INSTRUCTION MANUAL
Metal Housed Alarm Tone and Voice
Annunciation Sounder/Sounder Beacon Range.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 1 of 9
1) Introduction
The Appello tone and speech annunciation
sounder has three different styles in DC.
•D105AX Sounder
•DL105AXX Sounder Beacon (Xenon)
•DL105AXH Sounder Beacon (LED)
These Sounder units share a common set of
functions:-
•4 stages, each stage can record up to 30
seconds of CD quality audio.
•Facility to record via an on board microphone
or a line in input.
•The recorded message can be played back
proceeded either with or without the choice
of one of forty five tones.
The Beacon functions are either:-
•Xenon Strobe:
o1Hz flash rate
o1.5Hz flash rate
oDouble strike flash pattern
•LED:
oSteady
o2Hz flash rate
2) Operating and Marking
All units have the following operating
requirements and limitations.
Sounder only outputs
Unit Type No. Voltage Range Current
D105AX 24Vdc 10-30Vdc 256mA
Max Current 256mA @ 30Vdc
DL105AXX & DL105AXH sounder beacon units -
Add selected sounder & beacon currents to
calculate total current required.
Beacon only outputs
Unit Type No. Voltage Range Current
Xenon Beacon 12Vdc 10-14Vdc 500mA
24Vdc 20-28Vdc 250mA
LED Beacon 24Vdc 10-30Vdc 157mA
Max Current 166mA @ 30Vdc
Operating Temp: -25 to +55C
IP Rating: Type 4 / 4X / 3R / 13 , IP66
Marking:
3) Installation & Wiring Requirements
D105AX
DL105AXX & DL105AXH
Always de-energize unit before removing cover.
The installation of the units must be in accordance
with any local codes that may apply and should
only be carried out by a competent trained
electrical engineer.
The power terminals on the control unit are clearly
marked and will accept up to 1.5mm2cable.
DC Terminals
On main PCB.
++ = Positive
- - = Negative
The DL105AXX & DL105AXH units will have the
beacon already prewired to the unit so no extra
wiring is required.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 2 of 9
4) Beacon Set-up
The beacon unit may need to be configured
dependant on the type of flash required.
The xenon beacon is set as standard to 1Hz flash
rate mode but it can be set to either 1.5Hz flash
rate or double Strike flash pattern modes also. To
alter the settings, change the position of the
header pin as shown:
•Keep header on pins deignated ‘A’ for
1Hz flash rate mode
•Place header on pins designated ‘B’ for
1.5Hz flash rate mode
•Place header on pins designated ‘C’ for
double strike flash pattern mode
The LED beacon is set as standard to the 2Hz
flash mode but it can be set to a steady on mode
also. To alter the settings, change the position of
the header pin as shown.
•Remove header for steady mode.
•Keep header in standard position for
2Hz flashing mode
5) Unit Set-up and Recording
The unit will need to be configured to suit the end
user.
If recording either via the onboard microphone or
the in-line connector the unit will need to be
supplied with power.
DC units can be powered when completing
recording and set-up.
See section 7) Appello Setup Guide overleaf for
Set-up instructions and functions.
6) Tone Selection Table
The Appello unit has 45 different tones (See
Table 1) that can be selected for the first stage
alarm. The systems can then be switched to
sound second, third and fourth stage alarm tones.
The tones are selected by operation of a DIP
switch S4 on the main PCB.
The tone table (Table 1) shows the switch
positions for the 45 tones and which tones are
available for the second third and fourth stages.
Example
S4 Dip Switch -
Shown Set for Tone 1
(All switches OFF)
To sound stage one simply connect the supply
voltage (+ve and –ve), to the supply input
terminals on the correct PCB shown.
Second, Third and Fourth Stage Selection
The Appello unit uses –ve switching to change the
tone to the second, third and fourth stages.
Warning! : The negative supply must remain
connected to the -(ve) terminal and a link
made from this to the appropriate stage (S2)
