GE Digital Energy SG 400 kVA User manual

GE Digital Energy
Power Quality
SGS_400-500_UPS_GE_01a
Operating Manual
Uninterruptible Power supply
Digital Energy™
SG Series
400 & 500 kVA
480 Vac UL / Series 1
Manufactured by:
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
T +41 (0)91 / 850 51 51
F +41 (0)91 / 850 51 44
www.gedigitalenergy.com
GE imagination at work

Modifications reserved Page 2/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Model: SG Series 400 - 500 kVA / Series 1
Date of issue: 11/12/2008
File name: OPM_SGT_USM_M40_M50_1US_V020
Revision: 2.0
Identification No.:
Up-dating
Revision Concerns Date
2.0 GE Digital Energy – Power Quality 11/12/2008
COPYRIGHT © 2008 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not
necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.

Modifications reserved Page 3/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE.
We trust that the use of the SG Series
Uninterruptible Power Supply system, developed
and produced to the highest standards of quality,
will give you complete satisfaction.
Please read carefully the Operating Manual, which
contains all the necessary information and describes
all you need to know about the use of the UPS.
Thank you for choosing GE !
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform start-up and
commissioning of the UPS. Please Contact GE. Global Services at least two
weeks prior to schedule start-up and commissioning at 1-800-637-1738, or
Distributed in the USA by:
Your service contact:
g
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
www.gedigitalenergy.com
g
GE Digital Energy
Power Quality
2501 Pecan Street
Bonham, TX 75418
T: +1 800-637-1738
F: +1 903-640-0533
http://www.gedigitalenergy.com/ups

Modifications reserved Page 4/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Preface
Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will
help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the
switches, the meaning of the system events related to the front panel indication, and
provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the
installation site, and it provides weight, dimensions and procedures for moving, installing
and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE assumes no responsibility or liability for any losses or damages resulting from the use
of the information contained in this document.
NOTE !
SG Series 400 & 500 kVA is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and Battery System.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed
only for parallel system.

Modifications reserved Page 5/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Table of contents Page
1IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................... 7
2INTRODUCTION ............................................................................................................................................ 10
3DESCRIPTION ................................................................................................................................................ 11
3.1 BLOCK DIAGRAM AND MAIN ELEMENTS .............................................................................................................. 11
3.2 OPERATION MODES........................................................................................................................................................ 12
3.2.1 Normal operation mode .............................................................................................................................. 12
3.2.2 Utility failure operation ................................................................................................................................ 12
3.2.3 Utility recovery operation........................................................................................................................... 13
3.2.4 Automatic Bypass........................................................................................................................................... 13
3.2.5 Manual Bypass................................................................................................................................................. 13
3.3 PARALLEL SYSTEM OPERATION ................................................................................................................................ 14
3.3.1 Introduction to the parallel system........................................................................................................ 14
3.3.2 Features of RPA parallel system.............................................................................................................. 15
3.3.3 System control ................................................................................................................................................. 15
3.3.4 Synchronization............................................................................................................................................... 15
3.3.5 Load sharing...................................................................................................................................................... 15
3.4 RECTIFIERS PARALLELED ON THE SAME BATTERY ........................................................................................... 16
3.5 RECYCLING AT THE END OF SERVICE LIFE........................................................................................................... 17
4LAYOUT .......................................................................................................................................................... 18
4.1 LAYOUT SG Series 400 & 500 kVA............................................................................................................................ 18
5CONTROL PANEL .......................................................................................................................................... 19
5.1 CONTROL PANEL ............................................................................................................................................................. 19
5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL.............................................................. 19
6LCD SCREEN .................................................................................................................................................. 21
6.1 METERING MODE............................................................................................................................................................. 22
6.2 ALARMS................................................................................................................................................................................ 25
6.3 PARAMETERS..................................................................................................................................................................... 26
6.4 EDIT MODE.......................................................................................................................................................................... 28
6.5 USER PARAMETERS......................................................................................................................................................... 31
6.6 EVENTS (ALARMS AND MESSAGES) ......................................................................................................................... 34
6.6.1 Alarms list ........................................................................................................................................................... 34
6.6.2 Messages list ..................................................................................................................................................... 38
6.6.3 Event report SG Series................................................................................................................................... 40
7OPERATION.................................................................................................................................................... 41
7.1 PROCEDURES FOR SINGLE UPS................................................................................................................................ 42
7.1.1 Start-up of the SG Series.............................................................................................................................. 42
7.1.2 Maintenance shutdown (Load on Q2)................................................................................................... 43
7.1.3 From Manual Bypass (Q2) to normal function VFI .......................................................................... 44
7.1.4 Complete UPS shutdown (No Load supply)........................................................................................ 45
7.1.5 Restore to normal operation after “total off”..................................................................................... 46
7.1.6 Restore to normal operation after EPO (Emergency Power Off) ............................................... 47

