EVCO S.p.A. | EV3C23 & EV3C33 | Instruction sheet ver. 1.0 | Code PRELIMINARY | Page 1 of 3 | PT 44/16
EV3C23 & EV3C33 Controllers for refrigerated cabinets, counters and islands,
with configurable outputs
E ENGLISH
- Controllers for low or medium temperature units, static or ventilated, with light.
- Interval time defrost with configurable evaporator probe
- Configurable outputs
- Power supply 230 VAC or 115 VAC (according to the model).
- Cabinet probe and auxiliary probe (PTC/NTC).
- Door switch/multi-purpose input.
- Compressor relay 16A res. @250 VAC or 30A res. @250 VAC (according to the model).
- Cooling or heating operation.
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
- Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
- Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
- In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
N.B.
- Use cables of an adequate section for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If using an electrical or pneumatic screwdriver, adjust the tightening torque.
- If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the pow-
er.
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
- Disconnect the power supply before doing any type of maintenance.
- Do not use the device as safety device.
- For repairs and for further information, contact the EVCO sales network.
3 FIRST-TIME
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR. DEF. PARAMETER MIN... MAX.
SP 0.0 setpoint r1... r2
P0 1 probe type 0 = PTC 1 = NTC
P2 0 temperature unit of measurement 0 = °C 1 = °F
d1
0
defrost type
0 = electric 1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
7. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on
compressor off
- compressor protection active
- setpoint setting active
defrost or pre-dripping
active -
- defrost delay active
- dripping active
evaporator fan on
evaporator fan off
evaporator fan stop active
HACCP
saved HACCP alarm
-
new HACCP alarm saved
energy saving active
-
-
request for compres-
sor service
-
- settings active
- access to additional functions
active
°C/°F
view temperature
-
overcooling or overheating active
device off
device on
device on/off active
AUX Light on
Aux on Light on due to door open
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2 Unlock keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3 Set the SETPOINT
Check that the keypad is not locked.
1. Touch the SET key.
2. Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-50... 50”)
3. Touch the SET key (or do not operate for 15 s).
4.4 Activate manual DEFROST (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1. Touch the UP key for 2 s.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5 Cabinet LIGHT manual on/off switch mode
1. Touch the light key. Function always unlocked.
- Light manual command if u0 = 3 or u1= 3.
- Auxiliary manual command if u0=1 and u1<>3 if the keyboard is unlocked.
4.6 Cabinet LIGHT or AUXILIARY manual on/off switch mode
1. Touch the light key. Function always unlocked.
2. Touch FNC key for auxiliary load with keyboard unlocked.
- Load configuration u0 = 1(aux) and u1=3(light)
5 ADDITIONA FUNCTIONS
5.1 View/delete compressor functioning hours
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH view compressor functioning hours (hundreds)
rCH delete compressor functioning hours
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.2 View the temperature detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature
Pb2 auxiliary temperature
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or do not operate for 15 s).
9. Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2 Restore the factory settings (default) and store customized settings as default
N.B.
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- the storing of customized settings overwrites the default.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. DESCRIPTION
149 value to restore the factory settings (default)
161 value to store customized settings as default
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8. Interrupt the power supply to the device.
9. Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2 CA1 0.0 cabinet probe offset -25... 25 °C/°F
3 CA2 0.0 auxiliary probe offset -25... 25 °C/°F
4 P0 1 probe type 0 = PTC 1 = NTC
5 P1 1 enable °C decimal point 0 = no 1 = yes
6
P2
0
temperature unit of measure-
ment 0 = °C 1 = °F
7
P4
1
auxiliary probe function
0 = disabled
1 = evaporator probe (de-
frost + fan)
2 = evaporator probe (fan)
3 = condenser probe
8
P5
0
value displayed
