DanVex AD-10000 User manual

DanVex AD-10000
Adsorption air dehumidifier
Operation manual

R
www.danvex.fi
1

R
www.danvex.fi
CONTENT
Safety instructions.....................................................................................................................3
Introduction................................................................................................................................4
Purpose......................................................................................................................................4
Operation principle.....................................................................................................................4
Design........................................................................................................................................5
Dimensions and weight..............................................................................................................5
Installation..................................................................................................................................6
Technical data............................................................................................................................7
Commissioning..........................................................................................................................7
Maintenance.............................................................................................................................11
Transportation..........................................................................................................................12
Parts list...................................................................................................................................12
Attachment...............................................................................................................................13
Warranty obligations................................................................................................................16
2

R
www.danvex.fi
Safety instructions
AD series dehumidifiers meet all the requirements stated in European safety regulations and
standards.
All persons admitted to operate or maintain the DanVex AD-10000 dehumidifiers should read
these instructions manual and to be briefed for its safe operation.
Only the personnel with sufficient knowledge of the dehumidifiers operation principle is permitted
to perform the adsorption dehumidifiers operation and maintenance.
Only authorized personnel with special education is permitted to perform maintenance and repair
works on electrical system.
Only authorized service center personnel is permitted to perform repair works on electrical
components.
It is prohibited to install or operate the units in the locations subject to explosion hazard..
Before opening any panels of the unit body it is required to disconnect the dehumidifier from
the mains.
Before starting any maintenance works the dehumidifier should be out-of-operation for 15
minutes.
The unit's panels must be always closed except when the dehumidifier is being maintained.
The dehumidifier can be used for air drying at atmospheric pressure only.
Never use the dehumidifier without filters since the drying rotor can get contaminated which will
cause loss of efficiency.
This manual should always be at hand and not far from the dehumidifier.
The dehumidifier maintenance and inspection works should be performed in accordance with a
fixed schedule.
Only original spare parts should be used.
It is required to receive a written approval from «DanVex Оу» or from its local representative for
any changes or modifications of the dehumidifier.
3

R
www.danvex.fi 4
Introduction
This specification is a technical document that certifies the DanVex AD-10000 dehumidifier
parameters and characteristics.
Purpose
DanVex AD-10000 (in short AD-10000) is designed for efficient air dehumidification with the air
humidity up to 100%, at the temperature from –20ºС to +40ºС with minimum energy
consumption. It can be used either as an independent unit for installation inside and outside of
premises where air humidity control is required or along with an air treatment system.
Operation principal
The main dehumidifier part is a rotor having a cellular structure made from fibrous ceramic
material and SelicaGel. The rotor is divided into two zones by a sealing device: one for
dehumidification, another for regeneration.
Thus, the dehumidifier works with two air flows. The volume of the dehumidified air is bigger. The
air flow of a smaller volume is used for moisture removal from the dehumidifier rotor. The rotor is
subject to the action of different oppositely directed air flows by sectors. The air flow to be
dehumidified (PROCESS AIR) passes through the biggest sector. The moisture from the air is
trapped (adsorbed) by the rotor material. The air leaves the rotor in dehumidified condition (DRY
AIR) and is directed to a certain part of the building or a technological process where
dehumidified air or a certain air humidity levels are required. Since the rotor rotates slowly the
incoming air always contacts with the rotor active part, thus a continuous dehumidification
process is assured.
The air flow used for the rotor regeneration is called regeneration air (REGENERATION AIR). It is
о
heated up to 140 С and when passing through a small sector it removes the moisture trapped by
the rotor material. The moisture is removed from the rotor in the form of humid air (MOIST AIR)
which is discharged outside the dehumidified loop
Adsorption rotor
Process air
Rotor motor
Heater
Dry air
Moist air
Regeneration air
Filter
Filter
Process air fan
Regeneration air fan
· The air to be dehumidified passes through the rotor. Water molecules are absorbed by the rotor.
о
· The rotor is reactivated by another air flow preheated to 140 C. The moisture is removed from the room
in the form of moist air.
Pic.1. Dehumidifier air flows diagram

