manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Entes
  6. •
  7. Measuring Instrument
  8. •
  9. Entes EVM-R3 User manual

Entes EVM-R3 User manual

RAIL MOUNTED DIGITAL VOLTMETER
EVM-R3 / EVM-R3C / EVM-R3S
Setting Instant Tripping Function (For EVM-R3C)
Press the set button.
Press up or down buttons until tP is
displayed.
Press the set button.
Press up or down buttons until desired
value is displayed
Press the set button.
Displaying and Deleting Tripping Number (For EVM-R3C)
Press the set button.
Press up or down buttons until OP is
displayed.
Press the set button.
Press up button to delete tripping
number, else do not press any button.
Press the set button.
Adjustment Contact Situation (For EVM-R3C)
Press the set button.
Press up or down buttons until CO is
displayed.
Press the set button.
Press up or down buttons until desired
value is displayed. (0: Normally open,
1: normally closed)
Press the set button.
Displaying Phase-Phase or Phase-Neutral Voltage (For EVM-R3S)
Press until desired voltage is displayed.
Escaping the Set Menu (For EVM-R3C)
If you do not want to change any
adjustment in the menu;
Press up or down buttons until ESC is
displayed.
Press the set button.
s p
0
p
i
s p
0 p
0 0 5
0 0 0
s p
0
0 0 0
e s c
0 0 0
Precautions For Installation and Safe Use
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front
panel.
Do not try to clean the device with solvent or the like. Only clean the
device with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Only for rack panel mounting.
No responsibility is assured by the manufacturer or any of its
subsidiaries for any consequences arising out of the use of this
material.
1
Setting Latch Function (For EVM-R3C)
Press the set button.
Press up or down buttons until lt is
displayed.
Press the set button.
Press up or down buttons until desired
value is displayed
Press the set button.
s p
0
i
Setting of Delay Time (For EVM-R3C)
Setting of Set Point Value (For EVM-R3C)
EVM-R3 (Digital Voltmeter) :
EVM-R3 is designed for accurate measuring of the AC RMS voltage and for
saving the minimum and maximum values of the measured voltages. Minimum
and maximum values remain stored in the memory when the power supply is
off. This stored values can be read when the power is on. EVM-R3 can be used
with any application in which accurate voltage readings should be done between
10-600 V.
EVM-R3S (3-Phase Digital Voltmeter) :
EVM-R3S has the same operating principles as EVM-R3 but developed to
measure voltage in three-phase systems. By using the button on the front panel,
phase-phase (L1-L2, L1-L3, L2-L3) and phase-neutral (L1-N, L2-N, L3-N)
voltages can be selected and read from the display.
EVM-R3C (Setpointed Voltmeter) :
EVM-R3C has the same functions of the EVM-R3. In addition to these functions,
an over voltage level and time delay can be set. When the measured voltage
is over the set value, the output relay is activated at the end of the adjusted
time delay, generates an alarm signal and display starts blinking.
Minimum and Maximum Voltage :
The minimum and maximum voltage values are stored. User may read or delete
these values. Stored minimum and maximum voltage values remain stored,
when the power supply is off.
Setpoint (SP):
When the measured AC voltage between two points is over the setting value,
the output relay is activated in order to generate an error signal, at the end of
the delay time. If the AC voltage is 1.5 times of setting value, output relay is
activated without any delay. If the AC voltage value become lower the setting
value before the end of the delay time, the relay resets itself and no tripping
occurs.
Latch Function ( ):
In case of overvoltage the output relay is activated. Latch function is used to
select the output relay operation mode. Either 0 or 1 position may be selected.
At position 0: If the voltage is below the setting value, output relay releases
