manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Delta
  6. •
  7. Controllers
  8. •
  9. Delta DVP-EH User manual

Delta DVP-EH User manual

http://www.delta.com.tw/products/plc.asp
DVP-EH
DVP04PT-H
Platinum Temperature Sensors
Instruction Sheet
1 WARNING
Always read this manual thoroughly before using the DVP04PT-H.
In order to avoid electric shock, do not touch the terminals or conduct any maintenance while
power is applied to the PLC. Never open the PLC. Only qualified Delta personnel should conduct
any internal electrical work on the PLC.
This is an OPEN-TYPE device and is certified to meet the safety requirements of IEC 61131-2
(UL 508) when installed in an enclosure.
The DVP04PT-H must be placed in an environment away from high temperatures, high humidity,
exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles.
Do not apply AC power to any of the input/output terminals, this will cause permanent damage to
the DVP04PT-H.
Make sure that the DVP04PT-H is properly grounded , to avoid any electromagnetic noise.
Use wires with resistance when connecting the platinum resistance thermister (RTD) to the PLC.
Please keep the wires as short as possible when connecting the RTD’s to the PLC and keep
power wires as far away as possible from I/O wires to avoid noise interference.
2 INTRODUCTION
2.1 Model Explanation and Peripherals
 Thank you for choosing DELTA’s DVP Series PLC. The DVP04PT-H allows the connection of four
platinum temperature sensors (PT100 3-WIRE 100 Ω3850 PPM/°C (DIN 43760 JIS
C1604-1989)). The DVP-PLC EH MPU transforms the sensors input into a 14 bit digital signal,
which may then be manipulated using TO and FROM commands in the ladder logic program.
There are 49 Controlled Registers (CR) in each module (each register is 16 bits).
 DVP04PT-H platinum temperature sensors can update software version by RS-485
communication.
 The DVP04PT-H works with both Centigrade and Fahrenheit. The input resolution for Centigrade
is 0.1 degrees and for Fahrenheit is 0.18 degrees.
 Nameplate Explanation
0.1 C or 0.18 F
20.4VDC ~ 28.8VDC
VX.XX 04PT-H0T4250003
PLC model
Input Power Supply Spec.
Analog Input / Outp ut Module Spec.
Barcode
 Model Explanation
Model Serial Number
Product Series
Input+Output point
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors(PT-100)
TC: Thermocouple sensors(Type J/K)
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
Production week
Production place (Taoyuan)
Production year (2004)
Production Model
XA: A/D , D/A Functions
RT: Resistor Thermocouple
HC: High speed count input module
PU: single axis positioning unit
2.2 Product Profile and Outline
1. DIN rail location (35mm) 6. Terminals
2. Mounting hole to connect expansion
unit/expansion module
7. Expansion hole of the expansion unit
mounting pins
3. Model name 8. Terminal layout
4. Indicator LED for power, error and run state 9. Mounting port to connect expansion
unit/expansion module
5. DIN rail clip
2.3 External wiring
PT100
PT100
CH1
CH4
1mA
DC/ DC
5V
AG
+15V
-15V
AG
AG
AG
24+
24-
FG
I-
L-
L+
FG
I-
L-
L+
Converter
System
Class 3 Grounding
(100 of less)
terminal of
power module
Shielded*1
*2
*3
1mA
Shielded*1
Grounding
Note 1: Use only the wires that are supplied
with your temperature sensor (PT
100) for analog input and separate
from other power line or any wire that
may cause noise. Please use 3 wire
for PT 100.
Note 2: Terminal FG is a grounding location for
noise suppression.
Note 3: Please connect terminal of power
supply module and terminal of
DVP04PT-H platinum temperature
sensors module to system earth
ground or connects to machine cover.
Warning: DO NOT connect wires to the No
Connection (●) terminals.
3 STANDARD SPECIFICATIONS
3.1 Function Specifications
Platinum Temperature Module
(04PT) Centigrade (°C) Fahrenheit (°F)
Power supply voltage 24 VDC (20.4VDC~28.8VDC) ( –15%~+20%)
Analog input channel 4 channels per module
Sensors type 3-WIRE PT100Ω3850 PPM/°C(DIN 43760 JIS C1604-1989)
Current excitation 1 mA
Temperature input range -200°C~600°C -328°F~1112°F
Digital conversion range K-2000~K6000 K-3280~K11120
Resolution 14 bits (0.1°C) 14 bits (0.18°F)
