INSTRUCTION MANUAL
A105NAX, AL105NAXH & AL105NAXX APPELLO
Alarm Tone and Voice Annunciation Sounder
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 1 of 10
1) Introduction
The Appello tone and speech annunciation
sounder has three different styles in AC and DC.
•A105NAX Sounder
•AL105NAXH High Output LED
Sounder-Beacon Combination unit
•AL105NAXX Xenon Strobe
Sounder-Beacon Combination unit
These Sounder units share a common set of
functions:-
•4 stages, each stage can record up to 30
seconds of CD quality audio.
•Facility to record via an on board microphone
or a line in input.
•The recorded message can be played back
proceeded either with or without the choice
of one of forty five tones.
The Beacon functions are either:-
•Xenon Strobe - 1Hz flash rate
•LED - Either Steady or 2Hz blink rate
2) Operating and Marking
All units have the following operating
requirements and limitations.
Unit Type No. Voltage Range Current
Sounder only outputs
A105NAX DC 24Vdc 10-30Vdc 256mA
Max Current 256mA @ 30Vdc
A105NAX AC 115Vac 90-260Vac 112mA
230Vac 90-260Vac 124mA
Max Current 127mA @ 260Vac
AL105NAXH / AL105NAXX combined units - Add
selected sounder & beacon currents to calculate
total current required.
Beacon only outputs
AL105NAXH DC 24Vdc 10-30Vdc 157mA
Max Current 166mA @ 30Vdc
AL105NAXH AC 115Vac 90-260Vac 60mA
230Vac 90-260Vac 35mA
Max Current 60mA @ 90Vac
AL105NAXX DC 12Vdc 10-14Vdc 500mA
24Vdc 20-28Vdc 250mA
AL105NAXX AC 115Vac +/-10%Vac 100mA
230Vac +/-10%Vac 50mA
Operating Temp: -20 to +55C
IP Rating: Type 4 / 4X / 3R / 13 , IP66
Marking:
3) Installation & Wiring Requirements
A105NAX
AL105NAXH / AL105NAXX
A105NAX
DC UNIT
A105NAX
AC UNIT
AL105NAXH / AL105NAXX
DC UNITS
LED (H) / XENON (X)
BEACON OPTION
AL105NAXH / AL105NAXX
AC UNITS
LED (H) / XENON (X)
BEACON OPTION
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 2 of 10
Always de-energize unit before removing cover.
The installation of the units must be in
accordance with any local codes that may apply
and should only be carried out by a competent
trained electrical engineer.
The power terminals on the control unit are
clearly marked and will accept up to 1.5mm2
cable.
DC Terminals
On main PCB.
++ = Positive
- - = Negative
AC Terminals
On Sub PCB
L = Live
N = Neutral
E = Earth
The AL105N units will have the beacon already
prewired to the unit so no extra wiring is required.
4) Beacon Set-up
The beacon unit may need to be configured
dependant on the type of flash required.
The xenon beacon has a 1Hz flash rate only.
The LED beacon is set as standard to the 2Hz
flash mode but it can be set to a steady on mode
also. To alter the settings, change the position of
the header pin as shown.
•Remove header for steady mode.
•Keep header in standard position for
2Hz flashing mode
5) Unit Set-up and Recording
The unit will need to be configured to suit the end
user.
If recording either via the onboard microphone or
the in-line connector the unit will need to be
supplied with power.
DC units can be powered when completing
recording and set-up.
Warning! : During set-up AC units must be
temporarily powered from either a 12V battery
or a separate 10-30VDC isolated power supply,
connected directly to the DC terminals on the
main appello PCB. This is because the AC
units power supply is not isolated and there
may be a risk of electric shock.
See section 7) Appello Setup Guide overleaf for
Set-up instructions and functions.
6) Tone Selection Table
The Appello unit has 45 different tones (See
Table 1) that can be selected for the first stage
alarm. The systems can then be switched to
sound second, third and fourth stage alarm tones.
The tones are selected by operation of a DIP
switch S4 on the main PCB.
The tone table (Table 1) shows the switch
positions for the 45 tones and which tones are
available for the second third and fourth stages.
Example
S4 Dip Switch -
Shown Set for Tone 1
(All switches OFF)
To sound stage one simply connect the supply
voltage (+ve and –ve) for DC units and (L, N, E)
for AC units, to the supply input terminals on the
correct PCB shown.
L
N
E
S2
S3
S4
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 3 of 10
DC Units Second, Third and Fourth Stage
Selection
The Appello unit uses –ve switching to change
