manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Delta
  6. •
  7. Accessories
  8. •
  9. Delta DVP-EH Series User manual

Delta DVP-EH Series User manual

http://www.delta.com.tw/products/plc.asp
DVP-EH
DVP04PT-H
Platinum Temperature Sensors
Instruction Sheet
1 WARNING
Please carefully read this instruction thoroughly prior to use the DVP04PT-H.
In order to prevent electric shock, do not touch the terminals or conduct any maintenance while
power to the PLC is ON. Do NOT open the PLC. Only qualified personel or Delta staff is allowed
to conduct any internal electrical work on the PLC.
This is an OPEN-TYPE device, and was certified to meet the IEC 61131-2 (UL 508) safety
requirements when installed in an enclosure.
The DVP04PT-H must be kept under the environment away from high temperatures, high
humidity, exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles.
Do not apply AC power to any of the input/output terminals, or it may damage the DVP04PT-H.
Make sure that the DVP04PT-H is properly grounded , to prevent any electromagnetic noise.
Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC.
Please keep the wires as short as possible when connecting the RTD to PLC, and keep power
wires as far away as possible from I/O wires to prevent noise interference.
2 INTRODUCTION
2.1 Model Explanation and Peripherals
 Thank you for choosing DELTA DVP PLC Series. DVP04PT-H allows the connection of four
platinum temperature sensors (PT100 3-WIRE 100 Ω3850 PPM/°C (DIN 43760 JIS
C1604-1989)). The DVP-PLC EH MPU converts the sensors input into a 14 bit digital signal, and
then be manipulated by using TO and FROM instructions in the ladder logic program. There are
49 Controlled Registers (CR, each register has 16 bits) in each module.
 Software version DVP04PT-H platinum temperature sensors can be updated via RS-485
communication.
 DVP04PT-H displays both Centigrade and Fahrenheit. The input resolution for Centigrade is 0.1
degrees and for Fahrenheit is 0.18 degrees.
 Nameplate Explanation
0.1 C or 0.18 F
20.4VDC ~ 28.8VDC
VX.XX 04PT-H0T4250003
PLC model
Input Power Supply Spec.
Analog Input / Outp ut Module Spec.
Barcode
 Model Explanation
Model Serial Number
Product Series
Input+Output point
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors(PT-100)
TC: Thermocouple sensors(Type J/K)
S: for SS series MPU
P: for EP series MPU
H: for EH ser ies MPU
Production week
Production place (Taoyuan)
Production year (2004)
Production Model
XA: A/D , D/A Functions
RT: Resistor Thermocouple
HC: High speed count input module
PU: single axis positioning unit
2.2 Product Profile and Outline
1. DIN rail track (35mm) 6. Terminals
2. Mounting hole for wire to connect extension
unit/extension module 7. Mounting hole
3. Model name 8. Terminal layout
4. Indicator for power, error and run status 9. Mounting port to connect extension
unit/extension module
5. DIN rail clip
2.3 External wiring
PT100
PT100
CH1
CH4
1mA
DC/ DC
5V
AG
+15V
-15V
AG
AG
AG
24+
24-
FG
I-
L-
L+
FG
I-
L-
L+
Converter
System
Class 3 Grounding
(100 of less)
terminal of
power module
Shielded*1
*2
*3
1mA
Shielded*1
Grounding
Note 1: Use only the wires that are packed
with the temperature sensor (PT 100)
for analog input and separate from
other power line or any wire that may
cause noise. Please use 3wire for PT
100.
Note 2: Terminal FG is a ground location for
noise suppression.
Note 3: Please connect power supply
module terminal and DVP04PT-H
platinum temperature sensors module
terminal to system earth ground or
connect it to machine cover.
Warning: DO NOT connect wires to the No
Connection (●) terminals.
3 STANDARD SPECIFICATIONS
3.1 Function Specifications
Platinum Temperature Module
(04PT) Centigrade (°C) Fahrenheit (°F)
Power supply voltage 24 VDC (20.4VDC~28.8VDC) (–15%~+20%)
Analog input channel 4 channels per module
Sensors type 3-WIRE PT100Ω3850 PPM/°C(DIN 43760 JIS C1604-1989)
Current excitation 1mA
Temperature input range -200°C~600°C -328°F~1112°F
Digital conversion range K-2000~K6000 K-3280~K11120
Resolution 14 bits (0.1°C) 14 bits (0.18°F)
Overall accuracy ±0.5% of full scale of 25°C(77°F), ±1% of full scale during 0~55°C
(32~131°F)
Response time 200 ms ×channels
Isolation Method Isolation between digital and analog circuitry. But no isolation
