manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. DANLERS
  6. •
  7. Switch
  8. •
  9. DANLERS CESF PIR IP66 Quick start guide

DANLERS CESF PIR IP66 Quick start guide

Other DANLERS Switch manuals

DANLERS ControlZAPP CZ CEFL Quick start guide

DANLERS

DANLERS ControlZAPP CZ CEFL Quick start guide

DANLERS GRTLA MK Quick start guide

DANLERS

DANLERS GRTLA MK Quick start guide

DANLERS WAPIR Quick start guide

DANLERS

DANLERS WAPIR Quick start guide

DANLERS BMPIR10M Quick start guide

DANLERS

DANLERS BMPIR10M Quick start guide

DANLERS CESF PIR User manual

DANLERS

DANLERS CESF PIR User manual

DANLERS CEFLA PIR DALIP Quick start guide

DANLERS

DANLERS CEFLA PIR DALIP Quick start guide

DANLERS CESFPIRSV Quick start guide

DANLERS

DANLERS CESFPIRSV Quick start guide

DANLERS CESF PIR User manual

DANLERS

DANLERS CESF PIR User manual

DANLERS CEFL PIR Quick start guide

DANLERS

DANLERS CEFL PIR Quick start guide

DANLERS GRTLA MK User manual

DANLERS

DANLERS GRTLA MK User manual

DANLERS CZ CEFL Quick start guide

DANLERS

DANLERS CZ CEFL Quick start guide

DANLERS TWSW Quick start guide

DANLERS

DANLERS TWSW Quick start guide

DANLERS TLSW HB Quick start guide

DANLERS

DANLERS TLSW HB Quick start guide

DANLERS GRTL MK Quick start guide

DANLERS

DANLERS GRTL MK Quick start guide

DANLERS DUSW Quick start guide

DANLERS

DANLERS DUSW Quick start guide

DANLERS ControlZAPP CZ CESR 10VDC Quick start guide

DANLERS

DANLERS ControlZAPP CZ CESR 10VDC Quick start guide

DANLERS TLSW 10 ILM Quick start guide

DANLERS

DANLERS TLSW 10 ILM Quick start guide

DANLERS WACEPIR Quick start guide

DANLERS

DANLERS WACEPIR Quick start guide

DANLERS COPIR IP66 User manual

DANLERS

DANLERS COPIR IP66 User manual

DANLERS ControlZAPP CZ CEFL 10VDC Quick start guide

DANLERS

DANLERS ControlZAPP CZ CEFL 10VDC Quick start guide

DANLERS CEFL PIR LR Quick start guide

DANLERS

DANLERS CEFL PIR LR Quick start guide

DANLERS BMEXPIR Quick start guide

DANLERS

DANLERS BMEXPIR Quick start guide

DANLERS EasyZAPP EZ CEFL Quick start guide

DANLERS

DANLERS EasyZAPP EZ CEFL Quick start guide

DANLERS WACE RFS Quick start guide

DANLERS

DANLERS WACE RFS Quick start guide

Popular Switch manuals by other brands

SMC Networks SMC6224M Technical specifications

SMC Networks

SMC Networks SMC6224M Technical specifications

Aeotec ZWA003-S operating manual

Aeotec

Aeotec ZWA003-S operating manual

TRENDnet TK-209i Quick installation guide

TRENDnet

TRENDnet TK-209i Quick installation guide

Planet FGSW-2022VHP user manual

Planet

Planet FGSW-2022VHP user manual

Avocent AutoView 2000  AV2000BC AV2000BC Installer/user guide

Avocent

Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies PT-7728 Series user manual

Moxa Technologies

Moxa Technologies PT-7728 Series user manual

Intos Electronic inLine 35392I operating instructions

Intos Electronic

Intos Electronic inLine 35392I operating instructions

Cisco Catalyst 3560-X-24T Technical specifications

Cisco

Cisco Catalyst 3560-X-24T Technical specifications

Asante IntraCore IC3648 Specifications

Asante

Asante IntraCore IC3648 Specifications

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Siemens

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core DCS520 quick start guide

Edge-Core

Edge-Core DCS520 quick start guide

RGBLE S00203 user manual

RGBLE

RGBLE S00203 user manual

Thrustmaster FLIGHT SIMULATOR X quick guide

Thrustmaster

Thrustmaster FLIGHT SIMULATOR X quick guide

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Southwire

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Buhler Nivotemp NT 61 Brief instructions