the tone to the second, third and fourth stages.
Warning! : The negative supply must remain
connected to the -(ve) terminal and a link
made from this to the appropriate stage (S2)
terminal otherwise the unit will be damaged.
To change to the second, third or fourth stage
tone, link the -ve supply line to terminal relevant
stage terminal. Ie. for Stage 2 link the -ve supply
to the S2 terminal, for Stage 3 link the -ve supply
to the S3 terminal etc.
AC Units Second, Third and Fourth Stage
Selection
The Appello unit uses Live switching to change
the tone to the second, third and fourth stages.
To change to the second, third or fourth stage
tone, whilst maintaining the ac supply to the Live
and neutral, also link the Live supply line to
terminal relevant stage terminal. i.e. for Stage 2
link the Live supply to the S2 terminal, for Stage 3
link the Live supply to the S3 terminal etc.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 4 of 10
S2 - Set-up S4 - Tones Power & Alarm Stage Terminal
Function L.E.D 's
Peak level L.E.D
On board microphone
Audio Line-in
Jumper Alarm Tone & (Voice) Recorded Content
Volume Controls
7) Appello Setup Guide
The following guide is designed to get the user quickly interfacing with the Appello unit.
•The Appello unit can be set-up to either play an attention seeking tone and then a recorded
message or just play the recorded message.
•The user can:
oRecord on each of the 4 stages using either the Line In or Microphone inputs
oSelect the required alarm tone
oDelete unwanted messages.
•To re-record a message on a particular stage, the previous message on that stage must be
deleted first.
•Once the user has configured the unit, it must be put into it's Playback Mode and S2 switches set
to stage 1, as shown in Quick Ref - Playback Mode (Stage 1 illustrated) guide below.
•The “Mass Erase”function will erase all the recorded stages.
•The "Mass Erase" can also be used to reset the unit if any functionality is lost.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 5 of 10
Quick ref - Switch ‘S2’Dip Switch Function Settings
Switch
No.
OFF Position
Function
ON Position Function
1
Record Mode
Playback Mode
2
Stage selection switch
Switch 2 On & Switch 3 On = Alarm Stage 1
Switch 2 Off & Switch 3 On = Alarm Stage 2
Switch 2 On & Switch 3 Off = Alarm Stage 3
Switch 2 Off & Switch 3 Off = Alarm Stage 4
3
Stage selection switch
4
Line-In selected
On board Microphone selected
5
Program –Record &
Erase Mode ON
Playback –Record & Erase Mode OFF
6
Message & Tone
Playback
Message only Playback
7
Single Message or
Mass Erase Mode OFF
Single Message or Mass Erase Mode ON
Quick Ref - Playback Mode (Stage 1 illustrated)
1
For Stage 1:
Set Switch ‘S2’positions
1,2,3 & 5 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions
1,3 & 5 to 'ON’
For Stage 3:
Set Switch ‘S2’positions
1,2 & 5 to 'ON'
For Stage 4:
Set Switch ‘S2’positions
1 & 5 to 'ON'
2
Switch on power or
Press reset button
3a
Unit will sound alarm tone
and then recorded
content repeatedly
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 6 of 10
Quick Ref - Recording Mode (Stage 1 illustrated)
1
For Stage 1:
Set Switch ‘S2’positions
2,3 & 4 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions 3
& 4 to 'ON'
For Stage 3:
Set Switch ‘S2’positions 2
& 4 to 'ON'
For Stage 4:
Set Switch ‘S2’position 4 to
'ON'
To record from Line-in
instead of the on board
microphone follow above
step 1 but set Switch ‘S2’
position 4 to OFF
2
Switch on power or
Press reset button
3a
Press action button:
Start recording
3b
Speak into microphone or
plug line-in.
It is suggested that a 5cm
gap is maintained to the
microphone.
The peak detector L.E.D
should flash regularly to
maintain a good recording
level.
However, if it stays on for
most of the time, the
recording may be distorted.
4
Press action button:
Stop recording
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 7 of 10
Quick Ref - Erase Single stage Mode (Stage 1 illustrated)
1
For Stage 1:
Set Switch ‘S2’positions
2,3 & 7 to 'ON'
Alternatively for :
For Stage 2:
Set Switch ‘S2’positions
3 & 7 to 'ON'
For Stage 3:
Set Switch ‘S2’positions
2 & 7 to 'ON'
For Stage 4:
Set Switch ‘S2’position 7
to 'ON'
2
Switch on power or
Press reset button
3a
Press action button:
Erase will begin
3b
- - - - erase complete
