Deif AGC 200 User manual

AGC 200 Advanced Gen-set Controller
OPERATOR’S MANUAL
Display readings
Push-button functions
Alarm handling
Log list
Document no.: 4189340607B
SW version 3.5X.X or later

AGC 200 Operator’s Manual
DEIF A/S Page 2 of 22
Table of contents
1. ABOUT THIS DOCUMENT....................................................................................................3
GENERAL PURPOSE......................................................................................................................3
INTENDED USERS..........................................................................................................................3
CONTENTS/OVERALL STRUCTURE..................................................................................................3
2. WARNINGS AND LEGAL INFORMATION ...........................................................................4
LEGAL INFORMATION AND RESPONSIBILITY.....................................................................................4
ELECTROSTATIC DISCHARGE AWARENESS.....................................................................................4
SAFETY ISSUES............................................................................................................................4
DEFINITIONS ................................................................................................................................4
UL APPLICATIONS.........................................................................................................................4
3. AGC 200 VARIANTS..............................................................................................................5
ISLAND,AGC 212/222/232/242...................................................................................................5
AUTOMATIC MAINS FAILURE,AGC 213/233...................................................................................5
MAINS,AGC 245.........................................................................................................................6
MAINS AND TIE BREAKER,AGC 246..............................................................................................6
BUS TIE BREAKER,AGC 244.........................................................................................................7
4. DISPLAY PUSH-BUTTONS AND LEDS ...............................................................................8
PUSH-BUTTON FUNCTIONS............................................................................................................8
LED FUNCTIONS.........................................................................................................................11
5. DISPLAY AND MENU STRUCTURE...................................................................................13
LCD DISPLAY.............................................................................................................................13
MENU STRUCTURE......................................................................................................................13
STATUS LINE TEXT......................................................................................................................15
RUNNING MODES........................................................................................................................20
6. ALARM HANDLING AND LOG LIST...................................................................................21
ALARM HANDLING .......................................................................................................................21
LOG LIST....................................................................................................................................22

AGC 200 Operator’s Manual
DEIF A/S Page 3 of 22
1. About this document
General purpose
This document is the Operator’s Manual for DEIF’s Advanced Gen-set Controllers, the AGC 200
series. The document mainly includes general product information, display readings, push-
button and LED functions, alarm handling descriptions and presentation of the log list.
The general purpose is to give the operator important information to be used in the daily
operation of the unit.
Intended users
This Operator’s Manual is mainly intended for the daily user. On the basis of this document, the
operator will be able to carry out simple procedures such as start/stop and control of the
generator set.
Contents/overall structure
The document is divided into chapters, and in order to make the structure simple and easy to
use, each chapter will begin from the top of a new page.
Please make sure to read this handbook before working with the Multi-line 2
controller and the gen-set to be controlled. Failure to do this could result in
damage to the equipment or human injury.

AGC 200 Operator’s Manual
DEIF A/S Page 4 of 22
2. Warnings and legal information
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt
about how to install or operate the generator set controlled by the unit, the company responsible
for the installation or the operation of the set must be contacted.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
UL applications
These flat surface panel-mounted controllers are intended to be used in Listed Generator
Assemblies where the suitability of the combination has been determined by Underwriters
Laboratories.
These devices have been evaluated for fire and shock only. The accuracy and/or reliability of the
voltage regulating function have not been evaluated. Metering, monitoring, protection and signalling
functions have not been evaluated.
The notes provide general information which will be helpful for the reader to
bear in mind.
The warnings indicate a potentially dangerous situation which could result in
death, personal injury or damaged equipment, if certain guidelines are not
followed.
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.

