Ekinex EK-GD2-TP-1-HV User manual

1
KNX 90-230 Vac 1-channel phase cut dim-
mers
Code: EK-GD2-TP-1-HV
Datasheet STEKGD2TP1HV_EN
TP1
S
Note: values for output current and nominal power
have to be intended as maximum values, depen-
ding on the ventilation conditions. The reported va-
lues are measured with a room temperature of 40
°C. For electronic loads and/or LEDs whose PFC or
harmonic distortion is not known, consider the maxi-
mum power halved compared to the nominal value.
i
REFLEKGD2TP1HV
KNX bus device with single channel phase-cut dimmer
function for lighting loads, with power supply voltage 90
- 230 Vac at 50/60 Hz. Use in KNX standard home and
building automation systems.
Description
The ekinex KNX phase-cut single channel dimmer powe-
red at 90-230 Vac EK-GD2-TP-1-HV allows the bright-
ness control of luminous loads with supply voltage 90 -
230 Vac at 50/60 Hz. The device has a maximum output
power of 230 W. The loads that can be used with the dim-
mer can be: incandescent lamps, mains voltage halogen
lamps, dimmable mains voltage LED lamps, dimmable
mains voltage LED strips, switching power supplies for
dimmable phase cut LEDs. The dimmer cuts the phase in
Trailing Edge mode (on the falling edge). The device has
an integrated KNX certied bus communication module
with SELV 30 Vdc voltage.
• Conguration of behavior after power recovery, bus
ON/OFF, download via ETS
• Status indication of the outputs through LEDs
• Block function, forced operation, staircase light, scena-
rios, night, counter and logic functions for each chan-
nel, settable by ETS
• Alarm for short circuit, open load and power failure
• Auxiliary output function with status advice via KNX
• Installer mode (only if KNX bus is present): pressing
the programming button for about 2 seconds activates/
deactivates the ashing of the programming LED and
the load every 1 s
Technical data
Inputs
• Power supply: 90 - 230 Vac 50/60 Hz
• Maximum input current: 1 A
Outputs
• Power supply: 90 - 230 Vac 50/60 Hz
• Output power 110 W @ 110 Vac, 220 W @ 220 Vac,
230 W @ 230 Vac
• Minimum load power: 1 W
• Maximum output current: 1 A
Dimming
• Trailing edge dimming mode with open load control
(OPEN CIRCUIT) and short circuit on the load (SHORT
CIRCUIT)
• Dimming range: 1-100%
Environmental conditions and other characteristics
• Operating temperature: - 20 ° C ... + 40 ° C
• Storage temperature: - 40 ° C ... + 60 ° C
• Transport temperature: - 40 ° C ... + 60 ° C
• Maximum case temperature (tc): 80 °C
• Relative humidity: 91% non-condensing
• Protection degree: IP00
• Loads and supply wiring: 1.5 mm2solid – 2.5 mm2
stranded (16 - 13 AWG)
• Max torque 0.5 Nm for screw terminals
• KNX bus wiring: 0.26 ÷ 0.5 mm2 – 23 ÷ 20 AWG
• Stripping: 5.0 - 6.0 mm
• Housing in plastic material
• Device suitable for installation in ush-mounting wall
boxes
• Weight 37 g
• Dimensions (LxHxW): 53 x 61 x 29 mm
Main functional characteristics
• ON/OFF control and regulation of the luminous intensi-
ty of single or group lighting xtures
• Fade time on and o, minimum and maximum bright-
ness level, linear or logarithmic regulation curve setta-
ble via ETS
• Soft or instant on and o, with settable delay
Protections
• OVP Input voltage peak protection
• RVP Overcurrent protection with 3 A non-resettable
fuse
• OCP Output open circuit protection

