Override timer to be displayed (i.e. 2-hours). If used
with an Infinity Touch Control wall control, changing the setpoint
will cause a HOLD UNTIL with a default time of approximately 3
hours from the current time to be displayed. Either the Override
timer or default time can be increased or decreased by using the
TIME (+/-) button.
TIME UP/DOWN BUTTON
When used with Infinity User Interface wall control and the TIME
(+/-) button is pressed during a normal operation, "OVERRIDE"
is displayed and the Override timer is shown (default is 2-hours).
When used with an Infinity Touch Control wall control and the
TIME (+/-) button is pressed during a normal operation, pressing
the setpoint will cause a HOLD UNTIL with a default time of
approximately 3 hours from the current time to be displayed.
When used with either wall control, the Override timer or default
time can be increased or decreased by using the TIME (+/-) button.
While the timer or default time is shown, the TIME buttons can be
used to raise or lower the Override timer or the default time in
15-minute increments up to a maximum of 24 hours. If the time is
decreased to zero, the "OVERRIDE" text disappears along with the
timer or the default time will be replaced with "SCHEDULED,"
depending on the type of wall control, and the program resumes
regular operation.
NOTE: If the wall control is configured for non-programmable
operation, the Infinity Smart Sensor will ignore HOLD and
Override functions at the Smart Sensor.
HOLD BUTTON
Pressing the HOLD button momentarily will cause "HOLD" to be
displayed. The system will continue using the active (displayed)
temperature setpoints indefinitely. Pressing the HOLD button again
removes the "HOLD" text and the system resumes normal
programming schedules. When used with an Infinity User Interface
wall control, pressing the HOLD button for approximately 3
seconds will cause "UNOCCUPIED" to be displayed in the lower
left area of the LCD and the unoccupied temperature settings will
be displayed. Pressing the HOLD button again cancels the
"UNOCCUPIED" mode and the system resumes normal
programming schedules.
NOTE: The Infinity Touch Control System does not include an
"unoccupied" mode.
SYSTEM OFF
When the OFF mode is selected on the Infinity Touch Control/
Infinity User Interface wall control, the Infinity Smart Sensor will
show "SYSTEM OFF" in the lower left text area of the display
screen. The end user will be unable to operate the system from the
Smart Sensor.
KEYPAD LOCK
The Infinity Smart Sensor can be locked if the FAN and
HUMIDITY/OAT buttons are pressed simultaneously for
approximately 3 seconds. A padlock icon will appear and all push
button functions will be ignored. Pressing the FAN and
HUMIDITY/OAT buttons again for 3 seconds will unlock the
Infinity Smart Sensor.
VACATION
When the VACATION mode is activated from Infinity Touch
Control/Infinity User Interface wall control, the Infinity Smart
Sensor will display the "VACATION" in the lower left area of the
LCD. The padlock icon will appear, flash and ignore all push
button functions for 15 minutes.
ERROR DISPLAY
COM ERROR (Communication Error) will be displayed If the
Infinity Smart Sensor cannot send or receive communication data
with the Infinity Touch Control/ Infinity User Interface wall
control. Check ABCD wiring and Zone address.
SYST ERROR (System Error or Malfunction) will be displayed if
a system critical error is active at the Infinity Touch
Control/Infinity User Interface wall control. Check fault history at
the wall control.
.... 4141......
NOTE: * ABCD Connections are in Parallel with each other.
Smart Sensors and Equipment may be connected in any combination,
For easier troubleshooting, the installer may elect to use one terminal block
for wall contro! and smart sensor connections, and the other for equipment connections,
AB CD
--7_--,2--.
// \/
\/
....... 141+..... J
TO EQUIPMENT OR n,"
ACCESSORY CONNECTIONS O
C3
z
<(
D_
W
£
ABCD
s_Ks
W_
/
2
o
8S
_s
sg
ON
<
AB CD
\
ABCD
f\\
/
/\
a2
z
<
©
o
£
DAISY CHAIN
OPTION
r¢
S
z
<
o3
I
.COMMUNICATION
BUS
DAMPER CONTROL MODULE
ZONES 1-4
Fig. 3 - Typical Smart Sensor Wiring diagram
TO OTHER
_1_L.... _ SMARTSENSORS
IF AVAILABLE
A04135
Copyright 2012 Carrier Corp, • 7310 W, Morris St. • Indianapolis, IN 46231 Edition Date: 10/12
Manufacturer reserves the right to change, at any time, specification8 and design8 without notice and without obligations,
Catalog No: ZONESMS-02SI
Replaces: ZONESMS- lSl

