CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 8 -
1) Analog 1 Function Options
1) Fuel Level S-W –Fuel amount, in percentage, can be measured and displayed using a
standard StewartWarner scale sender of 240 ohms –33 ohms. 240 = Empty and 33 =Full.
Sender ground must be common with batterynegative.
2) Fuel Level VDO –Fuel amount, in percentage can be measured and displayed using a VDO
scale sender of 10 ohms –180 ohms. 10 = Empty and 180 =Full. Sender ground must be
common with battery negative.
3) Oil Pressure PSI –Oil pressure, in PSI, can be measured and displayedusing astandard
Stewart Warner scale sender of 240 ohms –33 ohms. 240 = 0 PSI and 33 = 100 PSI.
Sender ground must be common with batterynegative.
4) Oil Pressure bar –Oil pressure,in bar, can be measured anddisplayed standard Stewart
Warner scale sender of 240 ohms –33 ohms. 240 = 0 bar and 33 = 7 bar. Sender ground
must be common with batterynegative.
5) Oil Pressure VDO PSI –Oil pressure, in PSI, can be measured and displayedusing a
standard StewartWarner scale sender of 10 ohms –180 ohms. 10 = 0 PSI and 180 = 150
PSI. Sender ground must be common with battery negative.
6) Oil Pressure bar –Oil pressure,in bar, can be measured anddisplayed using a standard
Stewart Warner scale sender of 10 ohms –180ohms. 240 = 0 bar and 33 = 10 bar.
Sender ground must be common with batterynegative.
7) Switch –This setting allows for a switch to be connected rather thanan analog sender. Set
Analog 1 Message to assign alabel to the switch device.
8) None –Set when no functionality is required.
2) Digital Function Activation
1) Off / Always / Run –Describeswhen the parameter will be monitored for alarmconditions.
Run refers to when theengineis running. Offdisables the alarmconditions. Always enables
the alarm constantly regardless of engine state.
2) AlarmDelay –The time period, after Sender Check Bypass, that the parameter must be on
the alarmconditionbefore the alarmbecomes latched.