terminal otherwise the unit will be damaged.
To change to the second, third or fourth stage
tone, link the -ve supply line to terminal relevant
stage terminal. I.e. for Stage 2 link the -ve supply
to the S2 terminal, for Stage 3 link the -ve supply
to the S3 terminal etc.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 3 of 9
S2 - Set-up S4 - Tones Power & Alarm Stage Terminal
Function L.E.D 's
Peak level L.E.D
On board microphone
Audio Line-in
Jumper Alarm Tone & (Voice) Recorded Content
Volume Controls
7) Appello Setup Guide
The following guide is designed to get the user quickly interfacing with the Appello unit.
•The Appello unit can be set-up to either play an attention seeking tone and then a recorded
message or just play the recorded message.
•The user can:
oRecord on each of the 4 stages using either the Line In or Microphone inputs
oSelect the required alarm tone
oDelete unwanted messages.
•To re-record a message on a particular stage, the previous message on that stage must be
deleted first.
•Once the user has configured the unit, it must be put into it's Playback Mode and S2 switches
set to stage 1, as shown in Quick Ref - Playback Mode (Stage 1 illustrated) guide below.
•The “Mass Erase”function will erase all the recorded stages.
•The "Mass Erase" can also be used to reset the unit if any functionality is
lost.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 4 of 9
Quick ref - Switch ‘S2’Dip Switch Function Settings
Switch
No.
OFF Position
Function
ON Position Function
1
Record Mode
Playback Mode
2
Stage selection switch
Switch 2 On & Switch 3 On = Alarm Stage 1
Switch 2 Off & Switch 3 On = Alarm Stage 2
Switch 2 On & Switch 3 Off = Alarm Stage 3
Switch 2 Off & Switch 3 Off = Alarm Stage 4
3
Stage selection switch
4
Line-In selected
On board Microphone selected
5
Program –Record &
Erase Mode ON
Playback –Record & Erase Mode OFF
6
Message & Tone
Playback
Message only Playback
7
Single Message or
Mass Erase Mode OFF
Single Message or Mass Erase Mode ON
Quick Ref - Playback Mode (Stage 1 illustrated)
1
For Stage 1:
Set Switch ‘S2’positions
1,2,3 & 5 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions
1,3 & 5 to 'ON’
For Stage 3:
Set Switch ‘S2’positions
1,2 & 5 to 'ON'
For Stage 4:
Set Switch ‘S2’positions
1 & 5 to 'ON'
2
Switch on power or
Press reset button
3a
Unit will sound alarm tone
and then recorded
content repeatedly
Quick Ref - Recording Mode (Stage 1 illustrated)
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 5 of 9
1
For Stage 1:
Set Switch ‘S2’positions
2,3 & 4 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions 3
& 4 to 'ON'
For Stage 3:
Set Switch ‘S2’positions 2
& 4 to 'ON'
For Stage 4:
Set Switch ‘S2’position 4 to
'ON'
To record from Line-in
instead of the on board
microphone follow above
step 1 but set Switch ‘S2’
position 4 to OFF
2
Switch on power or
Press reset button
3a
Press action button:
Start recording
3b
Speak into microphone or
plug line-in.
It is suggested that a 5cm
gap is maintained to the
microphone.
The peak detector L.E.D
should flash regularly to
maintain a good recording
level.
However, if it stays on for
most of the time, the
recording may be distorted.
4
Press action button:
Stop recording
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 6 of 9
Quick Ref - Erase Single stage Mode (Stage 1 illustrated)
1
For Stage 1:
Set Switch ‘S2’positions
2,3 & 7 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions
3 & 7 to 'ON'
For Stage 3:
Set Switch ‘S2’positions
2 & 7 to 'ON'
For Stage 4:
Set Switch ‘S2’position 7
to 'ON'
2
Switch on power or
Press reset button
3a
Press action button:
Erase will begin
3b
- - - - erase complete
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 7 of 9
Quick Ref - Mass Erase Mode (Erases All Stages)
1
Set Switch ‘S2’position
7 to 'ON'
2
Set jumper J4
‘ME’to ON position
(centre and right pin
connected)
3
Switch on power or
Press reset button
