E2S D1 B2X05 Series User manual

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 1 of 8
INSTRUCTION MANUAL
D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21 Xenon
Beacons For use in Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON
HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
NE PAS PEINTURER
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT
DE CONDUIT DOIVENT AVOIR UN
RACCORD D'ÉTANCHÉITÉ RACCORDÉ À
MOINS DE 18 POUCES DE
L'ENFERMEMENT. POUR SUBSÉQUENT
LES CONDUITES DE CONDUIT LA
DISTANCE ENTRE LA SURFACE DE LA
MASSE DE REMPLISSAGE AU PLUS PRÈS
DE L’ENVELOPPE DOIT ÊTRE AUSSI
PETITE QUE CE QUI EST RÉALISABLE
MAIS EN AUCUN CAS SUPÉRIEURE À LA
PLUS PETITE DES DIMENSIONS
CORRESPONDANT À LA TAILLE DU
CONDUIT OU À 50 MM.
POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified as visual alarm devices for
fire alarm use –private mode only when used with Clear or
Red lens covers:
D1xB2X05DC024 / D1xB2X10DC024 / D1xB2X15DC024 /
D1xB2X21DC024
On-axis light output per UL1638:
Model
Light Intensity in cd
Clear
Lens
Red Lens
D1xB2X05DC024 - 1Hz
20.44
5.89
D1xB2X05DC024 - 1.33Hz
14.47
4.17
D1xB2X05DC024 - 1.5Hz
11.1
2.13
D1xB2X10DC024 - 1Hz
69.81
23.66
D1xB2X10DC024 - 1.33Hz
49.42
16.75
D1xB2X10DC024 - 1.5Hz
35.71
8.57
D1xB2X15DC024 - 1Hz
98.61
31.83
D1xB2X15DC024 - 1.33Hz
69.81
22.53
D1xB2X15DC024 - 1.5Hz
50.44
11.53
D1xB2X21DC024 - 1Hz
215.85
70.74
D1xB2X21DC024 - 1.33Hz
155.12
50.84
D1xB2X21DC024 - 1.5Hz
137.47
45.05
2.2 surge current ratings for use in fire alarm systems
Model
Nominal
Voltage
Voltage
Range
Flash
Rate
Peak
Surge
current
RMS
surge
current
D1xB2X05DC024
24Vdc
20-
28Vdc
1Hz
955mA
370mA
1.33Hz
960mA
370mA
1.5Hz
955mA
365mA
Double
960mA
355mA
D1xB2X10DC024
24Vdc
20-
28Vdc
1Hz
970mA
700mA
1.33Hz
970mA
700mA
1.5Hz
990mA
700mA
Double
990mA
695mA
D1xB2X15DC024
24Vdc
20-
28Vdc
1Hz
990mA
925mA
1.33Hz
990mA
930mA
1.5Hz
990mA
925mA
Double
990mA
905mA
D1xB2X21DC024
24Vdc
20-
28Vdc
1Hz
1590mA
1220mA
1.33Hz
1710mA
1240mA
1.5Hz
1590mA
1240mA
Double
1650mA
1200mA

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 2 of 8
2.3 NEC & CEC Class / Division Ratings for US / Canada
The D1xB2X Xenon beacons comply with the following
standards:
UL 1203 (Ed. 5) 2018
UL1638A (Ed. 1) 2016
UL1638 (Ed. 5) 2017
CSA C22.2 No. 30-M1986 (Ed. 3) 2016
CSA C22.2 No. 25 (Ed. 4) 2017
CSA C22.2 No. 205 (Ed. 3) 2017
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Class I Div 1 Group ABCD T5 Ta -55°C to +80°C
Class I Div 1 Group ABCD T6 Ta -55°C to +65°C
Class II Div 1 Group EFG T5 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C
Class I Div 1 Group ABCD T5 Ta -55°C to +55°C
Class I Div 1 Group ABCD T6 Ta -55°C to +40°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +80°C
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C
Class I Div 1 Group ABCD T5 Ta -55°C to +50°C
Class II Div 1 Group EFG T4 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +70°C
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3C Ta -55°C to +80°C
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +70°C
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3B Ta -55°C to +80°C
Class I Div 1 Group ABCD T3C Ta -55°C to +75°C
Class I Div 1 Group ABCD T4 Ta -55°C to +50°C
Class II Div 1 Group EFG T3C Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3C Ta -55°C to +60°C
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C
Class I Div 1 Group ABCD T4A Ta -55°C to +40°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D1xB2X Xenon beacons comply with the following
standards:
UL 60079-0 (Ed. 6) 2017
UL 60079-1 (Ed. 7) 2015
UL 60079-31 (Ed. 2) 2015
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +75°C
Class I Zone 1 AEx db IIC T6 Ta -55°C to +60°C
Zone 21 AEx tb IIIC T99°C Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +50°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +45°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 3 of 8
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +45°C
Zone 21 AEx tb IIIC T181°C Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +60°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +50°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +60°C
Installation must be carried out in compliance with the
National Electric Code.
