Installation/operation instructions ADL-111Q96/xxVDC
Page 7 of 7 4189330017B (UK)
The red LED indicator marked FAULT is illuminated, if an insulation error below the
set point is detected.
Response time
The table below illustrates the response time for the different instrument types with
max. leakage capacitor set to 1μF and 20μF respectively.
Type
Setting ADL-111Q96/24VDC ADL-111Q96/110VDC ADL-111Q96/220VDC
1μF 2.0s 3.2s 5.0s
20μF 11.0s 20.0s 40.0s
Fuses
Recommended fuse for aux. supply (X1, X2) max. 2A.
Commissioning
On delivery, the ADL-111Q96/xxVDC is set to 1μF as max. leakage capacitor, and the
relay function is set to NE. If the actual leakage capacitor is higher than 1μF, the ADL-
111Q96/xxVDC will indicate an insulation error. The value of this insulation error
depends on the actual size of the leakage capacitor. To avoid this, set the S1 switch
to position 20μF. If the ADL-111Q96/xxVDC is supplied from the IT network under
supervision, an alarm will occur in case of disconnection of the IT network. If this is to
be prevented, then set the S1 switch in position ND and change the wiring on the
relay contact according to the information in the chapter “Installation”.
Technical specifications
Please see the data sheet, document no. 4921230021.
Errors and changes excepted
If the installation is to be tested by means of a high-voltage
"MEGGER", the wire to the ADL-111Q96/xxVDC at terminal "L-" must
be disconnected before testing is carried out. Omitting this may result
in damage to the ADL-111Q96/xxVDC. Besides, the insulation test will
be affected by the built-in DC voltage generator impedance (Ri).
If the voltage exceeds the max. allowable value, e.g. 31.2V for the 24V
version, the indication on the instrument will be infinite and the green
LED starts flashing. The same indication will occur in situations where
the insulation error is fluctuating. The infinite indication on the
instrument and the flashing LED will remain, until a correct mean value
of the fluctuating insulation error can be determined.
A power-up reset is needed every time the setting 1μF or 20μF is
changed. It is not needed if only the relay function is changed.