between channels.
Digital data format 2’s complement of 16-bit, (13 Significant Bits)
Average function Yes (CR#2~CR#5 may be set and the range is K1~K4096)
Self diagnostic function Upper bound and lower bound detection per channel
Communication mode (RS-485)
Yes, either ASCII or RTU modes, communication rate can be
4800 /9600 /19200 /38400 /57600 /115200. Communication
format of ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8
E 1). When connecting to PLC MPU in series, RS-485 can’t be
used. The RS-485 is disabled when the DVP04PT-H is connected
in series to an MPU (use the RS485 on MPU).
Connection to a DVP-PLC MPU
in series
When DVP04PT-H modules are connected to an MPU, the
modules are numbered from 0 – 7. 0 is the closest and 7 is the
furthest to the MPU. 8 modules is the max and they do not occupy
any digital I/O points of the MPU.
3.2 Other Specification
Power Specification
Maximum Power Consumption 2W at 24 VDC (20.4VDC~28.8VDC) (-15 % ~ + 20%)
Environment Condition
Environment Condition Follow the DVP-PLC MPU.
Static Electricity Prevention All places between terminals and ground comply with the spec
4 CR (CONTROLLED REGISTER)
DVP04PT-H platinum temperature sensors Explanation
CR
No.
RS-485
Parameter
address
Latched Register name b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0 H 4064 ○R Model type System used, data length is 8bits (b7~b0). DVP04PT-H model code = H 0402
#1 Reserved
#2 H 4066 ○R/W CH1 average number
#3 H 4067 ○R/W CH2 average number
#4 H 4068 ○R/W CH3 average number
#5 H 4069 ○R/W CH4 average number
The number piece of readings used for the calculation of “average” temperature
on channels CH1~CH4.
Setting range is K1~K4096 and factory setting is K10.
#6 H 406A ╳R CH1 average degrees(°C)
#7 H 406B ╳R CH2 average degrees(°C)
#8 H 406C ╳R CH3 average degrees(°C)
#9 H 406D ╳R CH4 average degrees(°C)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees C)
#10~ #11 Reserved
#12 H 4070 ╳R CH1 average degrees(°F)
#13 H 4071 ╳R CH2 average degrees(°F)
#14 H 4072 ╳R CH3 average degrees(°F)
#15 H 4073 ╳R CH4 average degrees(°F)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees F)
#16~ #17 Reserved
#18 H 4076 ╳R Present temperature of
CH1 (°C)
#19 H 4077 ╳R Present temperature of
CH2 (°C)
#20 H 4078 ╳R Present temperature of
CH3 (°C)
#21 H 4079 ╳R Present temperature of
CH4 (°C)
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C)
#22~ #23 Reserved
#24 H 407C ╳R Present temperature of
CH1 (°F)
#25 H 407D ╳R Present temperature of
CH2 (°F)
#26 H 407E ╳R Present temperature of
CH3 (°F)
#27 H 407F ╳R Present temperature of
CH4 (°F)
Present temperature of channels CH1~CH4. (unit: 0.1degrees F)
#28~ #29 Reserved
#30 H 4082 ╳R Error status Data register stores the error status. Refer to the fault code chart for details.
#31 H 4083 ○R/W Communication address
setting
RS-485 communication address.
Setting range is 01~255 and factory setting is K1
#32 H 4084 ○R/W Communication baud rate
setting
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).
Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec).
b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec).
b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec).
b5: 115200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low bit and high bit of CRC code (RTU mode only)
b15: RTU mode.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Definition of ERR
LED
CH4 CH3 CH2 CH1
#33 H 4085 ○R/W Reset to factory setting
Example: Setting of CH1
1. b0 Reserved
2. b1 Reserved
3. b2: Set to 1 and PLC will be reset to factory settings.
Definition of ERR LED: b12~b15=1111(factory settings)
1. b12 corresponds to CH1: when b12=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
2. b13 corresponds to CH2: when b13=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
3. b14 corresponds to CH3: when b14=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
4. b15 corresponds to CH4: when b15=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
#34 H 4086 ○R Software version Display software version in hexadecimal. Example: H 010A = version 1.0A.
#35~#48 System used
○means latched.
╳means not latched.
R means read data by using FROM instruction or RS-485.
W means write data by using TO instruction or RS-485.
