1.1 ENVIRONMENTALCONDITIONS
1.2 COMPLIANCEWITHSTANDARDSAND SAFETY
1.2.1 COMPLIANCE WITH STANDARDS
The instrument complies with the following standards :
1.2.2 SAFETY
■The instrument complies with the requirements of standards EN 61010-1 and EN 61557, i.e.:
- service voltage: 550 V,
- measurement category: III with double insulation,
- level of pollution: 2.
- Never use on DC or AC networks exceeding 550V with respect to ground.
■This instrument is designed for indoor use at an altitude < 2000m
■Never open the housing of this instrument until it has been disconnected from any source of
electricity.
■Before making any measurement, make sure that the positions of the cords and the setting of the
switch are correct.
■Never connect to the circuit to be measured if the housing of the instrument is not closed.
■The protection provided by the instrument may be compromised if it is used in a manner other than
that specified
1.2.3 ELECTROMAGNETIC COMPATIBILITY
CE instrument, in conformity with product standard EN 61326-1 (ed. 97) + A1 (ed. 98):
Emissions: Requirements on class B equipment.
Immunity: Requirements on equipment used in discontinuous operation on industrial sites.
1.3 POWER SUPPLY
- Power supply : 6LR61.5Valkalinebatteries;theycanbereplacedbyrechargeablebatteries
having a capacity of at least 1,800mAh.
- Battery life : 30 hours or approximately
- 10, 000 loop measurements
- 30, 000 voltage or current measurements during 5 seconds.
1 position of the phase conductor 15 full-wave signal for the testing of RCDs
2 detected voltage probe 16 measurement without triggering of differentials (signalling level)
3 measurement smoothed for display 17 measurement with triggering of differentials (power level)
4 audible buzzer activated 18 RCD test current reading in "pulse" mode
5 call in progress (serial link) 19 test of residual current devices in "pulse" mode
6 battery charge level 20 test of residual current devices in "sweep" mode
7 standby switching function deactivated 21 secondary function activated
8 levelof memory use 22 type of quantity displayed
9 reading/recording in memory 23 selective measurement
10 secondary display unit A2 24 alarm function activated or display of an alarm threshold
11 "test" number for storage 25 "WARNING" indicator (if it appears, refer to the manual)
12 "object" number for storage 26 reference voltage
13 main display unit A1 27 time to tripping of the RCD
14 half-wave signal for the RCD test 28 compensation of measuring cables activated
Temperature: Service conditions: -10 to +55°C - storage and transport (without batteries): -40 to +70°C.
%RH (without condensation): Service conditions: 85% max. - storage and transport (without batteries): 90% max.
Tightness: IP54 as per standard NF EN 60 529.
- EN 61010-1 (Ed. 2001) - EN 60529 (Ed. 92)
- NF EN 61557 (Ed. 97: parts 1 to 7, ed. 2001: part 10) - EN 50102 (Ed. 95) / UL 94