AGC 200 Operator’s Manual
DEIF A/S Page 5 of 22
3. AGC 200 variants
Island, AGC 212/222/232/242
Automatic mains failure, AGC 213/233

AGC 200 Operator’s Manual
DEIF A/S Page 6 of 22
Mains, AGC 245
Mains and tie breaker, AGC 246

AGC 200 Operator’s Manual
DEIF A/S Page 7 of 22
Bus tie breaker, AGC 244

AGC 200 Operator’s Manual
DEIF A/S Page 8 of 22
4. Display push-buttons and LEDs
Push-button functions
The display unit holds a number of push-button functions which are described below.
Shifts the display to show the alarm list.
Resets horn output.
Tools. The tools are a number of windows for commissioning as well as some
special settings which are not accessible via the PC utility software. Please refer
to the Designer’s Reference Handbook for details.
Shifts the display to viewing of measured values. There are 20 different views.
Scroll through the views using the or button.
Shifts the display to show the event and alarm list. There are four lists to select
from: Event log, alarm log, battery test log and engine interface alarm log (CAN
J1939 engine controller interface).
Parameter list selection.
Moves the cursor left for manoeuvring in the menus.
Increases the value of the selected setpoint (in the setup menu). In the daily use
display, this button function is used for scrolling the displaying of generator
values.
Selects the entry in the display.
Decreases the value of the selected setpoint (in the setup menu). In the daily
use display, this button function is used for scrolling the displaying of generator
values.
Moves the cursor right for manoeuvring in the menus.
ESC Jumps one step backwards in the menu (to previous display or to the entry
window).
START Start of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
STOP Stop of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
Manual activation of close breaker sequence if ‘SEMI-AUTO’ is selected.
Manual activation of open breaker sequence if ‘SEMI-AUTO’ is selected.
AUTO Selects AUTO running mode.
SEMI Selects SEMI-AUTO running mode. Push-button commands are used for
start/stop, etc.

AGC 200 Operator’s Manual
DEIF A/S Page 9 of 22
MAN Selects MANUAL running mode. Like SEMI, but regulators are OFF.
OFF Selects OFF mode. All functions except protections are switched off.
TEST Selects TEST RUN of the generator.
Lamp test.

AGC 200 Operator’s Manual
DEIF A/S Page 10 of 22
The push-buttons are placed as follows:
AUTO mode.
MANUAL mode.
SEMI-AUTO mode.
OFF mode.
TEST mode.
Lamp test.
Close/open MB.
START:
Start of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
STOP:
Stop of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
View of measured values.
Log lists.
Alarm list.
Close/open GB.
Parameter settings.
Tools.
Silence horn.
Enter.
Step backwards.

AGC 200 Operator’s Manual
DEIF A/S Page 11 of 22
LED functions
The display unit holds 10 LED functions. Dependent on the situation, the colour of the LEDs is
green, red or a combination.
Alarm: LED flashing indicates that unacknowledged alarms are present.
LED steady light indicates that ALL alarms are acknowledged, but some are still
present.
Power: LED indicates that the auxiliary supply is switched on. If it is green, the AGC 200
is operational. If it is red, the self-check has failed.
Run: LED indicates that the generator is running.
Hz/V OK: LED green light indicates that the voltage/frequency is present and OK.
GB ON: LED indicates that the generator breaker is closed.
MB ON: LED indicates that the mains breaker is closed.
Mains OK: LED is green if the mains is present and OK.
LED is red at a mains failure.
LED is flashing green when the mains returns during the ‘mains OK delay’ time.
AUTO: LED indicates that auto mode is selected.
MAN: LED indicates that manual mode is selected.
SEMI: LED indicates that SEMI AUTO mode is selected.
OFF: LED indicates that OFF mode is selected.
Annunciator: 4 x LEDs with selectable indication function. Selection is made in M-logic.

AGC 200 Operator’s Manual
DEIF A/S Page 12 of 22
The display LEDs indicate the following:
Mains breaker ON.
Manual mode.
Alarm.
Generator breaker ON.
Generator frequency/voltage.
Engine running.
Mini-annunciator.
AUTO mode.
SEMI-AUTO.
OFF mode.