Explanation:
1. CR#0: The PLC model type.
2. CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 are reserved.
3. CR#2 ~ CR#5: Used to set the number piece of input readings used for the average temperature
calculation. The available range is K1~K4096 and factory setting is K10.
4. CR#6 to CR#9: The average temperature (°C). Temperature is calculated by averaging multiple
pieces temperature readings. Example: If CR#2 is 10, the temperature in CR#6 will be the
average of the last 10 readings on CH1.
5. CR#12 to CR#15: The average temperature (°C). Temperature is calculated by averaging multiple
pieces temperature readings. Example: If CR#2 is 10, the temperature in CR#12 will be the
average of the last 10 readings on CH1.
6. CR#18 ~ CR#21: display the present temperature (°C) of CH1~CH4 input signal.
Unit: mm
7. CR#24 ~ CR#27: display the present temperature (°F) of CH1~CH4 input signal.
8. CR#30 is the fault code register. Refer to the chart below.
Fault description Content b15~b8 b7 b6 b5 b4 b3 b2 b1 b0
Power source abnormal K1(H1) 0 0 0 0 0 0 0 1
Analog input value error K2(H2) 0 0 0 0 0 0 1 0
Setting mode error K4(H4) 0 0 0 0 0 1 0 0
Offset/Gain error K8(H8) 0 0 0 0 1 0 0 0
Hardware malfunction K16(H10) 0 0 0 1 0 0 0 0
Digital range error K32(H20) 0 0 1 0 0 0 0 0
Average times setting error K64(H40) 0 1 0 0 0 0 0 0
Instruction error K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code has the corresponding bit (b0~b7). Two or more faults may happen at the
same time. 0 means normal and 1 means fault happened.
9. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1.
10. CR#32: RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600 and 115200.
b0:4800bps, b1:9600bps (factory setting), b2:19200bps, b3:38400 bps, b4:57600 bps, b5:115200
bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15=0: ASCII mode, b15=1: RTU mode. Communication format for ASCII mode is 7Bit, even bit, 1
stop bit (7 E 1), while for RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
11. CR#33: b0~b11: Used to reset the settings of CH1~CH4 to factory defaults.
b12~b15: defined the ERR LED, factory setting is b12~b15=1111.
12. CR#34: software version.
13. CR#35~ CR#48: Reserved for internal system use.
14. The corresponding parameters address H4064~H4095 of CR#0~CR#48 are provided for users to
read/write data via RS-485 communication.
A. Baud rate can be 4800, 9600, 19200, 38400, 57600, 115200bps.
B. MODBUS communication protocol can be either ASCII or RTU mode. Communication format
for ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1), while for RTU mode is 8Bit, even bit, 1
stop bit (8 E 1).
C. Function code: 03H read data from register.
06H write 1pcs WORD into register.
10H write multiple WORD into register.
5 TEMPERATURE/DIGITAL CHARACTERISTIC CURVE
Temperature mode: (Centigrade)
+6000
+3000
-2000
+600-200
Digital Output
Temperature Input
C C
Temperature mode: (Fahrenheit)
+11120
+5560
-3280
+1112
-328
Digital Output
Temperature Input
F F
6 INITIAL PLC START-UP
 LED display:
1. Upon power-up, the ERROR LED will light on for 0.5 seconds the POWER LED will light
on continuously.
2. POWER LED on and ERROR LED off means No Error.
Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power
supply goes above 19.5V.
3. DVP04PT-H is connected to PLC MPU in series = RUN LED on MPU will be lit and A/D
LED or D/A LED should blink.
4. After receiving the first RS-485 instruction the A/D LED or D/A LED will blink.
5. If the input or output exceeds the upper or lower bounds, then the ERROR LED will blink.
 Example:
M1000
FROM K0
= H402 D0
TO K0
FROM K0
FROM K0
FROM K0
FROM K0
FROM
M1002
Explanation:
 Read the model type of extension module K0 (should be H0402 for DVP04PT-H model type).
 The average values of CH1~CH4 saved in D10~D13 are written into CR#2~CR#5.
 For DVP04PT-H model. The read average temperature (°C) of CH1~CH4 (4 data) from CR#6~CR#9
and saved to D20~D23.
 The read average temperature (°F) of CH1~CH4 (4 data) from CR#12~CR#15 and saved into
D24~D27.
 The read present temperature (°C) of CH1~CH4 (4 data) from CR#18~CR#21 and saved into
D30~D33.
 The read present temperature (°F) of CH1~CH4 (4 data) from CR#24~CR#27 and saved into
D34~D37.
7 RELATED INSTRUCTIONS EXPLANATION
