Ekinex EK-GM2-DL User manual

1
REFLEKGM2DL
DALI 1-channel dimmer
Code: EK-GM2-DL
Technical data
Inputs
• Input (constant voltage): 12 / 24 Vdc
• Supply voltage: min: 10.8 Vdc .. max: 26.4 Vdc
• Power absorbed while awaiting command: <500 mW
Outputs
• Output voltage = input voltage
• Output current: max 10 A @40°C
• Nominal power @12V: 120 W
• Nominal power @24V: 240 W
• Command supply current: 0.5mA (for 1-10V)
• Command required current (max): 0.1 mA (for 0-10V)
DALI bus dimmer with 12/24 Vdc power supply, it pro-
vides LED sources brightness control function. Dimming
can can be managed by using dierent types of comman-
ds: KNX buttons or other local control devices. The device
is suitable for installation in ush-mounting wall boxes.
Datasheet STEKGM2DL_EN
S
Note: the factory default values are: automatic de-
tection of the local command set to N.O. pushbutton
and minimum dimming value set to 1%.
i
Description
The ekinex DALI 1-channel dimmer EK-GM2-DL allows
brightness control of dimmable LED sources by means of
several kinds of button. It can be connected by means of
KNX (TP) pushbutton connected to a DALI / KNX Gate-
way or via another command device, directly connected
to the dedicated input, selectable from a normally open
button, 0-10V analog input, 1-10V analog input and 10 kΩ
potentiometer. The device has an integrated DALI bus
communication modules voltage and requires a 12 or 24
Vdc auxiliary power supply.
Functional characteristics
• Constant voltage dimmer, 1 channel
• DALI bus command
• Local command: N.O. pushbutton / analog input 0-10V
/ 1-10V / 10 kΩ Potentiometer
• Analog automatic detection of the local command
• Brightness adjustment for LED loads
• Voltage output for R loads
• Typical eciency > 95%
• Brightness adjustment up to full o (Dim to Dark)
• Brightness adjustment of white light or monochromatic
color
• Minimum value of dimming: 0.1% (1% Push)
• Memory function: it stores the last brightness level in
case of a power failure
• Possibility to set minimum dimming, Fade-in and Fade-
Out (Push menu)
• Optimized output curve
• Soft start and soft stop
Dimming
• Dimming frequency D-PWM: 300Hz
• D-PWM resolution: 16 bit
• D-PWM dimming range: 0.1-100%
Environmental conditions and other characteristics
• Operating temperature: -10 ° C ... + 40 ° C
• Storage temperature: - 40 ° C ... + 60 ° C
• Transport temperature: - 40 ° C ... + 60 ° C
• Relative humidity: 93% non-condensing
• Protection degree IP20 (device installed)
• Wiring: 1.5 mm2solid – 1.0 mm2stranded – 16- 17 AWG
• Stripping: 5.0 - 6.0 mm
• Housing in plastic material
• Device suitable for installation in ush-mounting wall
boxes
• Safety class II
• Weight 37 g
• Dimensions 43 x 43 x 23 mm (LxHxP)
1) Control logic protection only
Note: values for output current and nominal power
have to be intended as maximum values, depen-
ding on the ventilation conditions. The reported
values are measured with a room temperature of
40 °C.
i
Protections
The device is provided with the following protections:
• OVP Over voltage protection1
• UVP Under voltage protection1
• RVP Reverse polarity protection1
• IFP Input fuse protection1
• OCP Open circuit protection

