Ekinex EK-GL1-DL User manual

1
REFLEKGL1DL
DALI 4-channel dimmer
Code: EK-GL1-DL
Technical data
Inputs
• Input (constant voltage): 12 / 24 / 48 Vdc
• Supply voltage: min: 10,8 Vdc .. max: 52,8 Vdc
• Input current: 20 A max
• Power absorbed while awaiting command: <500 mW
Outputs
• Output voltage = input voltage
• Output current: max 5 A / channel, max 20 A total
• Nominal power @12V: 60 W / channel – 240 W total
• Nominal power @24V: 120 W / channel – 480 W total
• Nominal power @48V: 240 W / channel – 960 W total
• Thermal shutdown: 150 °C
DALI bus device to be supplied with 12 / 24 / 48 Vdc. It
provides the dimming control function for LED sources, by
means for several commands: KNX pushbuttons or other
local command devices.
Datasheet STEKGL1DL_EN
S
Note: values for output current and nominal power
have to be intended as maximum values, depen-
ding on the ventilation conditions
i
Description
The ekinex DALI 4-channel dimmer EK-GL1-DL allows
brightness control of dimmable LED sources by means
of several types of button. It can be connected by me-
ans of KNX (TP) pushbutton connected to a DALI / KNX
Gateway or via another device, directly connected to the
dedicated input, selectable from a normally open button,
0-10V analog input, 1-10V analog input and 10 kΩ poten-
tiometer. The device has an integrated DALI bus com-
munication module and requires a 12, 24 o 48 Vdc input
power supply.
Functional characteristics
• Constant voltage dimmer
• DALI bus command
• Number of channels: 4
• 4 local commands: N.O. pushbutton / analog input
0-10V / 1-10V / Potentiometer
• Controls: dimmer, dim to warm, tunable white, RGB,
RGBW
• Voltage outputs for R-L-C loads
• Typical eciency > 95%
• Brightness adjustment up to full o (Dim to Dark)
• Minimum brightness level: 0.1% (1% in push)
• D-PWM Modulation
• Adjusting D-PWM frequency: 300 / 600 / 1200 Hz
• Adjusting output curve: Linear / Quadratic / Exponential
• Soft dimming regulation
• Soft start and soft stop
Dimming
• Dimming frequency D-PWM: 300Hz – 600Hz – 1200Hz
• Dimming resolution D-PWM: 16 bit
• Dimming range D-PWM: 0.1-100%
Environmental conditions and other characteristics
• Operating temperature: -40 ° C ... + 60 ° C
• Storage temperature: - 40 ° C ... + 60 ° C
• Transport temperature: - 40 ° C ... + 60 ° C
• Relative humidity: 93% non-condensing
• Protection degree IP10 (device installed)
• Command & bus wiring: 1.5 mm2solid – 1 mm2stran-
ded – 30/14 AWG
• Power & LEDs wiring: 2. 5mm2solid – 1.5 mm2stran-
ded – 30/12 AWG
• Command & bus stripping: 6 mm
• Power and LEDs stripping: 7.5 mm
• Housing in plastic material
• Safety class II
• Weight 120 g
• Modular device 4 MU (1 MU = 18 mm)
• Dimensions 72 x 90 x 70 mm (LxHxP)
Protections
Il dispositivo è dotato delle seguenti protezioni:
• OTP Over temperature protection1
• OVP Over voltage protection2
• UVP Under voltage protection2
• RVP Reverse polarity protection2
• IFP Input fuse protection2
• SCP Short circuit protection
• OCP Open circuit protection
• CLP Current limit protection
1) Thermal Protection on the output channel in case of high temperature. The thermal
intervention is detected by transistor (>150°C)
2) Control logic protection only
Control, signaling and connection elements
The device is equipped with a screw terminal for connec-
ting the 12 / 24 / 48 Vdc input power supply and the LED
output loads (1), a screw terminal for connecting the local
commands (2), a screw terminal for the DALI line connec-
tion (3) and one signaling LED (4).

