COMPATIBLE CURRENT
PROBES & SENSORS FOR
POWER QUALITY METERS
E N G L I S H User Manual
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Copyright © Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All rights reserved.
No part of this documentation may be reproduced in any form or by any means (including electronic storage and retrieval or
translation into any other language) without prior agreement and written consent from Chauvin Arnoux®, Inc., as governed
by United States and International copyright laws.
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
This documentation is provided “as is,” without warranty of any kind, express, implied, or otherwise. Chauvin Arnoux®,
completeness of the text, graphics, or other information contained in this documentation. Chauvin Arnoux®, Inc. shall not be
the user of the documentation has been advised of the possibility of such damages.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Thank you for purchasing an AEMC current probe.
For best results from your instrument and for your safety, read the enclosed
operating instructions carefully and comply with the precautions for use. These
Measurement category IV corresponds to measurements taken at the
source of low-voltage installations.
Example: power feeders, counters and protection devices.
Measurement category III corresponds to measurements on building
installations.
-
trial devices.
Measurement category II corresponds to measurements taken on cir-
cuits directly connected to low-voltage installations.
Example: power supply to domestic electrical appliances and portable
tools.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
The protection assured by the current probe can be compromised if it is used in a
way that is not recommended by the manufacturer.
Comply with the rated maximum voltage and current, and the measurement
category. Do not use the current probe on networks where the voltage or
Comply with the conditions of use (e.g. temperature, humidity, altitude, degree
of pollution, location).
Do not use the current probe if its housing is open, deteriorated, or incorrectly
reassembled. Before each use, check the integrity of the insulation of the unit,
jaws, clamps, housing, and leads.
Do not subject the current probe to water or other liquids.
Keep the jaw contacts of the clamp absolutely clean.
Use suitable personal protective equipment when hazardous voltages may be
accessible in the installation where the measurement is made.
Any repairs must be carried out by accredited skilled personnel.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
1.1 Receiving Your Shipment......................................................................4
1.2 Ordering Information.............................................................................4
2.1 Control Features...................................................................................5
2.1.1 AmpFlex® Models 193-24-BK, 193-36-BK & 196-24-BK ..........5
2.1.2 MiniFlex® Model MA193-BK .....................................................6
2.1.3 AC/DC Current Probe Model J93 .............................................7
2.1.4 AC Current Probe Models MN93-BK & MN193-BK..................8
2.1.5 AC Current Probe Model MR193-BK........................................9
2.1.6 AC Current Probe Model SL261.............................................10
2.1.7 AC Current Probe Model SR193-BK ......................................11
4.1 Electrical .............................................................................................14
4.2 Environmental.....................................................................................15
4.3 Mechanical..........................................................................................15
4.4 Safety..................................................................................................16
5.1 Cleaning..............................................................................................17
5.2 Battery Replacement ..........................................................................17
5.2.1 Model MR193 .........................................................................17
5.2.2 Model SL261 ..........................................................................17
5.2.3 Model J93...............................................................................18
5.3 Repair and Calibration........................................................................19
5.4 Technical and Sales Assistance..........................................................19
5.5 Limited Warranty.................................................................................20
5.6 Warranty Repairs................................................................................20
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
Upon receiving your shipment, make sure that the contents are consistent with the
packing list. Notify your distributor of any missing items. If the equipment appears
at once, giving a detailed description of any damage. Save the damaged packing
container to substantiate your claim.
The current probes in this manual are compatible only with AEMC® Power
Analyzers (see § 4 for meter compatibility).
AmpFlex® Sensor 24" Model 193-24-BK ..........................................
AmpFlex® Sensor 36" Model 193-36-BK ..........................................
AmpFlex® Sensor 24” Model 196A-24-BK........................................
MiniFlex® Sensor 10" Model MA193-10-BK......................................
MiniFlex® Sensor 14" Model MA193-14-BK......................................