4a
Press action button:
Erase will begin
4b
- - - - erase complete
5
Reset Jumper J4
‘ME’to OFF position
Quick Ref - Synchronising Two Sounders (All stages)
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 8 of 9
1
Connect Synch cable to
Master and Slave PCB
2
Set 1 off Units as Master
and 1 off Unit as Slave
Set jumper J6 to Sync on
Set jumper J5 S/M on
Master unit to master
position (on)
Set jumper J5 S/M on
Slave unit to slave
position (off)
Position of S2 switch
does not affect synch
operation.
3
Switch on power onto the
Master unit first
Then switch power onto
the Slave unit
Master Unit
Slave Unit
4a
Press action button on the
Master Unit:
Synchronisation will begin
Master Unit
Slave Unit
4b
- - - - Synchronisation
complete
Switch off Power to units
Master Unit
Slave Unit
5
Reset on both units
jumper J6 to Sync off
Set jumper J5 S/M on
both units to Master
position (on)
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 9 of 9
Table 1: Tone selection table
Switch
Stage 2
Stage 3
Stage 4
Stage 1
Frequency Description
1
2
3
4
5
6
(S2)
(S3)
(S4)
Tone 1
340 Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 2
800/1000Hz @ 0.25 sec Alternating
Tone 17
Tone 5
Tone 29
Tone 3
500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop
Tone 2
Tone 5
Tone 29
Tone 4
800/1000Hz @ 1Hz Sweeping
Tone 6
Tone 5
Tone 29
Tone 5
2400Hz Continuous
Tone 3
Tone 20
Tone 29
Tone 6
2400/2900Hz @ 7Hz Sweeping
Tone 7
Tone 5
Tone 29
Tone 7
2400/2900Hz @ 1Hz Sweeping
Tone 10
Tone 5
Tone 29
Tone 8
500/1200/500Hz @ 0.3Hz Sweeping
Tone 2
Tone 5
Tone 29
Tone 9
1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P.
Tone 15
Tone 2
Tone 29
Tone 10
2400/2900Hz @ 2Hz Alternating
Tone 7
Tone 5
Tone 29
Tone 11
1000Hz @ 1Hz Intermittent
Tone 2
Tone 5
Tone 29
Tone 12
800/1000Hz @ 0.875Hz Alternating
Tone 4
Tone 5
Tone 29
Tone 13
2400Hz @ 1Hz Intermittent
Tone 15
Tone 5
Tone 29
Tone 14
800Hz 0.25sec on, 1 sec off Intermittent
Tone 4
Tone 5
Tone 29
Tone 15
800Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 16
660Hz 150mS on, 150mS off Intermittent
Tone 18
Tone 5
Tone 29
Tone 17
544Hz (100mS)/440Hz (400mS) - NF S 32-001
Tone 2
Tone 27
Tone 29
Tone 18
660Hz 1.8sec on, 1.8sec off Intermittent
Tone 2
Tone 5
Tone 29
Tone 19
1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s -NFC48-265
Tone 2
Tone 5
Tone 29
Tone 20
660Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 21
554Hz/440Hz @ 1Hz Alternating
Tone 2
Tone 5
Tone 29
Tone 22
544Hz @ 0.875 sec. Intermittent
Tone 2
Tone 5
Tone 29
Tone 23
800Hz @ 2Hz Intermittent
Tone 6
Tone 5
Tone 29
Tone 24
800/1000Hz @ 50Hz Sweeping
Tone 29
Tone 5
Tone 29
Tone 25
2400/2900Hz @ 50Hz Sweeping
Tone 29
Tone 5
Tone 29
Tone 26
Bell
Tone 2
Tone 15
Tone 29
Tone 27
554Hz Continuous
Tone 26
Tone 5
Tone 29
Tone 28
440Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 29
800/1000Hz @ 7Hz Sweeping
Tone 7
Tone 5
Tone 29
Tone 30
300Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 31
660/1200Hz @ 1Hz Sweeping
Tone 26
Tone 5
Tone 29
Tone 32
Two tone chime.
Tone 26
Tone 15
Tone 29
Tone 33
745Hz @ 1Hz Intermittent
Tone 2
Tone 5
Tone 29
Tone 34
1000 & 2000Hz @ 0.5 sec Alternating - Singapore
Tone 38
Tone 45
Tone 29
Tone 35
420Hz @ 0.625 sec Australian Alert
Tone 36
Tone 5
Tone 29
Tone 36
500-1200Hz 3.75sec /0.25sec. Australian Evac.
Tone 35
Tone 5
Tone 29
Tone 37
1000Hz Continuous - PFEER Toxic Gas
Tone 9
Tone 45
Tone 29
Tone 38
2000Hz Continuous
Tone 34
Tone 45
Tone 29
Tone 39
800Hz 0.25sec on, 1 sec off Intermittent
Tone 23
Tone 17
Tone 29
Tone 40
544Hz (100mS)/440Hz (400mS) - NF S 32-001
Tone 31
Tone 27
Tone 29
Tone 41
Motor Siren - slow rise to 1200 Hz
Tone 2
Tone 5
Tone 29
Tone 42
Motor Siren - slow rise to 800 Hz
Tone 2
Tone 5
Tone 29
Tone 43
1200 Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 44
Motor Siren - slow rise to 2400 Hz
Tone 2
Tone 5
Tone 29
Tone 45
1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm
Tone 38
Tone 34
Tone 29