2
Setup and installation
The steps to setup the device are as follows:
1. Connect the loads to the AC OUT ( -x, N) terminals
of the device
2. Connect the KNX bus to the corresponding terminal of
the device
3. Connect the 90 - 230 Vac power supply to the AC IN (L,
N) terminals of the device
Accessories
Rail-mounting support
The device EK-GD2-TP-1-HV can be mounted on 35 mm
rail (according to EN 60715) with the plastic support inclu-
ded in the delivery.
Before removing the device, make sure that inputs, ou-
tputs, and the AC power supply have been disconnected.
When assembling, make sure to leave only the front pa-
nel accessible; all other sides must not be accessible. For
the mounting proceed as follows:
• Insert the mounting support in the appropriate shaped
prole of the back side of the device
• then hook the teeth to the prole guide starting from
the bottom
• nally, push the upper part towards the guide for nal
coupling.
Before removing the device, be sure that inputs, outputs,
and the input power supply have been disconnected. Use
a screwdriver to slide down the locking device and remo-
ve the device from the rail.
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
i
Control, signaling and connection elements
The device is equipped with a screw terminal for connec-
ting the 90 - 230 Vac output loads (1), the 90 - 230 Vac
input power supply (2), a screw terminal for connecting
the KNX bus line (4) and a KNX programming / test but-
ton with a LED under the cover (5) . The pair of terminals
(3) is not used.
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
AC OUT
N N L
AC IN
1
4
2
3
5
EK-GD2-TP-1-HV
Mounting
The devices have degree of protection IP00 and are the-
refore suitable for use in dry interior rooms.
The 1-channel model is suitable for installation in wall-
mounting boxes. The plastic support allows mounting on
a prole rail according to EN 60715 inside electrical distri-
bution panels and cabinets.
Nr. Label Connection
1 AC Output - Live
AC OUT (N) AC Output - Neutral
2 AC IN (N) AC Input - Neutral
AC IN (L) AC Input - Live
3 - Not used
4 - KNX bus terminal
5 - Test / KNX programming button and LED
KNX bus line connection
The connection to the bus network takes place via the
KNX terminal included in the delivery and inserted in the
special housing located on the front of the device in the
upper part.
Characteristics of the KNX terminal block
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire
conductors and diameter between 0.6 and 0.8 mm
• recommended wire stripping approx. 5 mm
• color codication: red = + (positive) bus conductor,
black = − (negative) bus conductor

3
Connection of loads and power supply
The connection to the 90-230 Vac 50-60Hz power supply
is done via the screw terminals located in the lower part
of the device.
Characteristics of the supply and loads terminal block
• Screw tightening of the conductors
• Power and loads wiring: 1.5 mm2solid – 2.5 mm2stran-
ded – 16 - 13 AWG
• Stripping recommended approx.: 5.0 - 6.0 mm
• Max torque 0.5 Nm for screw terminals
Warning! The electrical connection of the appliance
must be carried out exclusively by qualied person-
nel. Incorrect installation can cause electrocution or
re. Before making the electrical connections, make
sure you have deactivated the mains voltage.
!
!
INSTALLATION TECHNICAL NOTES
• Installation and maintenance must be
performed only if the power supply has
been turned o.
• Installation and maintenance must only
be performed by qualied personnel in
compliance with current regulations.
• The product must be installed inside
a wall mounting box or an electrical pa-
nel, where it is recommended to install a
surge protector.
• The product must be protected by a sui-
tably sized fuse.
• The product must be protected by a su-
itably sized magnetothermic switch on
the main input line.
• The product must be installed in a verti-
cal position with the front / label facing
the front or in a horizontal position with
the front / label facing upwards. Other
product installation positions are not
allowed.
• Do not connect inductive loads.
• Do not connect to UPS (uninter-
ruptible power supply) with ou-
tput other than Pure Sine Wave.
The device is not grounded. Protection
from accidental contacts is guaranteed
by the casing.
• Use in thermally harsh environments
could limit the output power.
• In the system, keep the 90-230Vac circu-
its and the non-SELV circuits separate
from the SELV circuits at very low safety
voltage and from the KNX bus
• It is absolutely forbidden to connect, for
any reason whatsoever, directly or indi-
rectly, the 90-230Vac mains voltage to
the KNX bus or to the loads.
• Use double insulated cables.
Warning! To power the KNX bus lines, use exclusi-
vely KNX bus power supplies (e.g. ekinex EK-AB1-
TP, EK-AG1-TP or EK-AM1-TP). The use of other
power devices can compromise communication
and damage the devices connected to the bus.
!
Outputs
The cables connected to the outputs must be correctly
sized and must be isolated from any wiring or parts with
dierent voltages. The length and type of connection ca-
bles must comply with the regulations in force.
Conguration and commissioning
The conguration and commissioning of the device re-
quires the use of the ETS® (Engineering Tool Software)
V5 program or later versions. These activities must be
carried out in accordance with the design of the building
automation system created by a qualied professional.
To congure the device parameters, the corresponding
application program or the entire ekinex® product data-
base must be loaded into the ETS® program. For detailed
information on the conguration possibilities, consult the
application manual of the appliance available on the web-
site www.ekinex.com.
Installation diagrams
The device can be installed according to the following
schemes:
1. “Classic” 4-wire connection
KNX
bus
90-230 Vac
50-60 Hz
L
+
-
N
AC OUT
NNL
AC IN
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
“Classic” 4-wire connection diagram