AGC 200 Operator’s Manual
DEIF A/S Page 13 of 22
5. Display and menu structure
LCD display
The display is a backlit LCD graphical display. The display light intensity, LED indication and
contrast can be adjusted from menu 9150.
Basically, all measured and calculated values can be read in the display. These may be selected
via the PC utility software (USW).
Menu structure
The display includes two menu systems which can be used without password entry:
View menu system
This is the commonly used menu system. 20 windows are configurable and can be
entered by using the arrow push-buttons.
Setup menu system (not commonly used by the operator)
This menu system is used to set up the unit, and if the operator needs detailed
information that is not available in the view menu system.
Changing of parameter settings is password protected.
Entry window
When the unit is powered up, an entry window appears. The entry window is the first window of
the view menu system. It can always be accessed by pressing the BACK push-button three
times.
For selection of values, please refer to the Designer’s Reference Handbook.
MAINS FAILURE
U-Supply 24.1 V
G 0.00I PF 0 kW
G 0kVA 0 kVAr
Energy Total 0 kWh
Run absolute 0 hrs

AGC 200 Operator’s Manual
DEIF A/S Page 14 of 22
View menu
The view menu is the daily use menu for the operator.
First display line
Operational status.
Second, third and fourth display lines
Measurements.
Fifth and sixth display lines
Produced kWh and running hours.
Display view indicator
Placed over the selected view button.
In the view menu, various measured values are displayed.
View menu navigation
Display of measured values according to the selections made during configuration.
The views contain up to 20 different windows which can be selected using the and push-
buttons located on the right hand side of the display.
For detailed information about configuration, please see the Designer’s
Reference Handbook.
MAINS FAILURE
U- supply 24.1 V
G 0.00I PF 0 kW
G 0kVA 0 kVAr
Energy Total 0 kWh
Run absolute 0 hrs
1/20

AGC 200 Operator’s Manual
DEIF A/S Page 15 of 22
Status line text
This table explains the different messages.
Status text Condition Comment
BLOCK Block mode is activated
SIMPLE TEST Test mode is activated
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min Test mode is activated and test
timer counting down
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN Gen-set stopped or running and
no other action taking place
ISLAND SEMI
READY ISLAND AUTO Gen-set stopped in Auto
ISLAND ACTIVE Gen-set running in Auto
AMF MAN Gen-set stopped or running and
no other action taking place
AMF SEMI
READY AMF AUTO Gen-set stopped in Auto
AMF ACTIVE Gen-set running in Auto
FIXED POWER MAN Gen-set stopped or running and
no other action taking place
FIXED POWER SEMI
READY FIXED P AUTO Gen-set stopped in Auto
FIXED POWER ACTIVE Gen-set running in Auto
PEAK SHAVING MAN Gen-set stopped or running and
no other action taking place
PEAK SHAVING SEMI
READY PEAK SHAV AUTO Gen-set stopped in Auto
PEAK SHAVING ACTIVE Gen-set running in Auto
LOAD TAKEOVER MAN Gen-set stopped or running and
no other action taking place
LOAD TAKEOVER SEMI
READY LTO AUTO Gen-set stopped in Auto
LTO ACTIVE Gen-set running in Auto
MAINS P EXPORT MAN Gen-set stopped or running and
no other action taking place
MAINS P EXPORT SEMI
READY MPE AUTO Gen-set stopped in Auto
MPE ACTIVE Gen-set running in mains power
export mode
DG BLCKD FOR START Generator stopped and active
alarm(s) on the generator
GB ON BLOCKED Generator running, GB open and
an active ‘Trip GB’ alarm
SHUTDOWN OVERRIDE The configurable input is active
ACCESS LOCK The configurable input is
activated, and the operator tries
to activate one of the blocked
keys
GB TRIP EXTERNALLY Some external equipment has
tripped the breaker An external trip is logged in
the event log
MB TRIP EXTERNALLY Some external equipment has
tripped the breaker An external trip is logged in
the event log
IDLE RUN The ‘Idle run’ function is active
The gen-set will not stop, until a
timer has expired
IDLE RUN ###.#min The timer in the ‘Idle run’
function is active