This manual suits for next models

1

Other Carrier Control System manuals

Carrier Zone Manager User manual

Carrier

Carrier Zone Manager User manual

Carrier SmartView User manual

Carrier

Carrier SmartView User manual

Carrier bryant ONEBB3ZAC01 User manual

Carrier

Carrier bryant ONEBB3ZAC01 User manual

Carrier PIC 5+ User manual

Carrier

Carrier PIC 5+ User manual

Carrier i-Vu CCN Pro 4.2 User manual

Carrier

Carrier i-Vu CCN Pro 4.2 User manual

Carrier Infinity SYSTXCCITC-01SI User manual

Carrier

Carrier Infinity SYSTXCCITC-01SI User manual

Carrier AQUASNAP 30RA/RH Instruction Manual

Carrier

Carrier AQUASNAP 30RA/RH Instruction Manual

Carrier Zone Manager User manual

Carrier

Carrier Zone Manager User manual

Carrier SmartVu control Use and maintenance manual

Carrier

Carrier SmartVu control Use and maintenance manual

Carrier 3V VVT 33ZCVVTZC-01 Instructions and recipes

Carrier

Carrier 3V VVT 33ZCVVTZC-01 Instructions and recipes

Carrier ZONECC3ZAC01 User manual

Carrier

Carrier ZONECC3ZAC01 User manual

Carrier Infinity SYSTXCCICF01-B User manual

Carrier

Carrier Infinity SYSTXCCICF01-B User manual

Carrier Fireye PMSTR-4000 User manual

Carrier

Carrier Fireye PMSTR-4000 User manual

Carrier PRO-DIALOG PLUS 50AZ Manual

Carrier

Carrier PRO-DIALOG PLUS 50AZ Manual

Popular Control System manuals by other brands

DANHAG APP-control operating manual

DANHAG

DANHAG APP-control operating manual

Infinity Sidekick V1 user manual

Infinity

Infinity Sidekick V1 user manual

SEW-Eurodrive IPOS plus manual

SEW-Eurodrive

SEW-Eurodrive IPOS plus manual

West Mountain Radio TARGETuner manual

West Mountain Radio

West Mountain Radio TARGETuner manual

Kamome MACS-KM quick start guide

Kamome

Kamome MACS-KM quick start guide

dani alu Barrial A60e installation guide

dani alu

dani alu Barrial A60e installation guide

Vestil BOL-R Series instruction manual

Vestil

Vestil BOL-R Series instruction manual

EUTRAC NetComposer Technical manual

EUTRAC

EUTRAC NetComposer Technical manual

micro-trak ProPlant Reference manual

micro-trak

micro-trak ProPlant Reference manual

btsr ULTRAFEEDER operating manual

btsr

btsr ULTRAFEEDER operating manual

Marshall Electronics Network Control Box for IMD Monitors... operating instructions

Marshall Electronics

Marshall Electronics Network Control Box for IMD Monitors... operating instructions

VTI Instruments Metek EX1202 user manual

VTI Instruments

VTI Instruments Metek EX1202 user manual

Siemens SIMATIC NET TeleControl SINAUT ST7 System manual

Siemens

Siemens SIMATIC NET TeleControl SINAUT ST7 System manual

THOMSON Grass Valley Kalypso Classic Reference manual

THOMSON

THOMSON Grass Valley Kalypso Classic Reference manual

HEIDENHAIN LIF 181 R Mounting instructions

HEIDENHAIN

HEIDENHAIN LIF 181 R Mounting instructions

Mitsubishi Electric M800VW Series manual

Mitsubishi Electric

Mitsubishi Electric M800VW Series manual

Niles iPower IPC-8PRO Installation & operating guide

Niles

Niles iPower IPC-8PRO Installation & operating guide

Lennox Harmony II Zone Control System installation instructions

Lennox

Lennox Harmony II Zone Control System installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.