Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 10
1912XR Installation Guide
Cannot exceed 6.5 with one 367 Battery
Cannot exceed 13.0 with two 367 Batteries
Cannot exceed 19.5 with three 367 Batteries
Cannot exceed 26.0 with four 367 Batteries
Transformer required:
Whenever there are three or
four batteries being charged by the 1912XR panel, you
must install the DMP Model 322 Transformer.
7.6 1912XR power requirements
During AC power failure, the1912XR panel and all auxiliary devices connected to the 1912XR draw their
power from the battery. All devices must be taken into consideration when calculating the battery standby
capacity. Below is a list of the power requirements of the 1912XR panel. Add the additional current draw of
Security Command keypads, loop expanders, smoke detector output, and any other auxiliary devices used
in the system for the total current required. The total is then multiplied by the total number of standby hours
required to arrive at the total ampere/hours required.
1912XR STANDBY BATTERY POWER CALCULATIONS
Standby Current Alarm Current
1912XR Command Processor Panel 130mA ______ 130mA ______
Relay Outputs 1-2 (ON) Qty _____ x 30mA ______ Qty _____ x 30mA ______
Voltage Outputs 3-6 (ON) Qty _____ x 5mA ______ Qty _____ x 5mA ______
Active Loops 1-4 Qty _____ x 1.6mA ______ Qty _____ x *2mA ______
Active Loop 5 4mA ______ 30mA ______
2-Wire Smokes Qty _____ x .1mA ______ Qty _____ x .1mA ______
893 Dual Phone Line Module 12mA ______ 50mA ______
862N Network Card Qty _____ x 15mA ______ Qty _____ x 15mA ______
862P Printer Card Qty _____ x 15mA ______ Qty _____ x 15mA ______
872 HARD-WIRE-LESS™ Card Qty _____ x 15mA ______ Qty _____ x 15mA ______
881 Expansion Card Qty _____ x 15mA ______ Qty _____ x 15mA ______
Bell Output 1000mA max. ______
670, 770, 771 Keypads Qty _____ x 125mA ______ Qty _____ x 125mA ______
Annunciator (ON) Qty _____ x 20mA ______
Active Loops Qty _____ x 1.6mA ______ Qty _____ x *2mA ______
714 Loop Expander Qty _____ x 7mA ______ Qty _____ x 7mA ______
Active Loops (EOL installed) Qty _____ x 1.6mA ______ Qty _____ x *2mA ______
715 Loop Expander Qty _____ x 7mA ______ Qty _____ x 7mA ______
Active Loops (EOL installed) Qty _____ x 4mA ______ Qty _____ x 30mA ______
2-Wire Smokes Qty _____ x .1mA ______ Qty _____ x .1mA ______
716 Output Expander Qty _____ x 7mA ______ Qty _____ x 7mA ______
Active Form C Relays Qty _____ x 28mA ______
Aux. Powered Devices on Terminals 7 ______ mA ______ mA
(Other than 670, 770, 771, 714, 715, 716)
Total Standby ______ mA Total Alarm ______ mA
Total Standby ______ mA x number of standby hours needed ______ = ______ mA/hours
Total Alarm + ______ mA/hours
Total ______ mA/hours
x_.001_____
= ______ Ampere/Hours Required
* Based on 10% of active loops in alarm condition