R
www.danvex.fi
Design
The dehumidifier answers IP 44 protection class according to IEC.
Body
The dehumidifier body is made of stainless zinc-plated steel. It is thermally insulated which
allows the dehumidifier to be used in low-temperature premises and prevents condensate
formation inside the dehumidifier.
The body has a frame structure which allows easy moving of the dehumidifier during
transportation and installation.
The dehumidifier is equipped with detachable panels and doors that assure access for
maintenance and repair.
The rotor drive belt tension mechanism and a sealing system assures the dehumidification
reliable and efficient operation.
Rotor
The dehumidifier is equipped with a drying rotor manufactured in accordance with unique
technologies covered by a patent in force. The rotor represents a matrix consisting of numerous
air channels. It is made of composite material with introduced active SelicaGel and assures a
very large contact area with air flow for moisture adsorption in the small volume of the rotor. This
material is highly efficient for water molecules attraction and retention, it is noncombustible and
explosion-proof, with a long service life. The rotor manufacturing technology assures production
of a product capable of saturated air processing without risk of destruction, it means that the
rotor can be used along with a precooler. Besides, the rotor will not be damaged even if the fan or
the reactivation air heater fail to function.
Filters
The dehumidifier is equipped with two filters. One filter is located at the dehumidified air inlet, the
another one is installed at the reactivation air inlet.
Air flow fans: for dehumidified air flow and for reactivation air flow
The fans are of a radial type, single phase, IP 54 class, ISO F. The fans maintenance can be
performed after the service panels are removed.
Electric panel
Electrical components are located inside the dehumidifier and can be reached through
detachable or opening panels. Switches and indicators are located in the front part of the
dehumidifier.
Reactivation air heater
The reactivation air heater consists of a heating element.
Control panel
DanVex AD- 00 100 dehumidifier is equipped with an automatic control system. All commands
are input using the buttons located on the control panel with a LCD-display.
Dimensions and weight
Insignificant design changes are possible! Table 1
Length Depth Weight
Height Dehumidified
air Dry air Reactivation
air
Moist air
2250mm 1650mm 1800mm ø 630 mm ø 315 mm ø 315 mmø 630 mm 980 kg
5

R
www.danvex.fi 6
Pic. 2. AD-10000 dehumidifier dimensions
Installation
Installation and the covered area
AD-10000 dehumidifier is designed for indoor installation. It should be positioned upright on an
even surface. It is recommended to fix the dehumidifier. It is required to leave some free space
(1500 mm) in front and above the dehumidifier for filters, fans and rotor maintenance and
inspection.
Channel connections for permanent installation
The dehumidifier can be installed directly in the room to be dehumidified or in a separate
ventilation chamber. In case of special versions it can be places outdoors as well. To assure
better parameters and efficiency the air outlets should be equipped with diffusers.
Moist air duct
Moist air should be discharged outside the dehumidified loop (to outdoors). The air duct
should be as short as possible to minimize the possibility of condensation of the moisture
from the moist air. The duct should be slightly inclined downwards to prevent the condensate
entering the equipment. In case it is required to install the moist air duct upright it should be
insulated and drain holes should be drilled in the lowest part of the elbow bend (2-4 mm).
Regeneration air duct
The regeneration air duct should be as short as possible. A metal net is installed at the duct input
to prevent foreign matters entering the dehumidifier. There is no need to insulate the duct. The
duct inclination angle is optional.
Dehumidified and dry air ducts at the dehumidifier installation inside the dehumidified
loop
As a rule in case the dehumidifier is installed in the dehumidified loop air ducts for the air intake
are not required. A dry air duct is connected with the air-ducting system for dry air distribution
inside the premises.
Dehumidified and dry air ducts at the dehumidifier installation outside the dehumidified
loop
In case the dehumidifier is installed outside the dehumidified loop either a recirculation or an
open circuit is used. If a recirculation circuit is used the air to be dehumidified is supplied from the
loop via an air duct and the dehumidified dry air is supplied to the dehumidified room the same
way. If an open dehumidification circuit is used only dry air is supplied to the room.
Electrical connection
Please see the attached electric diagram

R
www.danvex.fi
Technical data of AD-10000
Table 2
Commissioning
Start up procedures:
1. Make sure the dehumidifier is disconnected from the power supply source and that its main
switch is in OFF position.
2. Open the dehumidifier service panels and make sure there are no foreign matters inside
the dehumidifier.
3. Make sure all air throttles are opened and that channels are clean and not blocked.
4. Make sure that air filters are installed and clean.
5. Manually turn the fans impellers and make sure they rotate freely.
6. Check the internal fuse.
7. Close the service panels and connect the dehumidifier to 380/400V power supply.
8. Switch on the dehumidifier power supply. The following will be displayed on the control
panel LCD:
7
Dehumidified air*
Rated air consumption
Pressure
3
m/hour
Pa
10000
500
Parameter Unit Value
Reactivation air*
Rated air consumption
Pressure
3
m/hour
Pa
3500
250
Electric power and rated current
Total power
Voltage (3 phase, 50 Hz)
kW
V
80
380/400
Reactivation air heater
Heater capacity
Heater type
kW
-
70
Tubular Heating Element
Miscellaneous data
Maximum sound pressure level
Operational temperatures range
Standard filter: dehumidified air
R eactivation air
IEC protection, the whole dehumidifier
dB(A)
оС
-
-
-
65
–20…+40
EU3
EU3
IP44
о 3
* The above mentioned values are nominal based on the air temperature of 20 С and the air density of 1,2kg/m

R
www.danvex.fi 8
9. Press «F1» to start the dehumidifier. The dehumidifier will start with default settings. Use «F4»
button to stop the dehumidifier. It should be noted that after switching off the fans and the rotor
continue operation for 5-10 minutes to prevent the overheating protection tripping.
10. Press «ESC» to enter the setting menu «Setting data 1». Enter temperature, relative humidity
and regeneration temperature by pressing «▼» or «▲» buttons till the required values are set.
Press «ENTER».
11. Press «▼» or «▲» for navigation, correction of temperature and relative humidity range.
Press «ENTER».