Overall accuracy ±0.5% of full scale of 25°C(77°F), ±1% of full scale during 0~55°C
(32~131°F)
Response time 200 ms ×channels
Isolation Method Isolation between digital and analog circuitry. There is no isolation
between channels.
Digital data format 2’s complement of 16-bit, (13 Significant Bits)
Average function Yes (CR#2~CR#5 may be set and the range is K1~K4096)
Self diagnostic function Upper bound and lower bound detection per channel
Communication mode (RS-485)
Yes, there are ASCII/RTU modes, communication rate can be
4800 /9600 /19200 /38400 /57600 /115200. Communication
format of ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8
E 1). When connecting to PLC MPU in series, RS-485 can’t be
used. The RS-485 is disabled when the DVP04PT-H is connected
in series to an MPU (use the RS485 on MPU).
Connection to a DVP-PLC MPU
in series
When DVP04PT-H modules are connected to an MPU, the
modules are numbered from 0 – 7. 0 is the closest to the MPU
and 7 is the furthest. The Maximum number of modules is 8
modules and they do not occupy any digital I/O points of the MPU.
3.2 Other Specification
Power Specification
Maximum Power Consumption 2W at 24 VDC (20.4VDC~28.8VDC) (-15 % ~ + 20%)
Environment Condition
Environment Condition Follow the DVP-PLC MPU.
Static Electricity Prevention Proper grounding and handling required of the unit and terminals
4CR (CONTROLLED REGISTER)
DVP04PT-H platinum temperature sensors Explanation
CR
No.
RS-485
Parameter
address
Latched Register name b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0 H 4064 ○R Model type System used, data length is 8bits (b7~b0). DVP04PT-H model code = H 0402
#1 Reserved
#2 H 4066 ○R/W CH1 average number
#3 H 4067 ○R/W CH2 average number
#4 H 4068 ○R/W CH3 average number
#5 H 4069 ○R/W CH4 average number
The number of readings used for “average” temperature on channels CH1~CH4.
Setting range is K1~K4096 and factory setting is K10.
#6 H 406A ╳R CH1 average degrees(°C)
#7 H 406B ╳R CH2 average degrees(°C)
#8 H 406C ╳R CH3 average degrees(°C)
#9 H 406D ╳R CH4 average degrees(°C)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees C)
#10~ #11 Reserved
#12 H 4070 ╳R CH1 average degrees(°F)
#13 H 4071 ╳R CH2 average degrees(°F)
#14 H 4072 ╳R CH3 average degrees(°F)
#15 H 4073 ╳R CH4 average degrees(°F)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees F)
#16~ #17 Reserved
#18 H 4076 ╳R Present temperature of
CH1 (°C)
#19 H 4077 ╳R Present temperature of
CH2 (°C)
#20 H 4078 ╳R Present temperature of
CH3 (°C)
#21 H 4079 ╳R Present temperature of
CH4 (°C)
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C)
#22~ #23 Reserved
#24 H 407C ╳R Present temperature of
CH1 (°F)
#25 H 407D ╳R Present temperature of
CH2 (°F)
#26 H 407E ╳R Present temperature of
CH3 (°F)
#27 H 407F ╳R Present temperature of
CH4 (°F)
Present temperature of channels CH1~CH4. (unit: 0.1degrees F)
#28~ #29 Reserved
#30 H 4082 ╳R Error status Data register stores the error status, refer to fault code chart for details.
#31 H 4083 ○R/W Communication address
setting
RS-485 communication address.
Setting range is 01~255 and factory setting is K1
#32 H 4084 ○R/W Communication baud rate
setting
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).
Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec).
b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec).
b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec).
b5: 115200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15: RTU mode.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Definition of ERR
LED
CH4 CH3 CH2 CH1
#33 H 4085 ○R/W Reset to factory setting
Example: Setting of CH1
1. b0 Reserved
2. b1 Reserved
3. b2: Set to 1 and PLC will be reset to factory settings.
Definition of ERR LED: b12~b15=1111(factory settings)
1. b12 corresponds to CH1: when b12=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
2. b13 corresponds to CH2: when b13=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
3. b14 corresponds to CH3: when b14=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
4. b15 corresponds to CH4: when b15=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
#34 H 4086 ○R Software version Display software version in hexadecimal. Example: H 010A = version 1.0A.