AGC 200 Operator’s Manual
DEIF A/S Page 16 of 22
Status text Condition Comment
COMPENSATION FREQ. Compensation is active The frequency is not at the
nominal setting
Aux. test ##.#V ####s Battery test activated
DELOAD Decreasing the load of the gen-
set in order to open the breaker
START DG(s) IN ###s The start gen-set setpoint is
exceeded
STOP DG(s) IN ###s The stop gen-set setpoint is
exceeded
START PREPARE The start prepare relay is
activated
START RELAY ON The start relay is activated
START RELAY OFF The start relay is deactivated
during the start sequence
MAINS FAILURE Mains failure and mains failure
timer expired
MAINS FAILURE IN ###s Frequency or voltage
measurement is outside the
limits
The timer shown is the
mains failure delay
Text in mains units
MAINS U OK DEL ####s Mains voltage is OK after a
mains failure The timer shown is the
mains OK delay
MAINS f OK DEL ####s Mains frequency is OK after a
mains failure The timer shown is the
mains OK delay
Hz/V OK IN ###s The voltage and frequency of
the gen-set is OK When the timer runs out it
is allowed to operate the
generator breaker
COOLING DOWN ###s Cooling down period is activated
GEN-SET STOPPING This info is shown when cooling
down has finished
EXT. STOP TIME ###s
PROGRAMMING LANGUAGE This info is shown if the
language file is downloaded
from the PC utility software
Generator is synchronising The dot marks the actual
generator phase angle
position in the
synchronisation
When the dot is at 12
o’clock, the generator and
busbar are in synchronism
The second dot indicates
when the relay output for
the generator or mains
breaker is activated
Generator running too slow
during synchronising
Generator running too fast
during synchronising
EXT. START ORDER A planned AMF sequence is
activated There is no failure on the
mains during this sequence

AGC 200 Operator’s Manual
DEIF A/S Page 17 of 22
Status text Condition Comment
SELECT GEN-SET MODE Power management has been
deactivated and no other gen-
set mode has been selected
AGC 24x only
QUICK SETUP ERROR Quick setup of the application
failed
MOUNT CAN CONNECTOR Connect the power management
CAN line
ADAPT IN PROGRESS The AGC 200 is receiving the
application that it has just been
connected to
SETUP IN PROGRESS The new AGC is being added to
the existing application
SETUP COMPLETED Successful update of the
application in all AGC units
REMOVE CAN CONNECTOR Remove the power management
CAN lines
RAMP TO #####kW The power ramp is ramping in
steps, and the next step that will
be reached after the timer has
expired will be displayed
DERATED TO #####kW Displays the ramp down setpoint

AGC 200 Operator’s Manual
DEIF A/S Page 18 of 22
Texts only related to power management (AGC 24x variants only)
Status text Condition Comment
DG unit
BLACKOUT ENABLE This information is shown if a
CAN failure is present in a
power management application
UNIT STANDBY If redundant mains units are
present, this message is shown
on the redundant unit
DELOADING BTB XX DG units are load sharing
asymmetrically to deload BTB
XX dividing 2 sections in an
application
BTB XX DIVIDING SEC. BTB XX is dividing 2 sections in
an application
SYNCHRONISING TB XX TB XX is synchronising
SYNCHRONISING MB XX MB XX is synchronising
SYNCHRONISING BTB XX BTB XX is synchronising
Mains unit
UNIT STANDBY If redundant mains units are
present, this message is shown
on the redundant unit
TB TRIP EXTERNALLY Some external equipment has
tripped the breaker An external trip is logged in
the event log
BTB unit
DIVIDING SECTION A BTB unit is dividing 2 sections
in an application
READY AUTO OPERATION BTB unit in Auto and ready for
breaker operation (no active
‘BTB trip’ alarm)
SEMI OPERATION BTB unit in Semi
AUTO OPERATION BTB unit in Auto, but not ready
for breaker operation (active
‘BTB trip’ alarm)
BLOCKED FOR CLOSING Last open BTB in a ring bus
BTB TRIP EXTERNALLY Some external equipment has
tripped the breaker An external trip is logged in
the event log
All units
BROADCASTING APPL. # Broadcast of an application
through the CAN line Broadcasts one of the four
applications from one unit
to the other AGCs in the
power management
system
RECEIVING APPL. # AGC 200 receiving an
application
BROADCAST COMPLETED Successful broadcast of an
application
RECEIVE COMPLETED Application received successfully
BROADCAST ABORTED Broadcast terminated
RECEIVE ERROR Application is not received
correctly

