PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
DANLERS ceiling surface passive infra-red
occupancy switches (CESF PIR) can be
ceiling mounted on a square pattress box
(DANLERS code: PABO).
The CESF PIR incorporates a passive infra-red
quad sensor to detect movement of a warm
body within its detection zone (diagram A) and
a photocell to monitor the ambient light level.
up to 5m
up to 7m
Strong detection zone
i.e. person moving
arm or walking
towards PIR
Secondary detection
zone i.e. person
walking perpendicular
to PIR
For optimum coverage recommended
mounting height: 2.4 to 5m
DIAGRAM A (DETECTION)
Upon detecting movement, if the ambient light
is dark enough, the CESF PIR will switch the
load on. The ambient threshold can be set by
the user to between approximately 30 lux and
1000 lux and maximum (photocell inactive) at
the PIR via the LUX adjuster (diagram B).
If no more movement is detected within a
pre-selected time, then the CESF PIR will
switch the load off. This time lag can be
set via the TIME adjuster to 10 seconds,
20 seconds, 40 seconds, 80 seconds,
2 minutes 30 seconds, 5 minutes, 10
minutes, 20 minutes or 40 minutes
(diagram B).
CESF PIR also incorporates a sensitivity
adjuster, labelled ‘SENS’, to reduce the range
and sensitivity of detection (diagram B).
INSTALLATION PROCEDURE
1. Please read these notes carefully before
commencing work.
In case of doubt please consult a qualified
electrician.
2. POSITIONING: The CESF PIR should be
installed to achieve correct coverage of
the area, see diagram A. If the photocell
override facility is required, the switch
must be located above an area where
daylight can give greater illumination
than the artificial light. Avoid locating this
product where it is exposed to windy or
drafty conditions (exposed lobbies, open
ceiling voids or near ventilation fans) or
near heat sources. To cover large areas
CESF PIRs should be spaced in a 5 metre
grid formation.
3. The greatest energy savings will be made
if each CESF PIR controls an independent
set of lamps. They can be wired in parallel
but this should ideally be limited to three,
see diagram D.
4. Make sure the power is isolated from
the circuit. The CESF PIR should be
connected as shown in diagrams C & D:
L - Live in.
N - Neutral in.
SL - Switched Line out.
LOADING
See overleaf for loading details.
START-UP MODE
When the PIR is powered up, the PIR will
switch on the lighting load for 1 minute then
switch it off. After 2 seconds it will switch
on again if it detects movement. With TIME
set to minimum the load will stay on for 10
seconds so the detection range can be
easily assessed. If a manual override-off
switch is positioned before the PIR in the
circuit (diagrams C & D, note 1) it will do
this each time the wall switch is switched
on. Alternatively, if the wall switch is placed
after the PIR (diagrams C & D, note 2) it will
not enter the start-up mode each time.
TIME, LUX AND SENSITIVITY SET UP
For convenience, ensure that the TIME is
set to the minimum when setting up the
LUX level. Afterwards set the TIME to a
value suitable for the application, making
reference to diagram B.
The LUX is best set up when the local
ambient light is at approximately the
minimum desired working light level, a lux
meter placed on the surface under the
CESF PIR may help. With the LUX set
fully clockwise wait for the CESF PIR to
switch off. Rotate the LUX adjuster slowly
anticlockwise (- to +), whilst waving your
hand approximately 1m below the PIR, until
the load switches on.
Turn the SENS adjuster fully clockwise
for maximum range and sensitivity of the
person detector. Turn anti-clockwise for
reduced range and sensitivity.
CESF PIR
Ceiling Surface Mounted
PIR Occupancy Switch (Presence detection)
Input: 220-240 Vac 50Hz
TIME
min max
LUX
max min
SENS
min max
Typical settings
30 LUX
1000 LUX
PHOTOCELL
INACTIVE
40m
20m
10m
5m
2.5m
80s
10s
20s
40s
100%
50%
DIAGRAM B (ADJUSTING TIME, LUX & SENSITIVITY)