0 = cabinet temperature
1 = setpoint
2 = auxiliary temperature
9 P8 5 display refresh time 0... 250 s
N. PAR. DEF. REGULATION MIN... MAX.
10
r0 2.0 setpoint differential 1... 15 °C/°F
11
r1 -50 minimum setpoint -99 °C/°F... r2
12
r2 50.0
maximum setpoint r1... 199 °C/°F
13
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
14
r5
0
cooling or heating operation
0 = cooling
1 = heating
15
r12
0
position of the r0 differential
0 = asymmetric
1 = symmetric
N. PAR. DEF. COMPRESSOR MIN... MAX.
16
C0
0
compressor on delay after pow-
er-on 0... 240 min
17
C2 3 compressor off minimum time 0... 240 min
18
C3 0 compressor on minimum time 0... 240 s
19
C4
10
compressor off time during cabi-
net probe alarm 0... 240 min
20
C5
10
compressor on time during cabi-
net probe alarm 0... 240 min
21
C6
80.0
threshold for high condensation
warning 0... 199 °C/°F
differential = 2 °C/4 °F
22
C7
90.0
threshold for high condensation
alarm 0... 199 °C/°F
23
C8 1 high condensation alarm delay 0... 15 min
N. PAR. DEF. DEFROST (if r5 = 0) MIN... MAX.
24
d0
8
automatic defrost interval
0... 99 h
0 = only manual
if d8 = 3, maximum interval
25
d1
0
defrost type
0 = electric
1 = hot gas
2 = compressor stopped
26
d2 8.0 threshold for defrost end -99... 99 °C/°F
27
d3
30
defrost duration
0... 99 min
se P3 = 1, maximum duration
0= no defrost available
28
d4 0 enable defrost at power-on 0 = no 1 = yes
29
d5 0 defrost dealy after power-on 0... 99 min
30
d6
2
value displayed during defrost
0 = cabinet temperature
1 = display locked
2 = dEF label
31
d7 2 dripping time 0... 15 min
32
d8
0
defrost interval counting mode
0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
33
d9
0.0
evaporation threshold for auto-
matic defrost interval counting if
d8=2
-99... 99 °C/°F
34
d11 0 enable defrost timeout alarm dFd 0 = no 1 = yes
35
d15
0
compressor on consecutive time
for hot gas defrost 0... 99 min
36
d18
40
adaptive defrost interval if d8 =
3
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
37
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
38
d20
180
compressor on consecutive time
for defrost 0... 999 min
0 = disabled
39
d22
2,0 if d8 = 3 adaptive
upper relative threshold to stand-
by the defrost interval counting
"evaporator temperatures aver-
age + d22”);
0..19.9C/F
EVCO S.p.A. | EV3C23 & EV3C33 | Instruction sheet ver. 1.0 | Code PRELIMINARY | Page 2 of 3 | PT 44/16
N. PAR. DEF. ALARMS MIN... MAX.
40
A1
10.0
threshold for low temperature
alarm LA 0... 99 °C/°F
0=disabled
41
A4
10.0
threshold for high temperature
alarm HA ... 99 °C/°F
42
A6
12
high temperature alarm delay af-
ter power-on 0... 99 min x 10
0=disabled
43
A7
15
high/low temperature alarms de-
lay 0... 240 min
44
A8
15
high temperature alarm delay af-
ter defrost 0... 240 min
45
A9
15
high temperature alarm delay af-
ter door closing 0... 240 min
46
A11
2.0
high/low temperature alarms re-
set differential 1... 15 °C/°F
N. PAR. DEF. FANS MIN... MAX.
47
F0
3
evaporator fan mode during
normal operation
0 = off 1 = on
2 = according to F15 and
F16 if compressor off, on
if compressor on
3 = thermo regulated (with
F1)
4 = thermo regulated (with
F1) if compressor on
48
F1
-1.0
threshold to stop evaporator fan.
Fan restarts at |F1-2°|C/F -99... 99 °C/°F
differential = 2 °C/°F
49
F2
0
evaporator fan mode during de-
frost and dripping 0 = off 1 = on
2 = according to F0
50
F3
2
evaporator fan off maximum
time after dripping 0... 15 min
51
F4
0
evaporator fan off time during
energy saving 0... 240 s x 10
52
F5
10
evaporator fan on time during
energy saving 0... 240 s x 10
N.
PAR. DEF. DIGITAL INPUTS MIN... MAX.
53
i0
5
door switch/multi-purpose input
function
0 = disabled
1 = compressor + evapora-
tor fan off + light ON
2 = evaporator fan off +
Light ON
3 = energy saving
4 = "iA" alarm (only display)
5 = "iA" pressure switch
54
i1
0
door switch/multi-purpose input
activation 0 = with contact closed
1 = with contact open
55
i2
30
open door alarm delay;
alarm delay "iA" (i0=4);
compressor restart delay for
pressure alarm "iA" (i0=5);
-1... 120 min
-1 = disabled
56
i3
15
regulation inhibition maximum
time with door open -1... 120 min
-1 = until the closing
57
i10
0
door closed consecutive time for
energy saving
0... 999 min
after regulation temperature
< SP
0 = disabled
58
i13
180
number of door openings for de-
frost 0... 240
0 = disabled
59
i14
32
door open consecutive time for
defrost 0... 240 min
0 = disabled
60
u0
3
K2
output configuration
0= defrost
1=auxiliary(light key, if u1=3
"V" key )
2= alarm
3= light (default)
61
u1
0
K3 output configuration
