- 2 -
Insulation impedance > 5MΩ(all I/O point-to-ground 500 VDC)
Noise immunity ESD: 8 kV Air Discharge, EFT: Power Line: 2 kV, Digital I/O: 1 kV,
Analog & Communication I/O: 250 V
Grounding
The diameter of grounding wire shall not be less than that of L, N
terminal of the power. (When many PLCs are in use at the same time,
please make sure every PLC is properly grounded.)
Operation/storage
Operation: 0 to 55°C (temperature), 50 to 95% (humidity), pollution
degree 2
Storage: -25 to 70°C (temperature), 5 to 95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (g) 696
Input Points
Max. input Model
Terminal Description Response
char. Cur. Vol. 20D/
20DT
20M
START0, START1 Enabling input 10 ms 6 mA 24 V 99
STOP0, STOP1 Disabling input 10 ms 6 mA 24 V 99
LSP0/LSN0,
LSP1/LSN1 Right/left limit input 10 ms 6 mA 24 V 99
X1/X2 (for Z axis) Right/left limit input
(LSP2/LSN2) 10 ms 6 mA 24 V - 9
A0+, A0-, A1+, A1-
(shared by Y/Z axis)
MPG A-phase pulse input +, -
(differential signal input) 200 kHz 15 mA 5 to
24 V 99
B0+, B0-, B1+, B1-
(shared by Y/Z axis)
MPG B-phase pulse input +, -
(differential signal input) 200 kHz 15 mA 5 to
24 V 99
PG0+, PG0-, PG1+,
PG1-
Zero point signal input +, -
(differential signal input) 200 kHz 15 mA 5 to
24 V 99
X3 (for Z axis) Zero point signal input (PG2) 10 ms 6 mA 24 V - 9
DOG0, DOG1
There are 2 variations according
to different operation modes:
1. DOG signal when zero return
2. Inserting enabling signal at
1-seg. or 2-seg. speed
1 ms 6 mA 24 V 99
X0 (for Z axis) Same as DOG0, DOG1 (DOG2) 10 ms 6 mA 24 V - 9
Digital Input Points
24 VDC signal common port input
Spec
Item Low-speed High-speed (200 kHz) #1 Note
Input wiring type Change wiring from S/S to SINK or SOURCE
Input indicator LED display; light on = ON, light off = OFF
Input voltage --
Action level OffOn: 20 μs, OnOff: 30 μs
Response time/
noise immunity #2 10 ms 0.5 μs
#1: Input point A, B, PG is
high-speed input; other
input point is low-speed
input.
#2: Input point X0 to X7
can conduct 10 to 60 ms
digital filter adjustment.
Output Points
Model
Terminal Description Response
char.
Max.
Cur.
(Input) 20D/
20DT 20M
CLR0+, LR0-,
CLR1+, CLR1-
Clearing signals (by the error counter in
Servo drive) 10 ms 20 mA 99
Y2 (for Z axis) Same as clearing signals (CLR2) 10 ms 30 mA - 9
FP0+, FP0-,
FP1+, FP1-
Forward/reverse running mode: Forward
pulse output
Pulse direction: towards pulse output end
500 kHz 40 mA 99