TROUBLESHOOTING
The load will not switch on:
• The LUX adjuster is set too low and is
inhibiting the switch.
• The SENS adjuster is set too low.
• The moving body is not emitting more
IR than the background. (Person
wearing insulating clothing in a warm
environment)
• Person is too far from the PIR switch, see
detection diagram.
• Person is moving unusually slowly
(perhaps when testing).
The load switches on when nobody is
present:
• Heater causing infra-red variations in a
small cold room. Reduce the sensitivity
adjuster or re-site the CESF PIR.
• Please contact DANLERS for further
technical support.
VARIANTS - MAINS VOLTAGE
CESFAPIR Surface mounted PIR
absence switch (square
enclosure)
CESFPIRAR Surface mounted PIR
switch with additional
range - 8m maximum
(square enclosure)
CESRPIR Surface mounted
PIR switch (round
enclosure)
CESRAPIR Surface mounted PIR
absence switch (round
enclosure)
13/04/2021DAT0098 CESFPIR
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
PRECAUTIONS AND WARRANTY
This product conforms to BS EN 60669-2-1 and
BS EN 55015.
Please ensure the most recent edition of the
appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp
circuit breaker and voltage surge protection.
Please ensure that this device is disconnected
from the supply if an insulation test is made.
Other DANLERS Product ranges
- Remotely adjusted PIR occupancy switches
- Manually adjusted PIR occupancy switches
- Daylight linked dimming controls
- Photocell switches
- Time lag switches
- Outdoor security switches
- Dimmer switches inc. LED dimming
- HVAC controls
- Radio remote (RF) controls
Please call for more information or visit
our website.
This product is covered by a warranty which
extends to 5 years from the date of manufacture.
INPUT:
Voltage: 220 - 240Vac
Frequency: 50Hz
LOADING:
Resistive loads: 6 amps (1500W)
Fluorescent: 6 amps (1500W)
LED Drivers and LED
lamps and fittings: 6 amps (1500W)
Electronic and wire
wound transformers: 3 amps (750W)
CFL and 2D lamps: 2 amps (500W)
Fans: 1 amp (250W)
Minimum load
2W resistive, suitable
for most energy
saving lamps, LEDs
and emergency
fittings.
OPERATING CONDITIONS:
The temperature difference between the
detection target and the background must
be at least 4 °C.
Ambient
temperature:
-20... +40 °C (lout
0.05 A)
Max. case
temperature: +70 °C
Storage
temperature: -25... +75 °C
Max. relative
humidity: 0... 80%, non cond.
CONNECTORS:
Terminal block
Wire size:
0.5mm2- 2.5mm2
solid or stranded
Wire strip length: 6-7mm
Tightening torque: 0,4 Nm/4 Kgf.cm
MECHANICAL DATA:
Dimensions: 86mm x 86mm x
22mm
Weight: 98g (unpacked)
Degree of
protection: IP20
Protection class: Built-in Class 2
Material (casing) Flame-retardant
polycarbonate
Finish / Colour Matt /White (RAL
9003)
Protection class: Built-in Class 2
CESF PIR
Ceiling Surface Mounted PIR Occupancy Switch (Presence detection)
Input: 220-240 Vac 50Hz
CONFORMITY AND STANDARDS:
EMC emission: EN60669-2-1:2004
inc. A12:2010
EMC immunity: EN60669-2-1:2004
inc. A12:2010
Safety: EN60669-2-1:2004
inc. A12:2010
Environment:
Complies with
WEEE and RoHS
directives
VARIANTS - LOW VOLTAGE:
DANLERS also design and manufacture an
extensive range of Ceiling Surface Mounted
PIR Occupancy Switch variants some of
which are listed below:
CESF PIR 12VAC
CESF PIR 12VDC
CESF PIR 24VAC
CESF PIR 24VDC
12V or 24V (ac or
dc) operation
CESF PIR 12VACVF
CESF PIR 12VDCVF
CESF PIR 24VACVF
CESF PIR 24VDCVF
12V or 24V (ac or
dc) operation Volt
Free contacts
TECHNICAL DETAILS
WIRING DIAGRAMS
L
load
Note 1: Optional manual
wall switch for overriding off.
Note 2:
Alternative
position for
optional
wall switch
N
230 VAC
NSLL CESF PIR
L
Note 1: Optional manual
wall switch for overriding off.
N
230 VAC
NSL
L
load
NSL
L
Note 2:
Alternative
position for
optional
wall switch
CESF PIR CESF PIR
DIAGRAM C (WIRING A SINGLE PIR) DIAGRAM D (WIRING IN PIRS IN PARALLEL)
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
13/04/2021DAT0098 CESFPIR