#35~#48 System used
○means latched.
╳means not latched.
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
Explanation:
1. CR#0: The PLC model type.
2. CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 are reserved.
3. CR#2 ~ CR#5: Used to set the number of input readings used for the average temperature
calculation. The available range is K1~K4096 and factory setting is K10.
4. CR#6 to CR#9: The average temperature (°C). The average temperature is calculated using
multiple temperature readings. Example: If CR#2 is 10, the temperature in CR#6 will be the
average of the last 10 readings on CH1.
5. CR#12 to CR#15: The average temperature (°C). The average temperature is calculated using
multiple temperature readings. Example: If CR#2 is 10, the temperature in CR#12 will be the
average of the last 10 readings on CH1.
6. CR#18 ~ CR#21: display present temperature (°C) of CH1~CH4 input signal.
Unit: mm
7. CR#24 ~ CR#27: display present temperature (°F) of CH1~CH4 input signal.
8. CR#30 is a fault code register. Refer to the following chart.
Fault description Content b15~b8 b7 b6 b5 b4 b3 b2 b1 b0
Power source abnormal K1(H1) 0 0 0 0 0 0 0 1
Analog input value error K2(H2) 0 0 0 0 0 0 1 0
Setting mode error K4(H4) 0 0 0 0 0 1 0 0
Offset/Gain error K8(H8) 0 0 0 0 1 0 0 0
Hardware malfunction K16(H10) 0 0 0 1 0 0 0 0
Digital range error K32(H20) 0 0 1 0 0 0 0 0
Average times setting error K64(H40) 0 1 0 0 0 0 0 0
Command error K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the
same time. 0 means normal and 1 means having fault.
9. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1.
10. CR#32: RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600 and 115200.
b0:4800bps, b1:9600bps (factory setting), b2:19200bps, b3:38400 bps, b4:57600 bps, b5:115200
bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15=0: ASCII mode, b15=1: RTU mode. Communication format: ASCII mode is 7Bit, even bit, 1 stop
bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
11. CR#33: b0~b11: Used to reset the settings of CH1~CH4 to factory defaults.
b12~b15: definition of ERR LED, factory setting is b12~b15=1111.
12. CR#34: software version.
13. CR#35~ CR#48: Reserved for internal system use.
14. The corresponding parameters address H4064~H4095 of CR#0~CR#48 may provide users to
read/write data via RS-485 communication.
A. Baud rate can be 4800, 9600, 19200, 38400, 57600, 115200bps.
B. Communication protocol ca be Modbus ASCII / RTU mode. Communication format: ASCII
mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even
bit, 1 stop bit (8 E 1).
C. Function code: 03H read data from register.
06H write a WORD into register.
10H write many WORD into register.
5 TEMPERATURE/DIGITAL CHARACTERISTIC CURVE
Temperature mode: (Centigrade)
+6000
+3000
-2000
+600-200
Digital Output
Temperature Input
C C
Temperature mode: (Fahrenheit)
+11120
+5560
-3280
+1112
-328
Digital Output
Temperature Input
F F
6 INITIAL PLC START-UP
 LED display:
1. Upon power-up, the ERROR LED will light for 0.5 seconds the POWER LED will light
continuously.
2. No errors= POWER LED on and ERROR LED off.
Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power
supply rises above 19.5V.
3. DVP04PT-H connected to PLC MPU in series = RUN LED on MPU will be lit and A/D LED
or D/A LED should blink.
4. After receiving the first RS-485 command the A/D LED or D/A LED will blink.
5. If the input or output exceeds the upper or lower bounds, then the ERROR LED will blink.
 Example:
M1000
FROM K0
= H402 D0
TO K0
FROM K0
FROM K0
FROM K0
FROM K0
FROM
M1002
Explanation:
 Reading the model type of extension module K0 (should be H0402 for DVP04PT-H model type).
 The average numbers of CH1~CH4 saved in D10~D13 will be wrote into CR#2~CR#5.
 If the model type is DVP04PT-H, reading the average temperature (°C) of CH1~CH4 (4 data) from
CR#6~CR#9 and save them into D20~D23.
 Reading the average temperature (°F) of CH1~CH4 (4 data) from CR#12~CR#15 and save them into
D24~D27.
 Reading the present temperature (°C) of CH1~CH4 (4 data) from CR#18~CR#21 and save them into
D30~D33.
 Reading the present temperature (°F) of CH1~CH4 (4 data) from CR#24~CR#27 and save them into