2
Accessories
Rail-mounting support
The device can be mounted on 35 mm rail (according to
EN 60715) with the support EK-SMG-35 to be ordered
separately.
Mounting
The device has degree of protection IP20, and is there-
fore suitable for use in dry interior rooms. The support
EK-SMG-35 allows the mounting on 35 mm rail in boards
or cabinets for electrical distribution.
Control, signaling and connection elements
The device is equipped with a screw terminal for connec-
ting the 12 / 24 Vdc input power supply and the output
loads (1), a screw terminal for connecting the local com-
mands and the DALI line (2).
EK-SMG-35
Spring for hooking on wall-mounting devices
The device can be hooked on the back of some ekinex®
wall-mounting devices by means of the spring EK-MAR
to be ordered separately (preventively check the compa-
tibility).
EK-MAR
1
2
1) Screw terminal for 12/24 Vdc input and output loads
2) Screw terminal for local commands and DALI LINE connections
Terminal blocks for connection of inputs and outputs
Nr. Mark Connections
1 DC IN + DC (+) input
2 DC IN - DC (-) input
3 OUT L+ Output (+)
4 OUT L- Output (-)
Nr. Mark Collegamento
1-2 - Not used
3-4 INPUT
IN-COM
N.O. Pushbutton input, analogic input or
potentiometer
5 DA-DALI IN DALI pole 1
6 DA-DALI IN DALI pole 2
a) Insert the mounting support into the appropriate shaped prole of the
interface

3
Setup and installation
The steps to setup the device are as follows:
1. connect the load LEDs to the output terminal blocks
“OUT” of the device.
2. connect the local command to INPUT terminal blocks
and / or connect the DALI bus to the related terminal
blocks;
3. connect the 12/24 Vdc power supply to the terminal
blocks “DC IN” of the device.
As an alternative to using local commands, a DALI / KNX
Gateway can be connected to a KNX pushbutton.
INSTALLATION TECHNICAL NOTES
• Installation and maintenance must be
performed only if the power supply has
been turned o.
• Installation and maintenance must only
be performed by qualied personnel in
compliance with current regulations.
• The product must be installed insi-
de an electrical panel protected against
overvoltages.
• The product must be installed in a verti-
cal position with the front / label facing
the front or in a horizontal position with
the front / label facing upwards. Other
product installation positions are not al-
lowed. The bottom position with the front
panel / label facing down is not allowed.
• Keep separated the circuits at 230V (LV)
and the circuits not SELV from circuits
to low voltage (SELV) and from any con-
nection with this product. It is absolutely
forbidden to connect, for any reason
whatsoever, directly or indirectly, the
230V mains voltage to the bus or to other
parts of the circuit.
!
Before removing the device, be sure that inputs, outputs,
and the DC power supply have been disconnected. By
using a screwdriver, slide the locking device down and
remove the device from the prole rail.
DALI bus line and command connections
The connection to the DALI bus network and the local
commands is done via the screw terminal, located on the
front of the device in the upper part.
The length of the connection cables between the local
commands (N.O. Pushbutton, 0-10V, 1-10V, Potentiome-
ter or other) and the product must be less than 10m; the
cables must be dimensioned correctly and they should be
isolated from every wiring or parts at voltage not SELV.
Use double insulated shielded and twisted cables.
The length and type of the connection cables to the DALI
bus must be compliant with the protocol specication and
with the present regulations and they should be isolated
from every wiring or parts at voltage not SELV. Use dou-
ble insulated shielded and twisted cables.
All the devices and the control signal connected to the
DALI bus and to the local command (N.O. Pushbutton,
0-10V, 1-10V, Potentiometer or other) must be SELV (the
devices connected must be SELV or supply a SELV si-
gnal).
Characteristics of the DALI terminal block
• Screw tightening of the conductors
• Command & bus wiring: 1.5 mm2solid – 1.0 mm2stran-
b) Place the support clamping tooth on the top edge of the mounting
rail and rotate device and support towards the guide until it completely
engages
c) Once fastened, connect the bus line, the inputs and the outputs
Installation scheme
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
i