2
Terminal blocks for connection of inputs and outputs
Mounting
The device has degree of protection IP10, and is therefore
suitable for use in dry interior rooms. The housing is made
for rail mounting according to EN 60715 in boards or ca-
binets for electrical distribution. The correct mounting is
when the input Vdc supply screw terminal is located at the
bottom. When installing be sure to leave accessible only
the front panel; all other sides must not be accessible. For
the mounting proceed as follows:
• with the aid of a tool bring the locking device in the fully
lowered position (a);
• place the upper edge of the rear inner prole on the
upper edge of the rail (b);
• rotate the device towards the rail (c);
• push the locking device upward until it stops (d).
Before removing the device, be sure that inputs, outputs,
and the input power supply have been disconnected. Use
a screwdriver to slide down the locking device and remo-
ve the device from the rail.
1) Screw terminal for 12/24/48 Vdc input and output loads
2) Screw terminal for local commands connection
3) Screw terminal for DALI line connection
4) Signaling LED
- -
OUT
L2- L3-
Dimmer LED
EK-GL1-DL
DC In: 12-48V
Imput: Push, 0/1-10V
Out: 4x max 5A
1
2
4
3
Nr. Mark Connection
1-3 DC IN + DC + input
2-4 DC IN - DC - input
5 OUT - L1+ Load 1 output - pole +
6 OUT - L1- Load 1 output - pole -
7 OUT - L2+ Load 2 output - pole +
8 OUT- L2- Load 2 output - pole -
9 OUT - L3+ Load 3 output - pole +
10 OUT - L3- Load 3 output - pole -
11 OUT - L4+ Load 4 output - pole +
12 OUT - L4- Load 4 output - pole -
Note: in the event of total output current higher
than 10 A, both power input pairs “V+” and “V-“
must be connected to the supply.
i
Nr. Mark Connection
1-3-5-7 IN1-2-3-4 Local command 1,2,3,4 input - pole 1
2-4-6-8 0V Local command 1,2,3,4 input - pole 2
Nr. Mark Connection
1 DA-DALI IN
DALI pole 1
4 DA-DALI OUT
2 DA-DALI IN
DALI pole 2
5 DA-DALI OUT
3-6 - Not used

3
The 12-way dip-switch setting (under the front cover) of-
fers a wide choice of possible congurations.
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
i
a b
dc
INSTALLATION TECHNICAL NOTES
• Installation and maintenance must be
performed only if the power supply has
been turned o.
• Installation and maintenance must only
be performed by qualied personnel in
compliance with current regulations.
• The product must be installed insi-
de an electrical panel protected against
overvoltages.
• The product must be installed in a verti-
cal position with the front / label facing
the front or in a horizontal position with
the front / label facing upwards. Other
product installation positions are not al-
lowed. The bottom position with the front
panel / label facing down is not allowed.
• Keep separated the circuits at 230V (LV)
and the circuits not SELV from circuits
to low voltage (SELV) and from any con-
nection with this product. It is absolutely
forbidden to connect, for any reason
whatsoever, directly or indirectly, the
230V mains voltage to the bus or to other
parts of the circuit.
!
Setup and installation
In order to setup the dip-switches and the rotary selector
switches, it is necessary to open the device front cover,
by means of a screwdriver as detailed in the image below.
Conguration Settings
Switches 1-2 = Load type
Switch 3 = Parallel outputs
Switches 4-5-6 = Map
Switches 7-8 = Dimming curve
Switches 9-10 = Input type (local
commands)
Switches 11-12 = Dimming fre-
quency (output frame rate)
Note: Factory settings = all OFF
DALI bus line and command connections
The connection to the DALI bus line and the local com-
mands is done via the screw terminal, located on the front
of the device in the upper part.
The length of the connection cables between the local
commands (N.O. Pushbutton, 0-10V, 1-10V, Potentiome-
ter or other) and the product must be less than 10m; the
cables must be dimensioned correctly and they should be
isolated from every wiring or parts at voltage not SELV.
Use double insulated shielded and twisted cables.
The length and type of the connection cables to the DALI
bus must be compliant with the protocol specication and
with the present regulations and they should be isolated
from every wiring or parts at voltage not SELV. Use dou-
ble insulated shielded and twisted cables.
All the devices and the control signal connected to the
DALI bus and to the local command (N.O. Pushbutton,
0-10V, 1-10V, Potentiometer or other) must be SELV (the
devices connected must be SELV or supply a SELV si-
gnal).
Characteristics of the DALI terminal block
• Screw tightening of the conductors
• Command & bus wiring: 1.5 mm2solid – 1 mm2stran-
ded – 30 - 14 AWG
• Command & bus stripping: 6 mm
• Conductor stripping recommended approx. 10 mm
• Maximum length of the connection between dimmer-
driver and control device < 10 m
• Length of connection cables < 10 m
Connection of power supply and LEDs
For the power supply use SELV power suppliers with li-
mited current, short circuit protection only and the power
must be correctly dimensioned. In case of usage of a po-
wer supplier with ground terminals, all points of the pro-
tective earth (PE = Protection Earth) must be connected
to a valid and certied protection earth.
The connection cables between the power source “low
voltage” and the product must be correctly dimensioned
and they should be isolated from every wiring or parts at
not-SELV voltage. Use double insulated cables.
The power supply must be dimensioned according to
the load connected to the device. If the power supply is
oversized with respect to the maximum absorbed current,
then insert a protection against over-current between the