Buhler

Buhler Nivotemp NT 61 Brief instructions

Kramer VS-41HDCP user manual

Kramer

Kramer VS-41HDCP user manual

Techly IDATA AU-270 user manual

Techly

Techly IDATA AU-270 user manual

Belkin F1U109 user manual

Belkin

Belkin F1U109 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.6ampsovercurrent,1kVovervoltage.Pleaseensure
thatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Ceiling Surface PIR occupancy switches
CESF PIR IP66
DANLERSceilingsurfacepassiveinfra-redoccupancyswitches(CESF
PIRIP66)canbeceilingmountedonthesquarepattressbox(PABO)
supplied.
TheCESFPIRIP66incorporatesapassiveinfra-redquadsensorto
detectmovementofawarmbodywithinitsdetectionzone(diagram
A)andaphotocelltomonitortheambientlightlevel.
Upondetectingmovement,iftheambientlightisdarkenough,the
CESFPIRIP66willswitchtheloadon.Theambientthresholdcan
besetbytheusertobetweenapproximately100luxandinnitelux
(photocellinactive)viatheLUXadjuster(diagramB).
Ifnomoremovementisdetectedwithinapre-selectedtime,thenthe
CESFPIRIP66willswitchtheloadoff.Thistimelagcanbesetvia
theTIMEadjusterto10seconds,20s,40s,1minute15seconds,
2m30s,5m,10m,20mor40minutes(diagramB).
CESF PIR IP66 also incorporates a sensitivity adjuster, labelled
‘SENS’,toreducetherangeandsensitivityofdetection(diagramB).
Loading
TheCESFPIRIP66canbeconnectedtoa230V(+/-10%)50Hz
(+/-10%)acsupply
Theycanswitchupto6amps(1500W)of:
• Fluorescentlamps,highfrequencyorswitchstart
• Incandescentormainshalogenlamps(recommendedwithintegralsafetyfuse)
• Electronicorwirewoundtransformers.
Theycanalsoswitchupto:
• 2amps(500W)oflowenergylamps:CFL,LED,2Detc.
• 1amp(250W)ofmetalhalidelampsorfans.
Theyhaveaminimumswitchingcapacityof0.5W,forlessthanthisaGold
relayversionshouldbeused,seeVariantssection.
Forlargerloads,thePIRcanbeusedtoswitchacontactor.
24/07/13 INSxxx CESF PIR IP66
Variants
AsDANLERSdesignandmanufactureintheUK,variantscanbesupplied,
codedbythefollowingsufxesandappliedinthisorder:
• 12Vor24V  12Vor24V(acordc)operation
• VF   VoltFreecontacts
• GOLDorLG GoldorLogicGoldcontacts
• NC   NormallyClosedcontacts
Variantdetailsarecoveredinanenclosedaddendumsheetifapplicable.
Troubleshooting
The load will not switch on:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
• TheSENSadjusterissettoolow.
• ThemovingbodyisnotemittingmoreIRthanthebackground.
  (Personwearinginsulatingclothinginawarmenvironment)
• PersonistoofarfromthePIRswitch,seedetectiondiagram.
• Personismovingunusuallyslowly(perhapswhentesting).
The load switches on when nobody is present:
• Heatercausinginfra-redvariationsinacoldsmallroomorceilingvoid
 drafts,fans,orsealeddoorscausingairmovement.
  Reducethesensitivityadjusterorconsiderusingthe
  CESFPIRIP662Ddoubledetectionversion.
• PleasecontactDANLERSforfurthertechnicalsupport.
Installation procedure
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
2.POSITIONING:TheCESFPIRIP66shouldbeinstalledtoachieve
correctcoverageofthearea,seediagramA.
Ifthephotocelloverride
facilityisrequired,theswitchmustbelocatedaboveanareawhere
daylightcangivegreaterilluminationthanthearticiallight.Avoid
locatingthisproductwhereitisexposedtowindyordraftyconditions
(exposed lobbies, open ceiling voids or near ventilation fans) or
nearheatsources.TocoverlargeareasCESFPIRIP66sshould
bespacedina5metregridformation.
3.ThegreatestenergysavingswillbemadeifeachCESFPIRIP66
controlsanindependentsetoflamps.Theycanbewiredinparallel
but this should ideally be limited to three, see diagram D.
4.Makesurethepowerisisolatedfromthecircuit.TheCESFPIR
IP66shouldbeconnectedasshownindiagramsC&D:
L-Livein.N-Neutralin.SL-SwitchedLineout.
Start-up mode
WhentheCESFPIRIP66ispoweredup,itwillswitchontheload
for1minute,theloadwillthenswitchoffandtheCESFPIRIP66will
enteritsOperatingMode.Ifamanualoverride-offswitchispositioned
beforetheCESFPIRIP66inthecircuit(diagramsC&D,note1)it
willdothiseachtimethewallswitchisswitchedon.Alternatively,if
thewallswitchisplacedafterthePIR(diagramsC&D,note2)itwill
not enter the start-up mode each time.
Time and Lux set-up
Forconvenience,ensurethattheTIMEissettotheminimumwhen
settinguptheLUXlevel.AfterwardssettheTIMEtoavaluesuitable
fortheapplication,makingreferencetodiagramB.
TheLUXisbestsetupwhenthelocalambientlightisatapproximately
theminimumdesiredworkinglightlevel,aluxmeterplacedonthesurface
undertheCESFPIRIP66mayhelp.WiththeLUXsetfullyclockwise
wait for the CESF PIR IP66 to switch off. Rotate the LUX adjuster
slowlyanticlockwise(-to+),whilstwavingyourhandapproximately
1mbelowthePIR,untiltheloadswitcheson.
L
load
Note 1: Optional
manual wall switch
for overriding off.
Note 2: Alternative
position for optional
wall switch
N
230 VAC
L
N
SL
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
For optimum coverage
recommended mounting
height: 2.4 to 5m
load
Note 1: Optional manual wall switch
for overriding off
Note 2: Alternative
position for optional
wall switch.
L
N
230 VAC
L
N
SL
L
N
SL
L
N
SL
A: Detection diagram
C: Wiring diagram,
single PIR
D: Wiring diagram, multiple PIRs
B: Adjusting time, lux
and sensitivity
TIME
min max
LUX
max min
SENS
min max
20s
40s
1m15s
2m30s
5m
10m
10s
20m
40m 100
∞
1000
66% 100%
Typical settings