4
Conguration and commissioning
Conguration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by a qualied planner.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the bus;
• carry out the device addressing, as described in the
next paragraphs.
Local command
Depending on the local control, the device can manage
dierent functions on the output loads.
Push dimmer
The intensity and the status change (ON/OFF) are con-
trolled by a N.O. pushbutton.
ded – 16 - 17 AWG
• Conductor stripping recommended: 5.0 - 6.0 mm
• Maximum length of the connection between dimmer-
driver and control device < 10 m
• Length of connection cables < 10 m
Connection of power supply and LEDs
For the power supply use SELV power suppliers with li-
mited current, short circuit protection only and the power
must be correctly dimensioned. In case of usage of a po-
wer supplier with ground terminals, all points of the pro-
tective earth (PE = Protection Earth) must be connected
to a valid and certied protection earth.
The connection cables between the power source “low
voltage” and the product must be correctly dimensioned
and they should be isolated from every wiring or parts at
not-SELV voltage. Use double insulated cables.
The power supply must be dimensioned according to
the load connected to the device. If the power supply is
oversized with respect to the maximum absorbed current,
then insert a protection against over-current between the
power supply and the device.
Characteristics of the supply and LEDs terminal block
• Screw tightening of the conductors
• Power & LEDs wiring: 1.5 mm2solid – 1.0 mm2stran-
ded – 16 - 17 AWG
• Power and LEDs stripping recommended approx.: 5.0
- 6.0 mm
• Max torque 0.5 Nm
Outputs
The length of the connection cables between the product
and the LED module must be less than 10 m; the cables
must be correctly dimensioned and they should be isola-
ted from every wiring or parts at not-SELV voltage. It is
preferable to use shielded and twisted cables.
In case it is needed to connect the device and LED mo-
dules with cables longer than 10m, the installer must gua-
rantee the correct functioning of the system. In any case,
do not exceed 30 m of the connection between the device
and the LED modules.
Button function Intensity
Click ON / OFF
Double click Maximum intensity
Long press (> 1 s) from OFF Turn ON at 1% (Nightly function), then
dimmer UP / DOWN
Long press (> 1 s) from ON Dimmer UP / DOWN
15 clicks in 5 seconds timeframe Enter PUSH MENU
0-10V, 1-10V or potentiometer
The dimming intensity is managed by tuning the input vol-
tage.
Button function Intensity
0-10V Dimmer: 0V = 0% - 10V = 100%
1-10V Dimmer: 1V = 0% - 10V = 100%
Potentiometer 10 kΩ Dimmer: continuous regulation 0-100%
Automatic detection of the local command type
At the rst switch on, the device is set by default to auto-
matic recognition of N.O. push button command.
• Automatic detection of 0-10V, 1-10V and potentiome-
ter command
The automatic recognition of analog signal 0/1-10V or
potentiometer starts as soon as either a 0/1-10V value
between 3V and 7V is sent out, or by setting the potentio-
meter with value included from 30% and 70%.
0-10 V command 1-10 V command Potentiometer
• Automatic detection of the N.O. pushbutton com-
mand
The N.O. pushbutton is identied automatically after 5
clicks in rapid sequence.
In N.O. pushbutton mode, the memory function is always
active.
N.O. pushbutton
Push menu
In the LED dimmer menu, the following functions are avai-
lable:
• minimum dimming value setting;
• power-on ramp (fade in) setting;
• power-o ramp (fade oou) setting.
Access to menu
When the LED dimmer is turned on, the output is set at
100% and the minimum dimming value at 1%. To access
the device menu, perform a sequence of 15 clicks over a
period of 5 seconds.