API Applicable model
ES EP EH
78
D FROM P
Read special module CR
data 
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1
¼¼
m2
¼¼
D ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
n
¼¼
 Note: The usage range of operand m1is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
ES series model doesn’t support pulse
execution instruction (FROMP, DFROMP).
16-bit instruction (9 STEPS)
FROM Continuous
execution FROMP Pulse
execution
32-bit instruction (17 STEPS)
DFROM Continuous
execution DFROMP Pulse
execution
 Flag: When M1083 On, it allows
to enable interrupt during
FROM/TO. Refer to the
below for detail.
Command
Explanation
 : the module number you are probing. : the number of Controlled Registers
to be read. : the data register location for storing data. : the number of CRs
to read at one time.
 DVP-series PLC uses this instruction to read CR data of each special module.
 : When assigning bit operand, K1~K4 are used for 16-bit and K5~K8 are used
for 32-bit.
 Please refer the following footnote for calculating of special module number.
Program
Example
 Read the content of CR#24 and CR#25 of module#0 and save it into D0 and D1
when n=2.
 Instruction will be executed when X0=ON. However, nothing will occur and the
stored data has no change when X0=OFF.
X0
FROM K0
API Applicable model
ES EP EH
79 DTO P
Special module CR
data write 
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1
¼¼
m2
¼¼
S
¼¼¼¼¼¼¼¼ ¼ ¼ ¼
n
¼¼
 Note: The usage range of operand m1is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
ES series does not support pulse execution
instruction (TOP, DTOP)
16-bit instruction (9 STEPS)
TO Continuous
execution TOP Pulse
execution
32-bit instruction (17 STEPS)
DTO Continuous
execution DTOP Pulse
execution
 Flag: When M1083=On, it
allows to insert interrupt
during FROM/TO. Refer to
following for detail.
Command
Explanation
 : the module number you are probing. : the number of Controlled
Registers to be written to. : the data to write. : the number of CR to be
written to in one time.
 DVP-series PLC uses this instruction to write data to Controlled Registers of
special modules.
 : When assign the bit operand, K1~K4 are used for 16-bit and K5~K8 are
used for 32-bit.
Program
Example
 Using the 32-bit instruction DTO. The program will write D11 and D10 into CR#3
and CR#2 of special module#0. DTO only allows one group of data to be written at
a time (n=1).
 The instruction is executed when X0=ON. Nothing will occur and the stored data
will have no change when X0=OFF.
X0
DTO K0
Footnote
 The rules for adding multiple special modules to a Main Processing Unit:
 m1: The maximum number of special modules attached to an MPU is 8. The
module closest to the MPU is 0 and the module furthest from the MPU is 7.
 m2: The number of Controlled Registers (CR) built in is 49. (#0~#48).
 FROM/TO instruction read/write one CR at a time, while DFROM/DTO
instruction read/write two CR at a time. Example below:
Upper 16-bit Lower 16-bit
Assigned CR numer
(Access16-bit if n=2, or 32-bit if n=1. Same controlled registers are accessed).
D0
D1
D2
D3
D4
D5
D0
D1
D2
D3
D4
D5
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
Assigned
Equipment
Assigned
CR
Assigned
Equipment
Assigned
CR
16-bit command when n=6 32-bit command when n=3
 In ES series models, flag M1083 is not provided. When FROM/TO instruction is
executed, all interrupts (including external or internal interrupt subroutines) will be
disabled. All interrupts will be executed after FROM/TO instruction is completed.
Besides, FROM/TO instruction also can be executed in the interrupt subroutine.
 The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH
series models:
a. When M1083=Off, all interrupts (including external or internal interrupt
subroutines) will be disabled when FROM/TO instruction is executed. The
Interrupts will resumed after FROM/TO instruction complete. Please be
advised FROM/TO instruction can be executed in the interrupt subroutine.
b. When M1083=On, if an interrupt enable occurs while FROM/TO
instruction are executing, the interrupt FROM/TO instruction will be
blocked till the requested interrupt finish. Unlike M1080 off situation,
FROM/TO instruction cannot be executed in the interrupt subroutine.