This manual suits for next models

2

Other E2S Security System manuals

E2S AlertAlight DL105X User manual

E2S

E2S AlertAlight DL105X User manual

E2S D1xC3 User manual

E2S

E2S D1xC3 User manual

E2S BExS120D User manual

E2S

E2S BExS120D User manual

E2S STExB2LD2 User manual

E2S

E2S STExB2LD2 User manual

E2S IS-CP4B-PT User manual

E2S

E2S IS-CP4B-PT User manual

E2S Appello A121APPX User manual

E2S

E2S Appello A121APPX User manual

E2S BExCBL2-L2D-P User manual

E2S

E2S BExCBL2-L2D-P User manual

E2S BExBG21D-P User manual

E2S

E2S BExBG21D-P User manual

E2S GNExB2X05-S Series User manual

E2S

E2S GNExB2X05-S Series User manual

E2S GNExCP6C-PB User manual

E2S

E2S GNExCP6C-PB User manual

E2S GNExCP7-BG-S User manual

E2S

E2S GNExCP7-BG-S User manual

E2S SPECTRA H110 T User manual

E2S

E2S SPECTRA H110 T User manual

E2S BExCP3C-PB User manual

E2S

E2S BExCP3C-PB User manual

E2S D1xB2X05-S User manual

E2S

E2S D1xB2X05-S User manual

E2S D1xS1 Series User manual

E2S

E2S D1xS1 Series User manual

E2S BExBG15D-P-SIL User manual

E2S

E2S BExBG15D-P-SIL User manual

E2S GNExCP6B-PT User manual

E2S

E2S GNExCP6B-PT User manual

E2S D2xB1XH1 User manual

E2S

E2S D2xB1XH1 User manual

E2S MBLD2 Series User manual

E2S

E2S MBLD2 Series User manual

E2S STExCP8-BG-D User manual

E2S

E2S STExCP8-BG-D User manual

E2S D1xB2LD2 Series User manual

E2S

E2S D1xB2LD2 Series User manual

E2S SPECTRA H100 B User manual

E2S

E2S SPECTRA H100 B User manual

E2S D2xC2LD2 Series User manual

E2S

E2S D2xC2LD2 Series User manual

E2S D1xS1FDC024-S User manual

E2S

E2S D1xS1FDC024-S User manual

Popular Security System manuals by other brands

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Bosch DS304 installation instructions

Bosch

Bosch DS304 installation instructions

Pima Hunter-Pro 832 installation guide

Pima

Pima Hunter-Pro 832 installation guide

Bosch D220 user guide

Bosch

Bosch D220 user guide

Lorex LW2201 Series Frequently asked questions

Lorex

Lorex LW2201 Series Frequently asked questions

Stahl YL60 Series operating instructions

Stahl

Stahl YL60 Series operating instructions

RHINO RCA-2 Operation instructions

RHINO

RHINO RCA-2 Operation instructions

MEGATRONIX VIKING VS 3125 installation manual

MEGATRONIX

MEGATRONIX VIKING VS 3125 installation manual

Pandora 397O manual

Pandora

Pandora 397O manual

Anodyne Electronics Manufacturing AA37 Series Installation and operation manual

Anodyne Electronics Manufacturing

Anodyne Electronics Manufacturing AA37 Series Installation and operation manual

Guardall RX16i user manual

Guardall

Guardall RX16i user manual

iSmartAlarm Home Security System owner's manual

iSmartAlarm

iSmartAlarm Home Security System owner's manual

Klaxon SO4 Series installation instructions

Klaxon

Klaxon SO4 Series installation instructions

Piper piper user manual

Piper

Piper piper user manual

GE 13-949 installation instructions

GE

GE 13-949 installation instructions

Carmanah R829 owner's manual

Carmanah

Carmanah R829 owner's manual

GE Concord 4 Series installation instructions

GE

GE Concord 4 Series installation instructions

Ei Electronics Ei208DWRF instructions

Ei Electronics

Ei Electronics Ei208DWRF instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.