D34~D37.
7 RELATED INSTRUCTIONS EXPLANATION
API Adaptive model
ES EP EH
78
D FROM P
Read special module CR
data 
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1
¼¼
m2
¼¼
D ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
n
¼¼
 Note: The usage range of operand m1is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
ES series model doesn’t support pulse
execution command (FROMP, DFROMP).
16-bit command (9 STEPS)
FROM Continuous
execution FROMP Pulse
execution
32-bit command (17 STEPS)
DFROM Continuous
execution DFROMP Pulse
execution
 Flag: When M1083=On, it allows
to insert interrupt during
FROM/TO. Refer to
following for detail.
Command
Explanation
 : the module number you are probing. : the number of Controlled Registers
to be read. : the data register location for storing data. : the number of CRs
to read at one time.
 DVP-series PLC uses this command to read CR data of each special module.
 : When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be
used for 32-bit.
 Please refer the following footnote for calculating of special module number.
Program
Example
 To read the content of CR#24 and CR#25 of module#0 and save it in D0 and D1, the
n=2.
 The command will be executed when X0=ON. When X0=OFF, nothing will occur and
the stored data will not change.
X0
FROM K0
API Adaptive model
ES EP EH
79 DTO P
Special module CR
data write 
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1
¼¼
m2
¼¼
S
¼¼¼¼¼¼¼¼ ¼ ¼ ¼
n
¼¼
 Note: The usage range of operand m1is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
For ES series, it doesn’t support pulse
execution command (TOP, DTOP)
16-bit command (9 STEPS)
TO Continuous
execution TOP Pulse
execution
32-bit command (17 STEPS)
DTO Continuous
execution DTOP Pulse
execution
 Flag: When M1083=On, it
allows to insert interrupt
during FROM/TO. Refer to
following for detail.
Command
Explanation
 : the module number you are probing. : the number of Controlled
Registers that will be written to. : the data to write. : the number of CRs
to write to one time.
 DVP-series PLC uses this command to write data into Controlled Registers of
special modules.
 : When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can
be used for 32-bit.
Program
Example
 Using the 32-bit command DTO. The program will write D11 and D10 into CR#3
and CR#2 of special module#0. DTO only allows one group of data to be written at
a time (n=1).
 The command is executed when X0=ON. When X0=OFF, nothing will occur and
the stored data will not change.
X0
DTO K0
Footnote
 The rules for adding multiple special modules to a Main Processing Unit:
 m1: The maximum number of special modules attached to an MPU is 8. The
module closest to the MPU is 0 and the module furthest from the MPU is 7.
 m2: The number of Controlled Registers (CR) built in is 49. (#0~#48).
 FROM/TO command, uses one CR at a time. DFROM/DTO command uses
two CR at a time. Example below:
Upper 16-bit Lower 16-bit
Assigned CR numer
(n=2 for 16-bit command and n=1 for 32-bit are equal controlled registers used).
D0
D1
D2
D3
D4
D5
D0
D1
D2
D3
D4
D5
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
Assigned
Equipment
Assigned
CR
Assigned
Equipment
Assigned
CR
16-bit command when n=6 32-bit command when n=3
 In ES series models, flag M1083 is not provided. When FROM/TO command is
executed, all interrupts (including external or internal interrupt subroutines) will be
disabled. All interrupts will be executed after FROM/TO command is completed.
Besides, FROM/TO command also can be executed in the interrupt subroutine.
 The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH
series models:
1. When M1083=Off, FROM/TO command is executed, all interrupts (including
external or internal interrupt subroutines) will be disabled. All interrupts will be
executed after FROM/TO command is completed. Besides, FROM/TO
command also can be executed in the interrupt subroutine.
2. When M1083=On, if an interrupt occurs while FROM/TO command has been
programmed, FROM/TO command will be interruptted to execute the interrupt.
However, FROM/TO command cannot be executed in the interrupt subroutine.