4
3. random address allocation: by connecting all the bal-
lasts at the same time, each one will get a random
address.
Subsequently, the address conguration can be changed
by using an application for parameterization, for example
by downloading the ekinex CGEKBG1TP software to your
PC which allows to:
• congure the DALI system and dene its parameters;
• set the DALI luminaires (groups, scenarios, IDs, etc.);
• test the communication on the DALI bus;
• update the device.
The software can be downloaded from www.ekinex.com
website and its use is described in the application manual
of the ekinex EK-BG1-TP DALI Gateway. The software
requires Microsoft Windows (7 and later).
power supply and the device.
Characteristics of the supply and LEDs terminal block
• Screw tightening of the conductors
• Power & LEDs wiring: 2. 5mm2solid – 1.5 mm2stran-
ded – 30 - 12 AWG
• Power and LEDs stripping recommended approx.: 7.5
mm
• Max torque 0.5 Nm
Outputs
The length of the connection cables between the dimmer
and the LED module must be less than 10m; the cables
must be correctly dimensioned and they should be isola-
ted from every wiring or parts at not-SELV voltage. It is
preferable to use double insulated shielded and twisted
cables.
In case it is needed to connect the device and LED mo-
dules with cables longer than 10m, the installer must gua-
rantee the correct functioning of the system. In any case,
do not exceed 30m of the connection between the device
and the LED modules.
SUPPLY
+
L N
230 Vac
12-48 Vdc
50-60 Hz
+
DALI
- -
OUT
L2- L3-
Dimmer LED
EK-GL1-DL
DC In: 12-48V
Imput: Push, 0/1-10V
Out: 4x max 5A
Installation scheme
Conguration and commissioning
Conguration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by a qualied planner.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the bus;
• carry out the device addressing, which can be done in
three ways:
1. by means of rotary selector switches (positioned be-
low the front cover);
2. simplied method: by connecting one ballast at a
time, each one will get the address progressively
from 0 to 63;
Note. In order to install and use the CGEKBG1TP
conguration software, it could be necessary the
installation of .NET Framework 4, which can bee
freely downloaded from Microsoft.com website.
i
Signaling LED
On the device front panel a signaling LED is present. If
there is no BUS power supply or there is a BUS error,
the signaling LED ashes quickly (2 pulses per second).
If there is BUS power supply but a BUS error occurs, the
signaling LED ashes slowly (1 pulse per second). If the
BUS signal is connected and working correctly, the LED
remains on steady.
Relationship with local commands: on power-up, in case
the bus connection is not present, the local command is
active. When the BUS connection is detected, the con-
trol passes to the BUS as long as the signal is present.
In the absence of the signal, if the local command is an
N.O.button, the control is passed to the local commands
when a N.O. button is pressed. On the other hand, if the
local command is 0-10V or 1-10V, the control immediately
passes to the local command.
Dimensions [mm]
111
62.00
91.00
71.00