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 8 of 10
Quick Ref - Mass Erase Mode (Erases All Stages)
1
Set Switch ‘S2’position
7 to 'ON'
2
Set jumper J4
‘ME’to ON position
(centre and right pin
connected)
3
Switch on power or
Press reset button
4a
Press action button:
Erase will begin
4b
- - - - erase complete
5
Reset Jumper J4
‘ME’to OFF position
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 9 of 10
Quick Ref - Synchronising Two Sounders (All stages)
1
Connect Synch cable to
Master and Slave PCB
2
Set 1 off Units as Master
and 1 off Unit as Slave
Set jumper J6 to Sync on
Set jumper J5 S/M on
Master unit to master
position (on)
Set jumper J5 S/M on
Slave unit to slave
position (off)
Position of S2 switch
does not affect synch
operation.
3
Switch on power onto the
Master unit first
Then switch power onto
the Slave unit
Master Unit
Slave Unit
4a
Press action button on the
Master Unit:
Synchronisation will begin
Master Unit
Slave Unit
4b
- - - - Synchronisation
complete
Switch off Power to units
Master Unit
Slave Unit
5
Reset on both units
jumper J6 to Sync off
Set jumper J5 S/M on
both units to Master
position (on)
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
[email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D165-00-001-IS_Issue_4 16-11-22
Sheet 10 of 10
Table 1: Tone selection table
Switch
Stage 2
Stage 3
Stage 4
Stage 1
Frequency Description
1
2
3
4
5
6
(S2)
(S3)
(S4)
Tone 1
340 Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 2
800/1000Hz @ 0.25 sec Alternating
Tone 17
Tone 5
Tone 29
Tone 3
500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop
Tone 2
Tone 5
Tone 29
Tone 4
800/1000Hz @ 1Hz Sweeping
Tone 6
Tone 5
Tone 29
Tone 5
2400Hz Continuous
Tone 3
Tone 20
Tone 29
Tone 6
2400/2900Hz @ 7Hz Sweeping
Tone 7
Tone 5
Tone 29
Tone 7
2400/2900Hz @ 1Hz Sweeping
Tone 10
Tone 5
Tone 29
Tone 8
500/1200/500Hz @ 0.3Hz Sweeping
Tone 2
Tone 5
Tone 29
Tone 9
1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P.
Tone 15
Tone 2
Tone 29
Tone 10
2400/2900Hz @ 2Hz Alternating
Tone 7
Tone 5
Tone 29
Tone 11
1000Hz @ 1Hz Intermittent
Tone 2
Tone 5
Tone 29
Tone 12
800/1000Hz @ 0.875Hz Alternating
Tone 4
Tone 5
Tone 29
Tone 13
2400Hz @ 1Hz Intermittent
Tone 15
Tone 5
Tone 29
Tone 14
800Hz 0.25sec on, 1 sec off Intermittent
Tone 4
Tone 5
Tone 29
Tone 15
800Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 16
660Hz 150mS on, 150mS off Intermittent
Tone 18
Tone 5
Tone 29
Tone 17
544Hz (100mS)/440Hz (400mS) - NF S 32-001
Tone 2
Tone 27
Tone 29
Tone 18
660Hz 1.8sec on, 1.8sec off Intermittent
Tone 2
Tone 5
Tone 29
Tone 19
1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s -NFC48-265
Tone 2
Tone 5
Tone 29
Tone 20
660Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 21
554Hz/440Hz @ 1Hz Alternating
Tone 2
Tone 5
Tone 29
Tone 22
544Hz @ 0.875 sec. Intermittent
Tone 2
Tone 5
Tone 29
Tone 23
800Hz @ 2Hz Intermittent
Tone 6
Tone 5
Tone 29
Tone 24
800/1000Hz @ 50Hz Sweeping
Tone 29
Tone 5
Tone 29
Tone 25
2400/2900Hz @ 50Hz Sweeping
Tone 29
Tone 5
Tone 29
Tone 26
Bell
Tone 2
Tone 15
Tone 29
Tone 27
554Hz Continuous
Tone 26
Tone 5
Tone 29
Tone 28
440Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 29
800/1000Hz @ 7Hz Sweeping
Tone 7
Tone 5
Tone 29
Tone 30
300Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 31
660/1200Hz @ 1Hz Sweeping
Tone 26
Tone 5
Tone 29
Tone 32
Two tone chime.
Tone 26
Tone 15
Tone 29
Tone 33
745Hz @ 1Hz Intermittent
Tone 2
Tone 5
Tone 29
Tone 34
1000 & 2000Hz @ 0.5 sec Alternating - Singapore
Tone 38
Tone 45
Tone 29
Tone 35
420Hz @ 0.625 sec Australian Alert
Tone 36
Tone 5
Tone 29
Tone 36
500-1200Hz 3.75sec /0.25sec. Australian Evac.
Tone 35
Tone 5
Tone 29
Tone 37
1000Hz Continuous - PFEER Toxic Gas
Tone 9
Tone 45
Tone 29
Tone 38
2000Hz Continuous
Tone 34
Tone 45
Tone 29
Tone 39
800Hz 0.25sec on, 1 sec off Intermittent
Tone 23
Tone 17
Tone 29
Tone 40
544Hz (100mS)/440Hz (400mS) - NF S 32-001
Tone 31
Tone 27
Tone 29
Tone 41
Motor Siren - slow rise to 1200 Hz
Tone 2
Tone 5
Tone 29
Tone 42
Motor Siren - slow rise to 800 Hz
Tone 2
Tone 5
Tone 29
Tone 43
1200 Hz Continuous
Tone 2
Tone 5
Tone 29
Tone 44
Motor Siren - slow rise to 2400 Hz
Tone 2
Tone 5
Tone 29
Tone 45
1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm
Tone 38
Tone 34
Tone 29