2.5 CEC Class / Zone ratings Canada
The D1xB2X Xenon beacons comply with the following
standards:
CAN/CSA C22.2 No. 60079-0 (Ed. 3) 2015
CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016
CAN/CSA C22.2 No. 60079-31 (Ed. 2) 2015
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Ex db IIC T4 Ta -55°C to +80°C
Ex db IIC T5 Ta -55°C to +75°C
Ex db IIC T6 Ta -55°C to +60°C
Ex tb IIIC T99°C Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Ex db IIC T4 Ta -55°C to +70°C
Ex db IIC T5 Ta -55°C to +50°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Ex db IIC T4 Ta -55°C to +80°C
Ex db IIC T5 Ta -55°C to +45°C
Ex tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +70°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +80°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +70°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +80°C
Ex db IIC T4 Ta -55°C to +45°C
Ex tb IIIC T181°C Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +60°C
Ex db IIC T4 Ta -55°C to +50°C
Ex tb IIIC T153°C Ta -55°C to +60°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.6 ATEX / IECEx certification
The D1xB2X Xenon beacons comply with the following
standards:
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7)
EN60079-1:2014 / IEC60079-1 (Ed. 7) (2014)
EN60079-31:2014 / IEC60079-31 (Ed. 2) (2013)
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T104°C Db Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +70°C
Ex db IIC T5 Gb Ta -55°C to +50°C
Ex tb IIIC T116°C Db Ta -55°C to +70°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +45°C
Ex tb IIIC T135°C Db Ta -55°C to +80°C
The D1xB2X10AC115, D1xB2X10AC230, D1xB2X15AC115
& D1xB2X15AC230 Xenon Beacons are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +70°C
Ex db IIC T4 Gb Ta -55°C to +65°C
Ex tb IIIC T139°C Db Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +80°C
Ex db IIC T4 Gb Ta -55°C to +65°C
Ex tb IIIC T146°C Db Ta -55°C to +80°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +80°C
Ex db IIC T4 Gb Ta -55°C to +45°C

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 4 of 8
Ex tb IIIC T169°C Db Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +60°C
Ex db IIC T4 Gb Ta -55°C to +50°C
Ex tb IIIC T141°C Db Ta -55°C to +60°C
Certificate No. DEMKO 19 ATEX 2009X
IECEx ULD 19.0006X
ATEX Mark, Equipment
Group and Category:
CE Marking
Notified Body No.:
The units can be installed in locations with the following
conditions:
Area Classification:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur
in normal operation, and if it does, it will
only exist for a short time.
Zone 21
Explosive dust air mixture likely to occur in
normal operation.