automatically, doesnt need any reset.
At position 1: Even if the voltage is below the setting value, output relay
remains activated until the reset and releases only by pressing the set button.
Instant Tripping :
If the AC voltage is 1.5 times of setting value, the output relay is activated without
any delay time. This function is user selectable.
At position 0: Instant tripping is OFF.
At position 1: Instant tripping is ON.
(
p
)
Press the set button.
Press up or down buttons until SP is
displayed.
Press the set button.
Press up or down buttons until voltage
Set Point value is displayed. (When up or
down buttons are continiously pressed,
the display change quickly.)
Press the set button.
sp
s p
2 5 0
2 7 5
Press the set button.
Press up or down buttons until dt is
displayed.
Press the set button.
Press up or down buttons until desired
value is displayed. (When up or down
buttons are continiously pressed, the
display change quickly.)
Press the set button.
s p
10.0
15.2
L1-N
L2-N
L3-N
L1-L2
L2-L3
L1-L3
All manuals and user guides at all-guides.com
RAIL MOUNTED DIGITAL VOLTMETER
EVM-R3 / EVM-R3C / EVM-R3S
Warning :
a) A switch or circuit breaker must be connected between the network
and the auxiliary supply input of device.
b) Connected switch or circuit breaker must be in close proximity to the
device.
c) Connected switch or circuit breaker must be marked as the
disconnecting device for the equipment.
d) The type of the used fuse must be FF type and the current of the used
fuse must be 1A.
e) No need of a vantilator in the installation area
f ) Do not use with generator
Dimensions
* Please check the device label for proper value.
*Different supply voltages are adjustable upon request.
EVM-R3
Voltmeter
Measuring
Input
VAC
1A
L
N
Operating
Voltage (Un)
Connection Diagrams
1A
EVM-R3S
3-Phase
Voltmeter
N
L1
L2
L3
1A
1A
1A
L
N
Operating
Voltage (Un)
53 mm
90 mm
45 mm
62 mm
58 mm
32 mm
48 mm
35 mm
Type PK 20
3 4
1 2
6 5 4 3
21
Measuring
Inputs
EVM-R3C
Setpointed
Voltmeter
Measuring
Input
VAC
1A
L
N
Operating
Voltage (Un)
Output
Contact
1 2 3 4
6 5
Factory Settings :
Set point value (s p )
Delay time ( )
Latch function value ( )
Instant tripping function value
Contact situation ( )
: 250
: 10.0
: 0
: 1 (Instant tripping is on)
: 0 (Normally open)
Displaying Minimum Voltage (For EVM-R3C)
Press and hold the down button to see.
Displaying Minimum Voltage (For EVM-R3)
Press one time to see the minumum voltage
value
Displaying Maximum Voltage (For EVM-R3C)
Press and hold the up button to see.
Press two time to see the maximum voltage value
Displaying Maximum Voltage (For EVM-R3)
Deleting the Minimum and Maximum Voltages
Press up and down buttons at the same time.(For EVM-R3C)
Press and hold for two second to delete demands
values (For EVM-R3)
If the button is not pressed again within 20 seconds,
EVM-R3 turns back automatically in measuring mode. (For EVM-R3)
(
p
)
A2879/rev.2
2
Technical Data
Operating Voltage (Un),*
Operating Range(DU) : Please look at labels on the device.
Operating Frequency(f) : 50/60 Hz
Accuracy : 1% ±1 digit [(%10-%100) full scale]
Measuring Input (Vin): 10-600 V AC (for EVM-R3, EVM-R3C)
10-300 V AC (Phase-Neutral) (for EVM-R3S)
10-500 V AC (Phase-Phase) (for EVM-R3S)
Power Consumption(Pcons): <4 VA
Burden : <1 VA (per phase)
Output Contact : 5 A, 250 V, 1250 VA (Resistive) (for EVM-R3C)
Ins. Tripping : 1.5 x Setpoint (for EVM-R3C)
Hysteresis : 4% x Setpoint (for EVM-R3C)
Delay Time : 0.0 - 99.9 sec. (for EVM-R3C)
Equipment Protection : Double Insulation ( ),
Measuring Category III
Ambient Temperature : -5 OC; +50 OC
Degree of Protection : IP 40 (Front Panel), IP 20 (Terminals)
Wire Cross section (for terminals): 2.5 mm2
Dimensions : Type PK 20
Installations : Rail mounting
Weight : 0.25kg
Packaging Information
Package Weight : 4 kg
Pcs per Package : 16 Pcs
All manuals and user guides at all-guides.com