This manual suits for next models

2

Other E2S Security System manuals

E2S STExB2LD2 User manual

E2S

E2S STExB2LD2 User manual

E2S BExBGL1D User manual

E2S

E2S BExBGL1D User manual

E2S D1 B2X05 Series User manual

E2S

E2S D1 B2X05 Series User manual

E2S STExB2LD2 User manual

E2S

E2S STExB2LD2 User manual

E2S BExCS110-L2 User manual

E2S

E2S BExCS110-L2 User manual

E2S D1*CP1-PS Series User manual

E2S

E2S D1*CP1-PS Series User manual

E2S BExCBL2-L2D-P User manual

E2S

E2S BExCBL2-L2D-P User manual

E2S HA121 User manual

E2S

E2S HA121 User manual

E2S BExBG15D-P-SIL User manual

E2S

E2S BExBG15D-P-SIL User manual

E2S D2xC2LD3 User manual

E2S

E2S D2xC2LD3 User manual

E2S D2xB1X05 Series User manual

E2S

E2S D2xB1X05 Series User manual

E2S GNExB2X05-S Series User manual

E2S

E2S GNExB2X05-S Series User manual

E2S D1xB2LD2 Series User manual

E2S

E2S D1xB2LD2 Series User manual

E2S GNExCP6C-PB User manual

E2S

E2S GNExCP6C-PB User manual

E2S D2XC2XH1 User manual

E2S

E2S D2XC2XH1 User manual

E2S GNExB2LD2 User manual

E2S

E2S GNExB2LD2 User manual

E2S D1xB2X Series User manual

E2S

E2S D1xB2X Series User manual

E2S WP6-BG User manual

E2S

E2S WP6-BG User manual

E2S D1xS1FDC024-S User manual

E2S

E2S D1xS1FDC024-S User manual

E2S BExBG05D-P-SIL User manual

E2S

E2S BExBG05D-P-SIL User manual

E2S BExBG21D-P User manual

E2S

E2S BExBG21D-P User manual

E2S Appello A121APPX User manual

E2S

E2S Appello A121APPX User manual

E2S BExCP3C-PB User manual

E2S

E2S BExCP3C-PB User manual

E2S MBLD2 Series User manual

E2S

E2S MBLD2 Series User manual

Popular Security System manuals by other brands

GEV FlammEx FSR 4566 quick start guide

GEV

GEV FlammEx FSR 4566 quick start guide

Steren CCTV-095 user manual

Steren

Steren CCTV-095 user manual

Velleman HAM220 user manual

Velleman

Velleman HAM220 user manual

Strategic Vista SG14S1041 instruction manual

Strategic Vista

Strategic Vista SG14S1041 instruction manual

Aruba LS-BT20 installation guide

Aruba

Aruba LS-BT20 installation guide

Samsung SSC-21WEB user guide

Samsung

Samsung SSC-21WEB user guide

Skov DOL 2100 Technical user guide

Skov

Skov DOL 2100 Technical user guide

RTK CB10736POP1 instruction manual

RTK

RTK CB10736POP1 instruction manual

Interlogix Simon XT installation guide

Interlogix

Interlogix Simon XT installation guide

Orno OR-AB-MH-3005 manual

Orno

Orno OR-AB-MH-3005 manual

ENFORCER Enforcer Access SD-71002-V0 brochure

ENFORCER

ENFORCER Enforcer Access SD-71002-V0 brochure

Rollins VISTA-10ROSE user manual

Rollins

Rollins VISTA-10ROSE user manual

ADEMCO VISTA-20SE installation instructions

ADEMCO

ADEMCO VISTA-20SE installation instructions

Falcon TBM-18 operating instructions

Falcon

Falcon TBM-18 operating instructions

Larson Electronics SLEDB-110V-6C instruction manual

Larson Electronics

Larson Electronics SLEDB-110V-6C instruction manual

NAPCO MAGNUM ALERT 3000 FIRE ALARM installation instructions

NAPCO

NAPCO MAGNUM ALERT 3000 FIRE ALARM installation instructions

Pyronix PCX 256 Programming manual

Pyronix

Pyronix PCX 256 Programming manual

GE 45411 user manual

GE

GE 45411 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.