R
www.danvex.fi
12. Press «▼» or «▲» for correction of regeneration air and process air temperature range.
Press «ENTER».
13. Press "ESC" to enter the "Working mode 1" menu to get information on the operation
conditions of process air fans, regeneration air fan, rotor and heater motor.
Alarm signals
In the dehumidifier there are two types of alarm signals: the first type is used to announce about
serious failures, the second type is used to announce about minor problems.
In case of a serious problem a buzzer will sound, the failure cause will be displayed on the screen
and the dehumidifier will stop. In case of a minor problem a buzzer will sound and the failure
cause will be displayed on the screen.
An acoustic signal is the indication of improper operation. Press «F2» to switch the acoustic
signal off. Press «ENTER»
9

R
www.danvex.fi 10

R
www.danvex.fi
Maintenance
The dehumidifier can operate for a long time providing the maintenance schedule is observed.
The maintenance schedule depends on its operational environment, air contamination level and
installation place. It can be corrected based on the actual conditions.
Improper maintenance and service can cause the reduction of the dehumidification efficiency
and the humidifier components failure.
ATTENTION! For the dehumidifier maintenance:
Turn off the dehumidifier 15 minutes before the front service panel is opened. It will allow the
dehumidifier to cool down.
Disconnect the dehumidifier from the mains by turning the switch to OFF position and
disconnecting the power plug from the mains socket.
Filters
The dehumidifier is equipped with two separate filters, one for process air and one for
regeneration air. The filters are located in front of their appropriate inputs and are used for
cleaning of the air entering the dehumidifier.
The filters cleaning and replacement intervals are based on the amount of dust and particles in
the air at the place of installation. It is recommended to check the filters at least once per month.
Never use the dehumidifier without filters.
Rotor
The rotor is maintenance free. However for cleaning purposes it can be flushed out by
compressed air. A rotor cleaning procedure requires special knowledge, for this reason it is
recommended to call the manufacturer's representative for assistance. The rotor bearing and the
rotor surface should be checked once a year.
11

R
www.danvex.fi 12
Motors
The motors are maintenance free.
It is required to check the motors once a year or in case of abnormal sound.
Heater
The regeneration heater is maintenance free, however twice a year it should be checked for
mechanical damages.
Rotor belt
It is required to carry out regular inspections of the belt tension.
Seals
It is required to carry out regular inspection of the seals for damage and dust contamination.
Transportation
Please observe the following rules of the dehumidifier transportation and storage:
Upon delivery it is required to check the dehumidifier for transportation damages.
The dehumidifier should be protected from rain and snow.
The dehumidifier should always be in upright condition.
It is not allowed to put heavy objects on the dehumidifier.
Rotor drive motor 1
Name Number per
dehumidifier
Condenser 1
Belt pulley 1
Rotor drive belt 1
Belt tensioner 1
Dehumidified air fan 1
Regeneration air fan 1
Heater 1
Rotor 1
Parts list
Table 3

R
www.danvex.fi
13
Attachment

R
www.danvex.fi 14

R
www.danvex.fi
15

Warranty obligations
DanVex warrants that all the equipment parts will answer the technical requirements for 12
months from the date of delivery (warranty period).
The warranty does not cover wearable parts such as filters. The warranty covers the defects in
workmanship and materials.
During the warranty period DanVex repairs and replaces the part having a defect of material or an
manufacturing error.
DanVex completely fulfills its warranty obligations when it supplies the Customer a repaired or a
spare part.
Parts repair or replacement does not result in the warranty period extension.
The parts and components replaced under the warranty belong to DanVex.
DanVex or its distributor upon DanVex request has a right to inspect the defective parts and to
check the correctness of the warranty claim.
Warranty repair execution conditions:
The damage occurred during the equipment normal operation. All recommendations and
instructions of the manufacturer concerning the equipment installation, operation and
maintenance were observed. Only original parts and materials were used for the equipment
maintenance and repair.
R
www.danvex.fi 16

Table of contents
Other DanVex Dehumidifier manuals

DanVex
DanVex AD-200 User manual

DanVex
DanVex DEH-3K User manual

DanVex
DanVex AD-800 Operating instructions

DanVex
DanVex DEH-1700P User manual

DanVex
DanVex DEH-1700wp User manual

DanVex
DanVex AD-200 User manual

DanVex
DanVex DEH-1600i User manual

DanVex
DanVex DEH-900i User manual

DanVex
DanVex DEH-600wp User manual

DanVex
DanVex DD Series User manual
Popular Dehumidifier manuals by other brands

AHT
AHT 20-350 User maintenance guide

International Refrigeration Products
International Refrigeration Products DH470 user manual

Royal Sovereign
Royal Sovereign BDH-550 owner's manual

HOMCOM
HOMCOM 821-022V70 Assembly instruction

Whirlpool
Whirlpool BHDH2500AS1 Use & care guide

air&me
air&me ROHAN user manual