0 = evaporator fan (default)
1 = defrost
2 = stand-by (with delay u3)
3 = light
62
u2
1
Light key enabled in stand
-
by.
Also suitable for Aux function.
0=no 1 =yes
63
u3
0
Standby o
utput delay
(u1=2)
af-
ter setting the unit in standby.
Be aware that the stand by relay
is on for the time set in u3 after.
! Disconnect the power supply
before doing any type of mainte-
nance.
0..999 seconds
0= disabled
64
u4
1
Alarm output silencing u0=2
0=no 1 =yes
N. PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX.
65
HE2
0
energy saving maximum duration
0... 999 min
-1 = until the door opening
66
HE2
0
low power consumption function
(switch off the display) 0... 240 min
0= disabled
N. PAR. DEF. SAFETIES MIN... MAX.
67
POF 0 enable ON/STAND-BY key func-
tion 0 = no 1 = yes
68
PAS -19 password -99... 999
8 ALARMS
COD. DESCRIPTION RESET REMEDIES
Pr1 cabinet probe alarm automatic - check P0
Pr2 auxiliary probe alarm automatic - check probe integrity
- check electrical connection
AL low temperature alarm automatic check A1 and A7
AH high temperature alarm automatic check A4 and A7
id open door alarm automatic check i0 e i1
COH high condensation warning automatic check C6
CSd
high condensation alarm
manual
- switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i0 and i1
iA pressure switch input alarm automatic i2 delay
dFd
defrost timeout alarm
manual
- touch a key
- check d2, d3 and d11
9 TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container Black, self-extinguishing
Category of heat and fire resistance D
Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks;
75.0 x 33.0 x 73.0 mm (2 15/16 x 1 5/16 x
2 7/8 in)
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with removable screw terminal
blocks; 75.0 x 33.0 x 83.0 mm (2 15/16 x 1
5/16 x 3 1/4 in)
Mounting methods for the control device
To be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the cover-
ing IP65 (front)
Connection method
Fixed screw terminal blocks
for wires up to 2,5 mm²
Removable screw terminal
blocks for wires up to
2,5 mm²; by request
TTL or seriale RS485 not
available
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft) Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0 to 55 °C (from 32 to 131 °F); from 0
to 50 °C (from 32 a 122 °F) in EV3... N3
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from
10 to 90%
Pollution status of the control device 2
Conformity
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH (EC) Regulation
1907/2006
EMC 2014/30/UE LVD 2014/35/UE
- EN 60730-1 - IEC 60730-1.
Power supply
230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3... N7
115 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3... N5
Earthing methods for the control device None
Rated impulse-withstand voltage
4 KV (2.5 KV in EV3C33N9)
Over-voltage category
III (II in EV3C33N9)
Software class and structure
A
Analogue inputs
2 for PTC or NTC probes (cabinet probe and
auxiliary probe)
PTC probes Sensor type
KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field
From -50 to 150 °C (from -58 to 302 °F)
Resolution
0.1 °C (1 °F)
NTC probes Sensor type
ß3435 (10 K@ 25 °C, 77 °F)
Measurement field
From -40 to 105 °C (from -40 to 221 °F)
Resolution
0.1 °C (1 °F)
Digital inputs
1 dry contact (door switch/multi-purpose)
Dry contact Contact type 5 VDC, 1.5 mA
Power supply None
Protection None
Digital outputs
3 electro-mechanical relays (compressor, defrost and evapo-
rator fan)
Compressor relay (K1) EV3C23 SPST, 16 A res. @ 250 VAC
EV3C33 SPST, 30 A res. @ 250 VAC
Light/configurable relay (K2) SPDT, 8 A res. @ 250 VAC
Evaporator fan / configurable relay (K3)
SPST, 5 A res. @ 250 VAC; (30,000 cycles)
Classificazione del dispositivo di comando se-
condo la protezione contro la scossa elettrica CLASS II EMC EN 60730-1 §2.7.5.
Type 1 or Type 2 Actions Type 1
Additional features of Type 1 or Type 2 ac-
tions
C
Displays
3 digits custom display, with function icons
Alarm buzzer Not available
Communication ports
TTL port not available RS-485 MODBUS port not available
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of EVCO and thus pro-
tected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full
or partial reproduction and disclosure of the content other than with the express approval of EVCO. The
customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the de-
vice. EVCO accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the equip-
ment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
telefono 0437 8422 | fax 0437 83648
email [email protected] | web www.evco.it