Zone 22
Explosive dust air mixture not likely to
occur in normal operation, and if it does, it
will only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification:
T1
450ºC
T2
300ºC
T3
200ºC
(D1xB2X15DC & D1xB2X21DC
up to 80°C ambient, D1xB2X10AC
& D1xB2X15AC up to 70°C
ambient, D1xB2X21AC up to 60°C
ambient)
T4
135ºC
(D1xB2X05DC & D1xB2X10DC
up to 80°C ambient, D1xB2X05AC
up to 70°C ambient,
D1xB2X10AC, D1xB2X15DC &
D1xB2X15AC up to 65°C ambient,
D1xB2X21AC up to 50°C ambient,
D1xB2X21DC up to 45°C
ambient)
T5
100ºC
(D1xB2X05DC up to 75°C
ambient, D1xB2X05AC up to 50°C
ambient, D1xB2X10DC up to
45°C ambient)
T6
85ºC
(D1xB2X05DC up to 60°C
ambient)
Dust Groupings:
Group IIIA
Combustible Flyings
Group IIIB
Non-conductive Dust
Group IIIC
Conductive Dust
Maximum Surface Temperature for Dust Applications:
104°C (D1xB2X05DC)
116ºC (D1xB2X05AC)
135ºc (D1xB2X10DC)
139°C (D1xB2X10AC, D1xB2X15AC)
141°C (D1xB2X21AC)
146°C (D1xB2X15DC)
169ºC (D1xB2X21DC)
Equipment Category: 2G / 2D
Equipment Protection Level: Gb, Gc, Db, Dc
Ambient Temperature Range:
-55°C to +80°C (D1xB2X05DC, D1xB2X10DC,
D1xB2X15DC, D1xB2X21DC)
-55°C to +70°C (D1xB2X05AC, D1xB2X10AC,
D1xB2X15AC)
-55°C to +60°C (D1xB2X21AC)
The certification approval has validated continuous use up to
38°C ambient and are for transient use up to 80°C ambient.
2.7 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
Suitable for exposure to Acetone , Ammonium Hydroxide ,
Diethyl Ether , Ethyl Acetate , Ethylene Dichloride , Furfural,
n-hexane , Methyl Ethyl Ketone , Methanol , 2-NitroPropane
and Toluene.
To maintain the ingress protection rating, the cable entries
must be fitted with suitably rated, certified cable entry and/or
blanking devices during installation.
2.8 Electrical Ratings
#Rated at 1Hz
Table 1: Electrical Ratings
Model
Nom.
Voltage
Voltage
Range
Nom.
operating
current
Max
Current
D1xB2X05DC012
12Vdc
12-14Vdc
585
600
D1xB2X05DC024
24Vdc
20-28Vdc
295
350
D1xB2X05DC048
48Vdc
42-54Vdc
145
150
D1xB2X05AC115
115Vac
110-
120Vac
140
200
D1xB2X05AC230
230Vac
220-
240Vac
70
100
D1xB2X10DC024
24Vdc
20-28Vdc
605
710
D1xB2X10DC048
48Vdc
42-54Vdc
230
250
D1xB2X10AC115
115Vac
110-
120Vac
220
300
D1xB2X10AC230
230Vac
220-
240Vac
130
180
D1xB2X15DC024
24Vdc
20-28Vdc
835
920
D1xB2X15DC048
48Vdc
42-54Vdc
330
360
D1xB2X15AC115
115Vac
110-
120Vac
310
420
D1xB2X15AC230
230Vac
220-
240Vac
170
230
D1xB2X21DC024
24Vdc
20-28Vdc
1130
1240
D1xB2X21DC048
48Vdc
42-54Vdc
530
560
D1xB2X21AC115
115Vac
110-
120Vac
500
530
D1xB2X21AC230
230Vac
220-
240Vac
195
270
0518
II 2G
II 2D

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 5 of 8
252.3 [9.93in]
7.00 [0.28in]
45.0°
3/4" NPT SIDE ENTRY
2 OFF POSITIONS
MARKED *
M20x1.5 SIDE ENTRY
2 OFF POSITIONS
MARKED #
3/4" NPT BOTTOM ENTRY
FOR POLE MOUNTING
BEACON
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
166.0 [6.54in]
83.0 [3.27in]
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
BASE CONFIGURED WITH
FEET SET OUT FOR SURFACE MOUNTING
BEACON
Ø9.0 [Ø0.36in]
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the
units.