5
nufacturer at the following address: Ekinex S.p.A. Via
Novara 35, I-28010 Vaprio d’Agogna (NO) Italy
Other information
• The instruction sheet must be delivered to the end cu-
stomer with the project documentation
• For further information on the product, please contact
the ekinex®technical support at the e-mail address:
com
• Each ekinex®device has a unique serial number on the
label. The serial number can be used by installers or sy-
stem integrators for documentation purposes and has
to be added in each communication addressed to the
EKINEX technical support in case of malfunctioning of
the device
• KNX®and ETS®are registered trademarks of KNX As-
sociation cvba, Brussels
© EKINEX S.p.A. The company reserves the right to make changes to this
documentation without notice.
Marks
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/EU) and the RoHS 3
Directive (2011/65/EU and 2015/863/EU).
• Reference Standards: EN
61347-1:2008+A1:2011+A2:2013, EN 61347-1:2015,
EN 55015:2013+A1:2015, EN 61547:2009
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Warning! Incorrect disposal of this product may
cause serious damage to the environment and hu-
man health. Please be informed about the correct
disposal procedures for waste collecting and pro-
cessing provided by local authorities.
!
Disposal
At the end of its useful life the product
described in this datasheet is classied
as waste from electronic equipment in
accordance with the European Directive
2012/19/EU (WEEE recast), and cannot
be disposed together with the municipal
undierentiated solid waste.
Warnings
• Installation, electrical connection, conguration and
commissioning of the device can only be carried out by
qualied personnel in compliance with the applicable
technical standards and laws of the respective countri-
es
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the essential
requirements of the applicable directives, for which the
device has been certied, is no longer guaranteed
• ekinex® defective devices must be returned to the ma-
111
62.00
91.00
71.00

6
Appendix A: setting
Settings of the load types and parallel outputs, depending
on the selected output connections:
Switches 1, 2, 3
Load type Description Connection
(total current 0 - 10A max)
Connection
(total current 0 - 20A max)
Settings
White, up to 4 loads
White, parallel outputs with the
highest current, single channel
at 10 A max or 20 A max (Ma-
cro dimmer)
Dynamic white, up to 2 loads
Dynamic white, pair of parallel
outputs with the highest current
RGB
RGBW
The Map has to be set depending on the load and the
requested function. Details are reported in the “Map set-
tings” section.

7
Map settings:
Switches from 4 to 6
White load Dynamic white load RGB load RGBW load
Dimmer Dimmer Dimmer Dimmer
Dim to warm Dim to warm Dim to warm
Dynamic
white
Dynamic
white
Dynamic
white
Smart HSV
Intensity, tempe-
rature correction,
color selection
and rotation,
saturation and
strobo
Smart HSV
Intensity, tempe-
rature correction,
color selection
and rotation,
saturation and
strobo
RGB RGB
RGBW
RGBW→RGB
conversion
RGBW
RGBW→RGB
conversion
Master
+ RGB +
Strobe
Master
+ RGB +
Strobe
Master
+ RGB +
Strobe
RGBW→RGB
conversion
Master
+ RGB +
Strobe
RGBW→RGB
conversion
Dimming curve settings:
Switches from 7 to 8
Default Quadratic Exponential Linear

8
Local command settings:
Switches from 9 to 10
Command
type
Description Connections Settings
Pushbutton N.O. pushbutton,
without memory
N.O. pushbutton,
with memory
0-10 V Analog input
0-10V
1-10 V Analog input
1-10V & Potentio-
meter
Dimming frequency settings:
Switches from 11 to 12
300 Hz 600 Hz 1200 Hz Reserved

9
Appendix B: addressing by means of rotary
selector switches
Addresses Selector positions Meaning
000 (default) Address is set through bus
DALI
from 001 to 064 Address is set by following
the DALI protocol, from 0
to 63
FFF (reserved)
Table of contents
Other Ekinex Dimmer manuals

Ekinex
Ekinex KNX 90-230 Operating and safety instructions

Ekinex
Ekinex EK-GH1-DL User manual

Ekinex
Ekinex EK-GO1-DL User manual

Ekinex
Ekinex EK-GD1-DL-4-HV User manual

Ekinex
Ekinex EK-GD2-TP-1-HV Instructions for use

Ekinex
Ekinex EK-GM2-DL User manual

Ekinex
Ekinex EK-GA1-TP Instructions for use

Ekinex
Ekinex EK-GD2-TP-1-HV User manual