AC/DC Current Probe Model J93 .....................................................
AC Current Probe Model MN93-BK..................................................
AC Current Probe Model MN193-BK................................................
AC Current Probe Model MR193-BK................................................
AC Current Probe Model SR193-BK ................................................
AC/DC Current Probe Model SL261* ...............................................
* Adapter for SL261 - BNC Adapter............................................
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
2
3
4
1
1. Flexible sensor
2. Sensor opening connector
3. Shielded lead
4. Custom 4-pin input connector (available standard or IP 67 compliant,
depending on instrument)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
2
3
4
1
1. Flexible sensor
2. Sensor opening device
3. Shielded lead
4. Custom 4-pin input connector
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
1. Jaws
2. 4-point CA connector
3. Safety guard
4. Zero adjustment knob
5. Power ON/ Low battery indicator
6. Three-position switch: ON, OFF, battery test
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
5
4
2
3
6
1
1. Jaws
2. Protective guard
3. Two-position range switch (MN193 only)
4. Jaw opening lever
5. Shielded lead
6. Custom 4-pin input connector
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
5
2
4
3
7
6
1
1. Jaws
2. Protective guard
3. Jaw opening lever
4. Two-position range switch
5. Shielded lead
6. Zero adjustment
7. Custom 4-pin input connector
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
2
3
5 6
4
1
1. Jaws
2. Zero adjust knob
3. Range selection switch
4. Battery compartment screw
5. Battery compartment cover
6. BNC Adapter (sold separately - Cat. #2140.40)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
4
2
3
5
1
1. Jaws
2. Protective guard
3. Jaw opening lever
4. Shielded lead
5. Custom 4-pin input connector
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
in a conductor or bus bar without opening the circuit. They also insulate the user
from dangerous voltages in the circuit.
The choice of current probe or sensor to be used depends on the amperage to be
measured and the diameter of the cables or size of the bus bar.
For three-phase measurements, use the color-coded ID markers to associate
system.
Connect the current probe or sensor to the current terminals of the instrument.
Connect the probe to the instrument.
Adjust the zero by turning the potentiometer with no conductor in the jaws of the
clamp.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
Press the jaw opening lever on the probe to open the jaws.
Clamp the probe around the conductor to be tested. For best results, center the
conductor in the jaws of the clamp.
I
® ®
AmpFlex®: Press simultaneously on both sides of the opening connector.
MiniFlex®
Clamp the sensor around the conductor to be tested. For best results, center the
conductor in the jaws of the clamp.
Close the sensor by pushing the moving part into the connector until it clicks.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
instrument with which they are used with.
"
"
"
"
"
(1) 10 to 6500AAC for Models 8435 and 8436
(2) 200mA to 10,000A measurement range for the PEL 100 Series.
Battery: 9V Alkaline NEDA 1604A, 6LR61
Battery Life: MR193 - 100H typical
SL261 - 55H typical
J93 - 70H typical
Battery life is twice the typical value when using Lithium batteries
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
Indoor use.
Degree of pollution: 2
Altitude: < 2000 m
"""
"""
"""
"
""
"
""
""
""
""
"
"
"
"
""
""
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
Protection index IP 40 for the probes and IP 30 jaws open, according to IEC 60 529
IP 65 for the AmpFlex® according to IEC 60 529
IK 04 according to IEC 50102
Drop test: According to IEC 61010-1
Electrical safety according to IEC 61010-2-032.
Maximum applicable voltage:
AmpFlex®
AmpFlex®196A: 1000V CAT IV
MiniFlex®
SL261: 600V CAT III
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
® will not be held responsible
for any accident, incident, or malfunction following a repair done other than by its
service center or by an approved repair center.
Use a soft cloth, dampened with soapy water. Rinse with a damp cloth
and dry rapidly with a dry cloth.
Do not use alcohol, solvents, or hydrocarbons.
Do not splash water directly on the instrument.
Disconnect the MR193 completely and turn the rotary switch to OFF.
Use a screwdriver to unscrew the screws and remove the battery
compartment cover on the backside of the unit.
Withdraw the battery from its compartment.
Disconnect the old battery without pulling on the wires and replace with
a new one, observing the polarity.
Put the battery into its compartment.
Put the cover back in place and screw the screws back in.
Disconnect the SL261 completely and turn the rotary switch to OFF.
compartment cover.
Replace the battery with a new one, observing the polarity.
Put the cover back in place and screw the screw back in.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Current Probes & Sensors for Power Quality Meters
Insert a tool, not more than 3mm in diameter, in the hole in the battery
compartment cover.
Remove it completely by hand.
Remove the battery and the shim from the compartment.
Place the new battery in the compartment with the polarity as indicated
on the label. Then replace the shim.
Put the battery compartment cover back in the slide and push it in until
you hear a click.
Used batteries must not be treated as ordinary household waste.
Recycle them appropriately.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