This manual suits for next models

1

Other Evco Controllers manuals

Evco EV3H94 User manual

Evco

Evco EV3H94 User manual

Evco EV8318 User manual

Evco

Evco EV8318 User manual

Evco Vcolor 338 L User guide

Evco

Evco Vcolor 338 L User guide

Evco c-pro 3 NODE kilo User manual

Evco

Evco c-pro 3 NODE kilo User manual

Evco EV3 700 Series User manual

Evco

Evco EV3 700 Series User manual

Evco EVK614 User manual

Evco

Evco EVK614 User manual

Evco EVF815 User guide

Evco

Evco EVF815 User guide

Evco EVX225 User manual

Evco

Evco EVX225 User manual

Evco Vcolor 679 User guide

Evco

Evco Vcolor 679 User guide

Evco EV3S204 User manual

Evco

Evco EV3S204 User manual

Evco EVD HP User guide

Evco

Evco EVD HP User guide

Evco Vcolor 229 Series User manual

Evco

Evco Vcolor 229 Series User manual

Evco c-pro 3 OEM HRV User guide

Evco

Evco c-pro 3 OEM HRV User guide

Evco EV3B33N7VXRX04 User manual

Evco

Evco EV3B33N7VXRX04 User manual

Evco EV3B71 User manual

Evco

Evco EV3B71 User manual

Evco EVF204 User manual

Evco

Evco EVF204 User manual

Evco EV3B24 User manual

Evco

Evco EV3B24 User manual

Evco c-pro 3 nano Series User manual

Evco

Evco c-pro 3 nano Series User manual

Evco EVJ 700 User guide

Evco

Evco EVJ 700 User guide

Evco Vcolor 818 User guide

Evco

Evco Vcolor 818 User guide

Evco EVF215 User manual

Evco

Evco EVF215 User manual

Evco EV3271 User manual

Evco

Evco EV3271 User manual

Evco EVX 800 Series User guide

Evco

Evco EVX 800 Series User guide

Evco Vcolor 318 M User guide

Evco

Evco Vcolor 318 M User guide

Popular Controllers manuals by other brands

Steinberg CMC Series Operation manual

Steinberg

Steinberg CMC Series Operation manual

Siemens SIMATIC S7 F manual

Siemens

Siemens SIMATIC S7 F manual

Omron E5ED-B instruction manual

Omron

Omron E5ED-B instruction manual

MDT AMI series Technical manual

MDT

MDT AMI series Technical manual

Trane Oxbox JAYLOAM002 installation manual

Trane

Trane Oxbox JAYLOAM002 installation manual

VIPA System 300S manual

VIPA

VIPA System 300S manual

EUCHIPS EUP200AD-1H24V-0 quick start guide

EUCHIPS

EUCHIPS EUP200AD-1H24V-0 quick start guide

Christie E510 user guide

Christie

Christie E510 user guide

E-FLITE EFLA600 manual

E-FLITE

E-FLITE EFLA600 manual

AudioCodes Mediant 2600 user manual

AudioCodes

AudioCodes Mediant 2600 user manual

Raven SmarTrax MD installation manual

Raven

Raven SmarTrax MD installation manual

Popp Flow Stop 2 quick start

Popp

Popp Flow Stop 2 quick start

Dyna-Flo DFR 026 Operation, Parts, and Instruction Manual

Dyna-Flo

Dyna-Flo DFR 026 Operation, Parts, and Instruction Manual

EFI E-42B Installation and service guide

EFI

EFI E-42B Installation and service guide

vacuubrand VACUU-SELECT Instructions for use

vacuubrand

vacuubrand VACUU-SELECT Instructions for use

nodon CRC-3-6 user guide

nodon

nodon CRC-3-6 user guide

SMC Networks EX600-SPN1 Operation manuals

SMC Networks

SMC Networks EX600-SPN1 Operation manuals

Carel powerSplit user manual

Carel

Carel powerSplit user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.