The input current will vary according to the voltage input
level.
3) Special Conditions of Use
The enclosure coating is non-conductive and may generate
an ignition-capable level of electrostatic charges under
certain extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be
subjected to external conditions (such as high pressure
steam) which might cause a buildup of electrostatic charges
on non-conducting surfaces. Additionally, cleaning of the
equipment should be done only with a damp cloth.
Flame Path Positions
4) Installation
There are no restrictions on unit orientation.
The junction box must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres -
Classification of areas. Explosive dust atmospheres
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
4.1 Safe Installation Requirements
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the enclosure.
If entries are fitted with adaptors they must be suitably
certified for the application. Fitting of blanking elements into
adaptors is not permitted.
Check that the ‘O’ ring seal is in place before replacing the
explosionproof cover.
Lens guard must be fitted for Class Division installations.
5) Location and Mounting
The location of the beacon should be made with due regard
to the area over which the warning signal must be visible. It
should only be fixed to services that can carry the weight of
the unit.
The D1xB2X beacon can be mounted using one of three
methods.
1. The beacon can be surface mounted by removing,
rotating and reinstalling the stowed mounting lugs. These
are suitable for 6mm diameter fixings.
a. Remove 2 x M5 fasteners per
mounting lug
b. Reverse and rotate lug and
reseat onto enclosure
c. Secure lug using the 2 x M5
Fasteners
2. Alternatively the beacon can be conduit mounted using
the ¾”NPT entry on the base of the unit.
3. Additionally, the beacon can be mounted using the
ratchet adjustable stainless-steel wall bracket assembly.
This is available as an accessory –part code: SP77-
0001.
Fig. 1 Fixing Location for Beacon
6) Access to the Enclosure
In order to connect the electrical supply cables to the beacon,
it is necessary to open the explosion proof enclosure. Loosen
the locking grub screw in the cover and then remove the
glass dome cover assembly to gain access to the chamber.
This can be achieved by unscrewing the glass dome cover,
taking extreme care not to damage the threads when doing
so.
Warning –High voltage may be present,
risk of electric shock. DO NOT open when
energised, disconnect power before
opening.
Warning –Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Flame Path internal thread on
base shown hatched
Cemented Joint
between glass
dome and metal
casting on lid
shown hatched
Flame Path
external thread
on lid shown
hatched

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 6 of 8
L
N
L L NN L L NN
L L NN
Fig. 2 Accessing the Enclosure.
On completion of the installation the flameproof threads
should be inspected to ensure that they are clean and that
they have not been damaged during installation. Ensure the
O-ring seal is in place and undamaged.
When fitting the flameproof cover ensure the thread is
engaged correctly. Fully tighten the cover all the way, ensure
no gap is visible between the cover and base of the beacon
enclosure.
7) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given
to the input current that each unit draws (see section 11), the
number of beacons on the line and the length of the cable
runs. The cable size selected must have the necessary
capacity to provide the input current to all of the beacons
connected to the line.
The entries are 2-off M20 x 1.5 thread & 3-off ¾” NPT thread
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
NPT plugs should be greased before insertion.
For high ambient temperatures the cable entry temperature
or the cable branching point temperature may exceed 60ºC
and therefore suitable heat resisting cables and cable glands
must be used, with a rated service temperature of at least the
values stated below:
8) Cable Connections
The units have 2-off M20 x 1.5 threaded entries and 3-off ¾”
NPT x 14 threaded entries.
Electrical Connections are to be made into the terminal
blocks using solid or stranded wire, sizes 0.5-2.5mm2 / AWG
20-14. Wire insulation needs to be stripped 6-7mm. Wires
may be fitted securely with crimped ferrules. Terminal screws
need to be tightened down with a tightening torque of 0.4 Nm
/ 3.5 Lb-in.