Other manuals for CESF PIR

2

Other DANLERS Switch manuals

DANLERS WACEPIR Quick start guide

DANLERS

DANLERS WACEPIR Quick start guide

DANLERS WAPIR Quick start guide

DANLERS

DANLERS WAPIR Quick start guide

DANLERS CESF PIR Quick start guide

DANLERS

DANLERS CESF PIR Quick start guide

DANLERS ControlZAPP CZ CEFL 10VDC Quick start guide

DANLERS

DANLERS ControlZAPP CZ CEFL 10VDC Quick start guide

DANLERS CEFL PIR Quick start guide

DANLERS

DANLERS CEFL PIR Quick start guide

DANLERS ControlZAPP CZ CESR 10VDC Quick start guide

DANLERS

DANLERS ControlZAPP CZ CESR 10VDC Quick start guide

DANLERS CESPLL10VDC Quick start guide

DANLERS

DANLERS CESPLL10VDC Quick start guide

DANLERS CESFPIRSV Quick start guide

DANLERS

DANLERS CESFPIRSV Quick start guide

DANLERS TLSW 10 ILM Quick start guide

DANLERS

DANLERS TLSW 10 ILM Quick start guide

DANLERS GRTL MK Quick start guide

DANLERS

DANLERS GRTL MK Quick start guide

DANLERS CESRA PIR DSIP Quick start guide

DANLERS

DANLERS CESRA PIR DSIP Quick start guide

DANLERS CEFLAPIR Quick start guide

DANLERS

DANLERS CEFLAPIR Quick start guide

DANLERS TWSW Quick start guide

DANLERS

DANLERS TWSW Quick start guide

DANLERS TLSW HB Quick start guide

DANLERS

DANLERS TLSW HB Quick start guide

DANLERS CESRAPIRSD Quick start guide

DANLERS

DANLERS CESRAPIRSD Quick start guide

DANLERS CEPH NO Quick start guide

DANLERS

DANLERS CEPH NO Quick start guide

DANLERS CEFLA PIR DALIP Quick start guide

DANLERS

DANLERS CEFLA PIR DALIP Quick start guide

DANLERS GRTLA MK User manual

DANLERS

DANLERS GRTLA MK User manual

DANLERS TLSW HB Quick start guide

DANLERS

DANLERS TLSW HB Quick start guide

DANLERS WACE RFS Quick start guide

DANLERS

DANLERS WACE RFS Quick start guide

DANLERS DUSW Quick start guide

DANLERS

DANLERS DUSW Quick start guide

DANLERS CEFL PIR LR Quick start guide

DANLERS

DANLERS CEFL PIR LR Quick start guide

DANLERS GRTLA MK Quick start guide

DANLERS

DANLERS GRTLA MK Quick start guide

DANLERS BMEXPIR Quick start guide

DANLERS

DANLERS BMEXPIR Quick start guide

Popular Switch manuals by other brands

Network Technologies UNIMUX-USBV-xO Installation and operation manual

Network Technologies

Network Technologies UNIMUX-USBV-xO Installation and operation manual

ALTAI MIS200P Quick setup guide

ALTAI

ALTAI MIS200P Quick setup guide

Converters.TV 826 Operation manual

Converters.TV

Converters.TV 826 Operation manual

Huawei Quidway S3100 Series Operation manual

Huawei

Huawei Quidway S3100 Series Operation manual

TRENDnet TPE-30102WS user guide

TRENDnet

TRENDnet TPE-30102WS user guide

MaxTech FHX-8100 user guide

MaxTech

MaxTech FHX-8100 user guide

IOGear GCS1782 installation guide

IOGear

IOGear GCS1782 installation guide

Chamberlain 760CB installation instructions

Chamberlain

Chamberlain 760CB installation instructions

Transition Networks SISTF101X-241-LRT user manual

Transition Networks

Transition Networks SISTF101X-241-LRT user manual

Scion-Tech SC04.MX42 user manual

Scion-Tech

Scion-Tech SC04.MX42 user manual

Network Technologies PRIMUX-16X64 quick start guide

Network Technologies

Network Technologies PRIMUX-16X64 quick start guide

NetComm NP3005 Specifications

NetComm

NetComm NP3005 Specifications

RuggedCom RuggedSwitch RS940G installation guide

RuggedCom

RuggedCom RuggedSwitch RS940G installation guide

Vetra MegaSwitch VIP-602 Series User instructions

Vetra

Vetra MegaSwitch VIP-602 Series User instructions

SOR 651 K9 RF General instructions

SOR

SOR 651 K9 RF General instructions

Intermatic RC2103S Owner installation instruction manual

Intermatic

Intermatic RC2103S Owner installation instruction manual

Horstmann CentaurPlus C11 Series 2 User operating instructions

Horstmann

Horstmann CentaurPlus C11 Series 2 User operating instructions

Matrix Switch Corporation MSC-2HD1632S product manual

Matrix Switch Corporation

Matrix Switch Corporation MSC-2HD1632S product manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.