6.2. Power Display
- After GTC-542 power turns ON, the current firm ware version is displayed.
- It displays 24.0 before completion of self test and outputs inputted voltage after the completion.
-When"BATTERYTEST"keyispressedwithexternalpowerapplied,itoutputssparebattery
- voltage.
- When it operates on spare battery, main power LED turns off and power LED lights on.
- When the spare battery is connected properly and there is no problem in charging and usage,
- BAT.GOOD LED lights on.
- When the spare battery is detached, battery key (internal switch) is off, or it is completely
- discharged, BAT. GOOD LED turns off and BAT.TROUBLE LED lights on.
www.gastron.com
16_17
GTC-542
Instruction Manual
■Pressing"TEST"S/Wfor2secorlongeringasconcentrationdsiplaymodeentersTestmode.
■Intestmode,whenitpasses30minafterthelastS/Wcontrol,itautomaticallyreturnstothegasconcentration
display mode
6.4. Test Mode
- When it enters Test mode, gas concentration number displays and flickers.
- This function enables testing at channel unit without injecting gas to the detector sensor. It can
- setanarbitraryconcentrationwhentheuserpresses"Test"S/Wandalarmfunctionoperates
- normally with a user-defined concentration.
-When"FUNC"S/Wispressed2secorlonger,itentersFND/LED/BarLEDTestfunction.
- 3-Color bar graph LED displays green, orange, and red at 0.5 s interval and each function
- LED flickers at 0.5 s interval.
-When"RESET"S/Wispressed,itreturnstogasconcentrationdisplaymode.
▼▲
Full Range
- After GTC-542 power turns ON, the current firm ware version is displayed.
- VER is displayed for 0.5 sec on FND then number displays.
- The current version is 1.03.
-Afterwarming-upby"SELF"flashingforapprox.30seconFNDofconcentrationdisplay,
- it immediately enters the measurement mode.
- Upon an event of fault of the equipment or detector at this time, fault alarm appears.
▼
X.XX
- Displays gas concentration received by the detector on FND digital display in numbers.
- Gas concentration is also displayed by 3-color bar graphic LED. Concentrations below the
- primary alarm concentration in green, below the secondary alarm concentration in orange,
- and above the secondary alarm concentration in red.
- 3-level alarm thresholds are always displayed by 3-color bar graphic LED. Alarm1 threshold
- in green, Alarm2 threshold in orange, and alarm3 threshold in red.
- When the detector is not connected or input current from the detector is under 10% below the
- sethighscalevalue,"Undr"displaysandflashesat1secinterval
- Trouble LED lights on, warning light flashes, and buzzer sounds
- When buzzer stop key is pressed, the warning light turns on and the buzzer stops.
-Whentheinputcurrentfromthedetectorisover10%abovethesethighscalevalue,"ovE"
- displays and flashes at 1 sec interval.
- Alarm 1, 2, 3 LED lights flickers, warning light flickers, and buzzer sounds.
- Top circular LED of the 3-Color bar graphic LED lights on red.
- When gas concentration is detected to be above the set value for alarm, alarm function counts
- the dwell time and if it is above the set dwell time, alarm function operates.
- Alarm relay turns on when it is above the alarm dwell time.
-Whenalarmlatchtypeis"ON",uponoperationofalarmfunction,alarmstatusandgas
- concentration value are maintained at the max. value. It does not get release when the gas
- concentrationisdecreasedbelowthealarmthresholdand"RESET"keymustbeusedtoreleaseit.
- When Alarm Latch Type is OFF, Alarm is released automatically in accordance to gas
- concentration.
6. Operation Method6. Operation Method
■Checkwiringsforoperationpower,detectionparts,alarmparts,andconcentrationdisplay.
■CheckthepowerinputthenturnONthepowerS/W.
■CheckwhetherpowerLEDatalarmandconcentrationdisplaypartslighton.
■Checkwhether"SELF"isdisplayedonFNDconcentrationdisplaypart.
6.1. Power ON
■Afterpoweron,whenthereisnoerrorfrom"SELFTEST",itautomaticallyentersMeasuringMode.
6.3. Measuring Mode