See section 5 of this manual for access to the enclosure.
9) Wiring
A 4-way terminal block is provided on the DC beacons for
power. There are 2-off +ve, 2-off –ve terminal and an internal
Earth boss.
9.1 Wiring Diagrams
Fig. 3 D1xB2X Simplified Block Diagram
Terminals
--+ +
Fig. 4 D1xB2XDC Terminals
A 5-way terminal block is provided on the AC beacons for
power. There are 2-off Live, 2-off Neutral and an Earth
terminal.
Fig. 5 D1xB2X Simplified Block Diagram
Glass dome
cover
3/4" NPT
Entry
M20 Entry
3/4" NPT
Conduit
Entry

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 7 of 8
Terminals
L L N N E
Fig. 6 D1xB2XAC Terminals
9.2 Line Monitoring
On the D2xB1X unit, DC reverse line monitoring can be used
if required.
All DC beacons have a blocking diode fitted in their supply
input lines. An end of line monitoring resistor can be
connected across the +ve and –ve terminals in the explosion
proof enclosure. If an end of line resistor is used it must have
the following values:
Minimum resistance 3K3 Ohms Minimum Power 0.5W
Minimum resistance 500 Ohms Minimum Power 2.0W
The resistor must be connected directly across the +ve and
-ve terminals as shown in the following drawing. Form the
resistor legs as shown in Fig. 7a, fit the resistor across the
two terminals, as shown in Fig. 7b.
Fig. 7a End of Line Resistor Forming
Fig. 7b End of Line Resistor Placement
10) Earthing
The unit has an external and an internal earth terminal,
(please see fig 8).
Internal earthing connections should be made to the internal
Earth terminal in the base of the housing using a ring crimped
terminal to secure the earth conductor under the earth clamp.
The earth conductor should be at least equal in size and
rating to the incoming power conductors.
External earthing connections should be made to the M5
earth stud, using a ring crimp terminal to secure the earth
conductor to the earth stud. The external earth conductor
should be at least 4mm” in size.
Fig. 8: Internal and External Earth Locations
End of Line
Resistor
Internal Earth
Terminal
External Earth
Stud

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 8 of 8
11) Settings
11.1 Flash Rate Setting
The D1xB2X beacon can produce different flash patterns as
shown in Table 1. The flash patterns are selected by
operation of the flash setting DIP switch on the PCB, Fig 9.
Note: Only 1Hz flash rate is Private Mode Fire approved
AC Units DC Units
Fig. 9: DIP Switch Location
1=ON; 0=OFF
Example shown: 10 = Flashing 1.5Hz
(Default setting is 00 1Hz)
(*Setting permitted for use as private mode fire alarm device)
Table 2: Switch Positions for Flash Patterns
12) Interchangeable & Spare Parts
The Beacon lens cover is interchangeable, contact E2S Ltd for a
replacement lens cover available in various colours.
To change the lens cover, unscrew the 4-off M5 socket head screws,
spring and flat washers using a 4mm Hex key. Remove the wire
guard and replace the old lens cover with the new lens cover.
Fig. 10 Replacement of beacon lens cover
Fit the wire guard back onto the housing, over the new lens cover
aligning the fixing holes of the guard, lens cover and housing. Refit
the fixings to hold into place, the fixings MUST be fitted in the order
shown above.
13) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19 / IEC60079-19 Explosive atmospheres -
Equipment repair, overhaul and reclamation
EN 60079-17 / IEC60079-17 Explosive atmospheres -
Electrical installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer
removed.
Flameproof joints are not intended to be repaired.
Switch
Setting
S1 Mode
00
1Hz* (60FPM)
01
1.33Hz (80FPM)
10
1.5Hz (90FPM)
11
Double Flash
Warning –Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Warning –high-intensity light source.
Avoid looking directly at the light source for
extended periods of time.
M5 screw
M5 spring washer
M5 flat washer
This manual suits for next models
7
Table of contents
Other E2S Security System manuals