Other manuals for DVP-EH Series

1

This manual suits for next models

1

Other Delta Accessories manuals

Delta 36-601 User manual

Delta

Delta 36-601 User manual

Delta PB-A1002 User manual

Delta

Delta PB-A1002 User manual

Delta BIESEMEYER 78-955 User manual

Delta

Delta BIESEMEYER 78-955 User manual

Delta DPB Series User manual

Delta

Delta DPB Series User manual

Delta ELEKTRA UV E-5 User manual

Delta

Delta ELEKTRA UV E-5 User manual

Delta AMBIS User manual

Delta

Delta AMBIS User manual

Delta AS-BF Series User manual

Delta

Delta AS-BF Series User manual

Delta dvp04pt-s User manual

Delta

Delta dvp04pt-s User manual

Delta RetroSign GR1 User manual

Delta

Delta RetroSign GR1 User manual

Delta Uno Sense S1649 User manual

Delta

Delta Uno Sense S1649 User manual

Delta DPA Series User manual

Delta

Delta DPA Series User manual

Delta high living GT-8000 User manual

Delta

Delta high living GT-8000 User manual

Delta GT-9000 User manual

Delta

Delta GT-9000 User manual

Delta LE-753112 User manual

Delta

Delta LE-753112 User manual

Delta GRX User manual

Delta

Delta GRX User manual

Delta SH-OP01 User manual

Delta

Delta SH-OP01 User manual

Delta DVP04TC-S User manual

Delta

Delta DVP04TC-S User manual

Delta DNS-14 User guide

Delta

Delta DNS-14 User guide

Delta 46-896 User manual

Delta

Delta 46-896 User manual

Delta VIS100-30G12D User manual

Delta

Delta VIS100-30G12D User manual

Delta 41319 Series User manual

Delta

Delta 41319 Series User manual

Delta PB-C1003 User manual

Delta

Delta PB-C1003 User manual

Delta DPA Series User manual

Delta

Delta DPA Series User manual

Delta LE-50637 User manual

Delta

Delta LE-50637 User manual

Popular Accessories manuals by other brands

Honeywell CTS-A Series installation instructions

Honeywell

Honeywell CTS-A Series installation instructions

Hobo WELL-CAP-02 installation instructions

Hobo

Hobo WELL-CAP-02 installation instructions

Ouster OS1-128 Hardware user manual

Ouster

Ouster OS1-128 Hardware user manual

Dynafit NEO User instructions

Dynafit

Dynafit NEO User instructions

rivacase VA2070 user manual

rivacase

rivacase VA2070 user manual

GE ve735am installation instructions

GE

GE ve735am installation instructions

Fife MAXCESS SE-26B operating instructions

Fife

Fife MAXCESS SE-26B operating instructions

Panasonic EZ-10 Series instruction manual

Panasonic

Panasonic EZ-10 Series instruction manual

La Crosse Technology TX8U instruction manual

La Crosse Technology

La Crosse Technology TX8U instruction manual

PCB Piezotronics U106B Installation and operating manual

PCB Piezotronics

PCB Piezotronics U106B Installation and operating manual

Froggit DP150 manual

Froggit

Froggit DP150 manual

Louroe Electronics AP-2 Installation and operating instructions

Louroe Electronics

Louroe Electronics AP-2 Installation and operating instructions

IKEA SOLBANA manual

IKEA

IKEA SOLBANA manual

ENSA ENSA-MS1 instruction manual

ENSA

ENSA ENSA-MS1 instruction manual

Philips HQ3 Specifications

Philips

Philips HQ3 Specifications

Schippers MS BWS Operation manual

Schippers

Schippers MS BWS Operation manual

ELEKTROBOCK BZ11 quick start guide

ELEKTROBOCK

ELEKTROBOCK BZ11 quick start guide

Outdoor Tech KODIAK 2.0 manual

Outdoor Tech

Outdoor Tech KODIAK 2.0 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.