AGC 200 Operator’s Manual
DEIF A/S Page 19 of 22
View menu example
View reading (20 views) Log reading Parameter settings
Press Press
Press Press Press
Press
The scrollbar
indicates that more
readings are
available below
MAINS FAILURE
U- supply 24.1 V
G 0.00I PF 0 kW
G 0kVA 0 kVAr
Energy Total 0 kWh
Run absolute 0 hrs
1/20
MAINS FAILURE
Event log .
Alarm log
Battery test log
MAINS FAILURE
Setup menu
1000 Protection .
2000 Synchronisation
2500 Regulation
3000 Binary input
MAINS FAILURE
P 0kW 0 %
Q 0kVAr 0 %
S 0kVA 0 %
Energy Total 0 kWh
Run absolute 0 hrs
MAINS FAILURE
MAINS FAILURE .
Wed Sept 23 13:36:23
MB OFF
Wed Sept 23 13:36:33
MAINS FAILURE
Setup menu
1000 G –P> 1 .
1010 G –P> 2
1030 G I> 1
1040 G I> 2
MAINS FAILURE
1000 G –P> 1
Setpoint: -9.0% .
Timer: 10.2s
Output A: Not used
Output B: Not used

AGC 200 Operator’s Manual
DEIF A/S Page 20 of 22
Running modes
The running modes are selected using the buttons as follows:
Mode Description
SEMI - The display push-buttons (START, STOP, GB ON, GB OFF) are active and can
be used by the operator.
- The regulators are also active, i.e. the speed control will bring the generator to
nominal speed upon start.
- When pushing a breaker button for closing, the AGC 200 will synchronise (if
allowed) the breaker. When the breaker closes, the controls stop.
TEST - The unit will start the generator, carry out the test sequence (predefined time
period) and stop the generator again. Subsequently, the generator will return to
AUTO or SEMI-AUTO mode. The mains breaker will remain closed, and the
generator breaker will remain open. NOTE: The test running can be: Simple test:
Starting the gen-set without closing the GB; Load test: Parallel to the mains and
take load to a predefined value; Full test: Transfer the load to the gen-set and
open the MB.
AUTO - The unit will automatically carry out the control type selected (AMF, fixed power,
etc.).
- The display control push-buttons (START, STOP, GB ON, GB OFF) are
disabled.
- If the selected running mode is fixed power, mains power export, load takeover
or island, timer start/stop (week watch) or binary input, then start/stop can be
used.
MAN - The display push-buttons (START, STOP) are active and can be used by the
operator.
- The regulators are not active, i.e. speed (and voltage) control has to take place
using external controls for generator speed and possibly generator voltage
control.
- The breakers will be able to open or close at any time. A synchronisation check
will always be performed to ensure safe closing of the breakers.
BLOCK - The unit will not be able to start. BLOCK mode can be selected during standstill
and the password is needed to leave BLOCK mode. If the BLOCK mode is
selected while the gen-set is running, the mode will have no effect until the gen-
set is stopped. To select another mode after the BLOCK mode, the password
must be entered.