This manual suits for next models

2

Other Entes Measuring Instrument manuals

Entes EMG Series User manual

Entes

Entes EMG Series User manual

Entes EVM-R3 User manual

Entes

Entes EVM-R3 User manual

Entes MPR-1 Series User manual

Entes

Entes MPR-1 Series User manual

Entes MPR-53S User manual

Entes

Entes MPR-53S User manual

Entes MPR-3 Series User manual

Entes

Entes MPR-3 Series User manual

Entes EVM-3 Instruction manual

Entes

Entes EVM-3 Instruction manual

Entes MPR-4 Series User manual

Entes

Entes MPR-4 Series User manual

Entes MPR-53CS User manual

Entes

Entes MPR-53CS User manual

Entes MPR-4 Series User manual

Entes

Entes MPR-4 Series User manual

Entes MPR-45 User manual

Entes

Entes MPR-45 User manual

Entes AKC Series User manual

Entes

Entes AKC Series User manual

Entes MPR-32 User manual

Entes

Entes MPR-32 User manual

Entes ES3 Series User manual

Entes

Entes ES3 Series User manual

Entes EVM-05C User manual

Entes

Entes EVM-05C User manual

Entes DCV-10 User manual

Entes

Entes DCV-10 User manual

Entes EPR-04 Instruction manual

Entes

Entes EPR-04 Instruction manual

Entes EVM-15 User manual

Entes

Entes EVM-15 User manual

Entes EPM-4A User manual

Entes

Entes EPM-4A User manual

Entes EVM-3S User manual

Entes

Entes EVM-3S User manual

Entes DCA-10 User manual

Entes

Entes DCA-10 User manual

Entes EMK-01 User manual

Entes

Entes EMK-01 User manual

Popular Measuring Instrument manuals by other brands

Mitutoyo IMZ-MJ user manual

Mitutoyo

Mitutoyo IMZ-MJ user manual

PCB Piezotronics PCB-3503A1160KG/030LY manual

PCB Piezotronics

PCB Piezotronics PCB-3503A1160KG/030LY manual

Konica Minolta CM-25cG instruction manual

Konica Minolta

Konica Minolta CM-25cG instruction manual

Hanna Instruments HI 98188 instruction manual

Hanna Instruments

Hanna Instruments HI 98188 instruction manual

EXFO FLS-100 user guide

EXFO

EXFO FLS-100 user guide

2Flow RM130 instruction manual

2Flow

2Flow RM130 instruction manual

Parker SCPSi quick start guide

Parker

Parker SCPSi quick start guide

Hioki 9605-01 instruction manual

Hioki

Hioki 9605-01 instruction manual

GeoSIG AC-23 user manual

GeoSIG

GeoSIG AC-23 user manual

RaySafe i3 Installation & service manual

RaySafe

RaySafe i3 Installation & service manual

ZIEHL MSF 220 SV operating manual

ZIEHL

ZIEHL MSF 220 SV operating manual

Brookfield LV operating instructions

Brookfield

Brookfield LV operating instructions

Beckman Coulter Cytomics FC 500 Instructions for use

Beckman Coulter

Beckman Coulter Cytomics FC 500 Instructions for use

Eaton Crouse-hinds series instruction sheet

Eaton

Eaton Crouse-hinds series instruction sheet

ThinkRF R5700 Programmer's guide

ThinkRF

ThinkRF R5700 Programmer's guide

Omron ZN-DPX21-S Series user manual

Omron

Omron ZN-DPX21-S Series user manual

Precision Digital Corporation ProtEX-RTP PD6830 Series instruction manual

Precision Digital Corporation

Precision Digital Corporation ProtEX-RTP PD6830 Series instruction manual

ELPRO Site Monitoring Kit user manual

ELPRO

ELPRO Site Monitoring Kit user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.