4
Note. The conguration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tied training centers.
i
2. Four-wire connection with phases and neutral reversed
Not having phase and neutral references, the device can
also be connected by inverting all the phases with the
neutral:
3. Three-wire connection with common neutral
This 3-wire conguration is useful for connecting loads in
systems with phase/neutral already connected.
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton (5) loca-
ted on the front side of the housing. In this operating
mode, the programming LED is turned on;
• download into the device the physical address and the
conguration with the ETS®program.
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned o. Now the bus device is
programmed and ready for use.
Device reset
To reset the device, remove the power from the KNX bus;
then press the programming button and, keeping it pres-
sed, restore power to the KNX bus: if, after approximately
10 s, the programming LED ashes quickly, it means that
the reset has been carried out. At this point it is necessary
to re-address and congure the device via ETS.
Warning! The reset operation brings back the devi-
ce to its factory delivery state. The addressing and
value of the parameters set during conguration are
lost.
!
90-230 Vac
50-60 Hz
L
N
KNX
bus +
-
AC OUT
NNL
AC IN
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
Four-wire connection diagram with
phases and neutral reversed
KNX
bus
90-230 Vac
50-60 Hz
L
+
-
N
AC OUT
NNL
AC IN
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
Three-wire connection diagram with common neutral

5
@220 V 50/60 Hz
SYMBOL LOAD TYPE MAX
POWER MODE CURVE
Halogen or incandescent bulbs (230V ~ 50/60Hz) 230 W TE Linear
Ferromagnetic transformers (Halogen bulbs at 12/24V ~ 50/60Hz) Incompatible
Electronic transformers (Halogen bulbs 12/24V ~ 50/60Hz) 115 W TE Logarithmic
Dimmable LED lamps (230V ~ 50/60Hz) 115 W TE Logarithmic
Lamp power supplies LED (230V ~ 50/60Hz) 115 W TE Logarithmic
LED strip (230V ~ 50/60Hz) 230 W TE Linear /
logarithmic
Energy saving lamps (ESL/CFL) Incompatible
Warning! Never connect the transformer wi-
thout rst having connected the load on the se-
condary, to avoid overvoltages that are destruc-
tive to the appliance.
!
TE = Trailing Edge
@110 V 50/60 Hz
SYMBOL LOAD TYPE MAX
POWER MODE CURVE
Halogen or incandescent bulbs (230V ~ 50/60Hz) 110 W TE Linear
Ferromagnetic transformers (Halogen bulbs at 12/24V ~ 50/60Hz) Incompatible
Electronic transformers (Halogen bulbs 12/24V ~ 50/60Hz) 55 W TE Logarithmic
Dimmable LED lamps (230V ~ 50/60Hz) 55 W TE Logarithmic
Lamp power supplies LED (230V ~ 50/60Hz) 55 W TE Logarithmic
LED strip (230V ~ 50/60Hz) 110 W TE Linear /
logarithmic
Energy saving lamps (ESL/CFL) Incompatible
Summary table of load types depending on the input power supply