This manual suits for next models

20

Other Chauvin Arnoux Measuring Instrument manuals

Chauvin Arnoux C.A 1310 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 1310 User manual

Chauvin Arnoux C.A 6292 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6292 User manual

Chauvin Arnoux C.A 6503 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6503 User manual

Chauvin Arnoux AEMC Instruments MR417 User manual

Chauvin Arnoux

Chauvin Arnoux AEMC Instruments MR417 User manual

Chauvin Arnoux C.A 5205 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 5205 User manual

Chauvin Arnoux C.A 700 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 700 User manual

Chauvin Arnoux AEMC Instruments OX5042 User manual

Chauvin Arnoux

Chauvin Arnoux AEMC Instruments OX5042 User manual

Chauvin Arnoux F605 User manual

Chauvin Arnoux

Chauvin Arnoux F605 User manual

Chauvin Arnoux C.A 6681 LOCAT-N User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6681 LOCAT-N User manual

Chauvin Arnoux C.A 6250 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6250 User manual

Chauvin Arnoux C.A 6549 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6549 User manual

Chauvin Arnoux E3N User manual

Chauvin Arnoux

Chauvin Arnoux E3N User manual

Chauvin Arnoux C.A 6545 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6545 User manual

Chauvin Arnoux C.A 6531 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6531 User manual

Chauvin Arnoux CA 10 User manual

Chauvin Arnoux

Chauvin Arnoux CA 10 User manual

Chauvin Arnoux CA 8345 User manual

Chauvin Arnoux

Chauvin Arnoux CA 8345 User manual

Chauvin Arnoux AEMC PowerPad 8436 User manual

Chauvin Arnoux

Chauvin Arnoux AEMC PowerPad 8436 User manual

Chauvin Arnoux ULYS MCM User manual

Chauvin Arnoux

Chauvin Arnoux ULYS MCM User manual

Chauvin Arnoux MiniFLEX  MA200 User manual

Chauvin Arnoux

Chauvin Arnoux MiniFLEX MA200 User manual

Chauvin Arnoux Y4N User manual

Chauvin Arnoux

Chauvin Arnoux Y4N User manual

Chauvin Arnoux PAC 11 User manual

Chauvin Arnoux

Chauvin Arnoux PAC 11 User manual

Chauvin Arnoux ORITEL IR 205 User manual

Chauvin Arnoux

Chauvin Arnoux ORITEL IR 205 User manual

Chauvin Arnoux AEMC J93 User manual

Chauvin Arnoux

Chauvin Arnoux AEMC J93 User manual

Chauvin Arnoux C.A 6541 User manual

Chauvin Arnoux

Chauvin Arnoux C.A 6541 User manual

Popular Measuring Instrument manuals by other brands

Stanford Research Systems SR785 Brochure & specs

Stanford Research Systems

Stanford Research Systems SR785 Brochure & specs

Newport N-STP-910 operating manual

Newport

Newport N-STP-910 operating manual

Micronics Ultraflo 2000 operating manual

Micronics

Micronics Ultraflo 2000 operating manual

Fluke ASM-990 Series Operating guidelines

Fluke

Fluke ASM-990 Series Operating guidelines

ISOMAG CS3820 Operating and maintenance manual

ISOMAG

ISOMAG CS3820 Operating and maintenance manual

National Instruments FD-11613 manual

National Instruments

National Instruments FD-11613 manual

YOKOGAWA AQ6370D user manual

YOKOGAWA

YOKOGAWA AQ6370D user manual

Mirion Technologies DMC 3000 user guide

Mirion Technologies

Mirion Technologies DMC 3000 user guide

PCE Health and Fitness PM 3 user manual

PCE Health and Fitness

PCE Health and Fitness PM 3 user manual

marsden HM-201M user manual

marsden

marsden HM-201M user manual

ETouch ETM-G01E quick start guide

ETouch

ETouch ETM-G01E quick start guide

Pro-dig Intelli-Tork owner's manual

Pro-dig

Pro-dig Intelli-Tork owner's manual

biochrom Ultrospec 50 user manual

biochrom

biochrom Ultrospec 50 user manual

LB Altimeters ALFA QUICK START & ROAD MAP

LB Altimeters

LB Altimeters ALFA QUICK START & ROAD MAP

Laser Technology TruPulse 200X Quick reference field guide

Laser Technology

Laser Technology TruPulse 200X Quick reference field guide

Lovibond Tintometer XD 7500 quick start guide

Lovibond

Lovibond Tintometer XD 7500 quick start guide

Sun Microsystems MGA-1400 installation instructions

Sun Microsystems

Sun Microsystems MGA-1400 installation instructions

Kimans HYDRASONIC S8 user manual

Kimans

Kimans HYDRASONIC S8 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.