5
A ash of the LED loads indicates that the rst menu has
been accessed: “MENU 1”. The access to each menu is
sequential.
Menu 1: minimum dimming value setting
Each single click allows you to vary between 7 minimum
dimming values. The following minimum levels are availa-
ble: 0.1%, 1%, 5%, 10%, 20%, 30% and 100%.
Once the minimum dimming value has been selected,
then long press to conrm: a double ash conrms the
passage to MENU 2.
The software can be downloaded from www.ekinex.com
website and its use is described in the application manual
of the ekinex EK-BG1-TP DALI Gateway. The software
requires Microsoft Windows (7 and later).
23
43
43.00
23
43
43.00
Note. Only in case the minimum level is set to
100%, once the setting is conrmed, the device au-
tomatically exits the MENU.
i
Menu 2: power-on ramp (fade in) setting
Each single click allows to set the fade in. The following
“fade in” times are available: instantaneous, 1 second, 2
seconds, 3 seconds, 6 seconds.
Once the “fade in” time has been selected, then press
and hold to conrm: three ashes conrm the passage
to MENU 3.
Menu 3: power-o ramp (fade out) setting
Each single click allows to set the fade out. The following
“fade out” times are available: instantaneous, 1 second, 2
seconds, 3 seconds, 6 seconds.
After selecting the “fade out” time, then long press to con-
rm: three quick ashes conrm the storage of the set-
tings and the exit from the menu.
Once exited the menu, the LED load connected to the
dimmer output turns on at the minimum value set.
Functions
Relationship between DALI bus and local commands:
on power-up, in case the bus connection is not present,
the local command is active. When the bus connection
is detected, the control passes to the bus. In the absen-
ce of the signal, if the local command is an N.O. button,
the control is passed to the local commands the button is
pressed.
Device addressing
• Simplied method (one ballast connected at a time):
each one will get the address progressively from 0 to
63;
• Random Address Allocation: by connecting all the bal-
lasts at the same time, each one will get a random
address.
Subsequently, the address conguration can be changed
by using an application for parameterization, for example
by downloading the ekinex CGEKBG1TP software to your
PC which allows to:
• congure the DALI system and dene its parameters;
• set the DALI luminaires (groups, scenarios, IDs, etc.);
• test the communication on the DALI bus;
• update the device.
Address Function Map: dimmer
0 Dimmer Dimmer (Intensity value) 0 .. 254
DALI address map
The intensity and ON / OFF switching of the output is ma-
naged via the DALI channel.
Dimensions[mm]
Marks
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/EU) and the RoHS 2
Directive (2011/65/UE).
• Reference Standards: EN 61347-1:2015, EN
55015:2013+A1:2015, EN 61547:2009, EN
50581:2012, IEC/EN 62386-101/102.
Note. In order to install and use the CGEKBG1TP
conguration software, it could be necessary the
installation of .NET Framework 4, which can bee
freely downloaded from Microsoft.com website.
i

6
Warnings
• Installation, electrical connection, conguration and
commissioning of the device can only be carried out by
qualied personnel in compliance with the applicable
technical standards and laws of the respective countri-
es
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the essential
requirements of the applicable directives, for which the
device has been certied, is no longer guaranteed
• ekinex®defective devices must be returned to the ma-
nufacturer at the following address: Ekinex S.p.A. Via
Novara 35, I-28010 Vaprio d’Agogna (NO) Italy
Other information
• The instruction sheet must be delivered to the end cu-
stomer with the project documentation
• For further information on the product, please contact
the ekinex®technical support at the e-mail address:
com
• Each ekinex®device has a unique serial number on
the label. The serial number can be used by installers
or system integrators for documentation purposes and
has to be added in each communication addressed to
the EKINEX technical support in case of malfunctio-
ning of the device
• KNX®and ETS®are registered trademarks of KNX As-
sociation cvba, Brussels
© EKINEX S.p.A. The company reserves the right to make changes to this documen-
tation without notice.
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Disposal
At the end of its useful life the product
described in this datasheet is classied
as waste from electronic equipment in
accordance with the European Directive
2012/19/EU (WEEE recast), and cannot
be disposed together with the municipal
undierentiated solid waste.
Warning! Incorrect disposal of this product may
cause serious damage to the environment and
human health. Please be informed about the
correct disposal procedures for waste collec-
ting and processing provided by local authori-
ties.
!
Table of contents
Other Ekinex Dimmer manuals

Ekinex
Ekinex EK-GD2-TP-1-HV Instructions for use

Ekinex
Ekinex EK-GH1-DL User manual

Ekinex
Ekinex EK-GL1-DL User manual

Ekinex
Ekinex EK-GD2-TP-1-HV User manual

Ekinex
Ekinex EK-GD1-DL-4-HV User manual

Ekinex
Ekinex EK-GO1-DL User manual

Ekinex
Ekinex KNX 90-230 Operating and safety instructions

Ekinex
Ekinex EK-GA1-TP Instructions for use