6
Product
code
Application program
(## = release)
Communica-
tion objects
(nr. max)
Group ad-
dresses
(nr. max)
EK-GD2-TP-1-HV
APEKGDXTPXHV##.knxprod
27 27
Dimensions [mm]
Marks
• KNX
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/EU), the Low Volta-
ge Directive (2014/35/EU) and the RoHS 2 Directive
(2011/65/EU).
• Reference Standards: EN 63044-5-1:2019, EN 63044-
5-2:2019, EN 63044-3:2017, EN 62368-1:2020.
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Disposal
At the end of its useful life the product
described in this datasheet is classied
as waste from electronic equipment in
accordance with the European Directive
2012/19/EU (WEEE recast), and cannot
be disposed together with the municipal
undierentiated solid waste.
Document
This technical datasheet refers to the A1.0 release of the
ekinex® device code. EK-GD2-TP-1-HV and is available
for download on the website www.ekinex.com in PDF for-
mat (Portable Data Format).
Warnings
• Installation, electrical connection, conguration and
commissioning of the device can only be carried out by
qualied personnel in compliance with the applicable
technical standards and laws of the respective countri-
es
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the essential
requirements of the applicable directives, for which the
device has been certied, is no longer guaranteed
• ekinex®KNX defective devices must be returned to the
manufacturer at the following address: EKINEX S.p.A.
Via Novara 37, I-28010 Vaprio d’Agogna (NO) Italy
Other information
• This datasheet is aimed at installers, system integra-
tors and planners
• For further information on the product, please contact
the ekinex®technical support at the e-mail address:
com
• Each ekinex®device has a unique serial number on
the label. The serial number can be used by installers
or system integrators for documentation purposes and
has to be added in each communication addressed to
the EKINEX technical support in case of malfunctioning
of the device
• KNX®and ETS®are registered trademarks of KNX As-
sociation cvba, Brussels
© EKINEX S.p.A. The company reserves the right to make changes to this
documentation without notice.
Warning! Incorrect disposal of this product may
cause serious damage to the environment and
human health. Please be informed about the
correct disposal procedures for waste collec-
ting and processing provided by local authori-
ties.
!
52.80
60.70 28.55
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
AC OUT
N N L
AC IN
52.80
60.70 28.55
Ekinex S.p.a. Via Novara, 37
28010 Vaprio d’agogna NO - Italy
EK-GD2-TP-1-HV
IN: 90-230 VAC 50/60Hz
OUT: 1A
Made in Italy
AC OUT
N N L
AC IN
Table of contents
Other Ekinex Dimmer manuals

Ekinex
Ekinex EK-GD2-TP-1-HV Instructions for use

Ekinex
Ekinex EK-GH1-DL User manual

Ekinex
Ekinex EK-GO1-DL User manual

Ekinex
Ekinex EK-GD1-DL-4-HV User manual

Ekinex
Ekinex KNX 90-230 Operating and safety instructions

Ekinex
Ekinex EK-GM2-DL User manual

Ekinex
Ekinex EK-GA1-TP Instructions for use

Ekinex
Ekinex EK-GL1-DL User manual
Popular Dimmer manuals by other brands

Lutron Electronics
Lutron Electronics QSNE-4A-D installation guide

YORKVILLE
YORKVILLE LP302 manual

LEGRAND
LEGRAND adorne WNAL63 installation instructions

LEGRAND
LEGRAND Arteor 5740 08/58 manual

EUCHIPS
EUCHIPS Walldim 105 quick start guide

EnvironmentalLights.com
EnvironmentalLights.com Dim-MiniLine product manual