This manual suits for next models

1

Other Delta Controllers manuals

Delta NC10EB User manual

Delta

Delta NC10EB User manual

Delta AS Series User manual

Delta

Delta AS Series User manual

Delta VFD-E User manual

Delta

Delta VFD-E User manual

Delta DTV Series User manual

Delta

Delta DTV Series User manual

Delta DCS User manual

Delta

Delta DCS User manual

Delta DVP-PM Series Instructions for use

Delta

Delta DVP-PM Series Instructions for use

Delta DVP-20PM User manual

Delta

Delta DVP-20PM User manual

Delta DVP-PLC Instructions for use

Delta

Delta DVP-PLC Instructions for use

Delta AS Series User manual

Delta

Delta AS Series User manual

Delta DVP-EH Series User manual

Delta

Delta DVP-EH Series User manual

Delta E Series Mounting instructions

Delta

Delta E Series Mounting instructions

Delta DVP-10PM User manual

Delta

Delta DVP-10PM User manual

Delta DVP-ES3 Series User manual

Delta

Delta DVP-ES3 Series User manual

Delta DVP32ES200RC User manual

Delta

Delta DVP32ES200RC User manual

Delta ASD-B2-0121-B User manual

Delta

Delta ASD-B2-0121-B User manual

Delta NC200 User manual

Delta

Delta NC200 User manual

Delta DVP08SM11N User manual

Delta

Delta DVP08SM11N User manual

Delta RMC200 User guide

Delta

Delta RMC200 User guide

Delta VFD-L User manual

Delta

Delta VFD-L User manual

Delta DVP-SA2 User manual

Delta

Delta DVP-SA2 User manual

Delta DVP-SS2 User manual

Delta

Delta DVP-SS2 User manual

Delta DVP14ES00R2 User manual

Delta

Delta DVP14ES00R2 User manual

Delta VFD-V Series User manual

Delta

Delta VFD-V Series User manual

Delta DVP-15MC Series User manual

Delta

Delta DVP-15MC Series User manual

Popular Controllers manuals by other brands

GAC EEG6500 manual

GAC

GAC EEG6500 manual

Mitsubishi MELSEC iQ-F FX5 series user manual

Mitsubishi

Mitsubishi MELSEC iQ-F FX5 series user manual

Johnson Controls TEC3010 installation instructions

Johnson Controls

Johnson Controls TEC3010 installation instructions

Auber Instruments SYL-3615 instruction manual

Auber Instruments

Auber Instruments SYL-3615 instruction manual

Phoenix Mecano RK Rose+Krieger Compact-e-3 manual

Phoenix Mecano

Phoenix Mecano RK Rose+Krieger Compact-e-3 manual

B&K Reference 30 owner's manual

B&K

B&K Reference 30 owner's manual

Hanna Instruments BL 983322-0 instruction manual

Hanna Instruments

Hanna Instruments BL 983322-0 instruction manual

Victron energy SmartSolar MPPT 150/85 Series manual

Victron energy

Victron energy SmartSolar MPPT 150/85 Series manual

LSI MegaRAID SAS 9361-4i Quick installation guide

LSI

LSI MegaRAID SAS 9361-4i Quick installation guide

Zamel SRP-22 manual

Zamel

Zamel SRP-22 manual

Viridian Aristocrat Vertex manual

Viridian

Viridian Aristocrat Vertex manual

Grundfos SA-SPM instructions

Grundfos

Grundfos SA-SPM instructions

Barthelme DMX503 operating instructions

Barthelme

Barthelme DMX503 operating instructions

Emerson Dixell XR40D Installing and operating instructions

Emerson

Emerson Dixell XR40D Installing and operating instructions

Honeywell VR4305 quick start guide

Honeywell

Honeywell VR4305 quick start guide

RNA ESR 2500 operating instructions

RNA

RNA ESR 2500 operating instructions

Carrier ChillerVu Installation and startup guide

Carrier

Carrier ChillerVu Installation and startup guide

Topkodas PROGATE Quick setup guide

Topkodas

Topkodas PROGATE Quick setup guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.