Modifications reserved Page 6/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
7.2 PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER .................................................... 48
7.2.1 Start-up of the SG Series as frequency converter .......................................................................... 48
7.2.2 Complete UPS shutdown (No Load supply)........................................................................................ 49
7.2.3 Restore to normal operation after “total off”..................................................................................... 50
7.2.4 Restore to normal operation after EPO (Emergency Power Off) ............................................... 51
7.3 PROCEDURES FOR PARALLEL SYSTEM .................................................................................................................. 52
7.3.1 Parallel System start-up .............................................................................................................................. 52
7.3.2 Maintenance system shutdown (Load supplied from Q2 on all Units) ................................. 54
7.3.3 From Manual Bypass (Q2) to normal function VFI .......................................................................... 56
7.3.4 Separate a Unit from the parallel system (System Redundancy)........................................... 58
7.3.5 Reconnect a Unit to a parallel system.................................................................................................. 60
7.3.6 Parallel system shutdown (No Load supply)...................................................................................... 61
7.3.7 Restore to normal operation after “total off”..................................................................................... 63
7.3.8 Restore to normal operation after EPO (Emergency Power Off) ............................................... 65
7.4 PROCEDURES FOR PARALLEL SYSTEM WITH COMMON BATTERY............................................................ 67
7.4.1 Parallel System start-up .............................................................................................................................. 67
7.4.2 Maintenance system shutdown (Load supplied from Q2 on all Units) ................................. 69
7.4.3 From Manual Bypass (Q2) to normal function VFI .......................................................................... 71
7.4.4 Separate a Unit from the parallel system (System Redundancy)........................................... 73
7.4.5 Reconnect a Unit to a parallel system.................................................................................................. 75
7.4.6 Parallel system shutdown (No Load supply)...................................................................................... 76
7.4.7 Restore to normal operation after “total off”..................................................................................... 78
7.4.8 Restore to normal operation after EPO (Emergency Power Off) ............................................... 80
8OPTIONS......................................................................................................................................................... 82
8.1 COMMUNICATION OPTIONS....................................................................................................................................... 82
8.2 OPTIONS IN UPS CABINET ........................................................................................................................................... 82
8.3 CONNECTION FOR OPTIONS ...................................................................................................................................... 83
8.3.1 Remote Signalling Box (RSB) ...................................................................................................................... 83
9MAINTENANCE.............................................................................................................................................. 84
9.1 MAINTENANCE.................................................................................................................................................................. 84
9.1.1 Service check .................................................................................................................................................... 84
9.1.2 Fans and ventilation ...................................................................................................................................... 84
9.1.3 Other components with limited lifetime .............................................................................................. 84
9.1.4 Battery.................................................................................................................................................................. 84
9.1.5 Long shut-down periods of the UPS-system..................................................................................... 85
9.1.6 UPS room conditions and temperature ............................................................................................... 85
9.1.7 Long shut-down periods of the UPS-system..................................................................................... 85
10 NOTES............................................................................................................................................................. 86
10.1 NOTES FORM ..................................................................................................................................................................... 86

Modifications reserved Page 7/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 400 & 500 kVA that should be
followed during installation and maintenance of the UPS and battery.
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 95°F
(35°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.

Modifications reserved Page 8/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorised personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch
them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.

Modifications reserved Page 9/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may
occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.

Modifications reserved Page 10/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
2 INTRODUCTION
An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable,
continuous, disturbance free supply.
In case the power provided by the Utility Fails, or exceeds the permitted tolerances, the power to supply
the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load)
or until the Utility power returns.
SG Series is a true double conversion VFI (Voltage Frequency Independent) UPS system where the Load is
continuously supplied by the Inverter through the Rectifier.
In case of trouble on the Inverter Output Voltage, or when overload or short-circuit on the output occur,
the Load is instantly transferred to the Utility via the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is restored.
Key features:
• More Critical equipment supported
Rated at 0.8 Power Factor for SG Series 400 kVA and at 0.9 Power Factor for SG Series 500 kVA, SG
Series delivers more real power than other UPS in the market.
With today’s trend toward power factor corrected loads, SG Series can support more total Load
than any other UPS available, allowing you to support a greater number of today’s enterprise
computing Power Factor Corrected (PFC) equipment.
• No single point of failure
Redundant Parallel Architecture (RPA) is an exclusive GE technology.
With RPA, SG Series UPS are controlled in a true peer-to-peer configuration where all critical
elements and functions (including Bypass) are redundant.
SG Series is designed to be the most reliable power protection system available on the market
today.
• High Efficiency
Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series offers low output
voltage distortion and provides efficiencies up to 93%.
• Fully digital
Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology corner stones
of new age of power quality and power reliability.
• Extremely flexible
Tailor made power protection to meet your individual installation requirements; SG Series offers
various options like input harmonic filters and our comprehensive JUMP software suite for mission
control and data protection to cover all your application needs.

Modifications reserved Page 11/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3 DESCRIPTION
3.1 BLOCK DIAGRAM AND MAIN ELEMENTS
Fig. 3.1-1 Block diagram
The SG Series system can be divided into the following main elements:
Control System SG Series is designed with microprocessor-controlled signal processing
circuits. The interface between the operator and the unit is provided by the monitoring system on the
front panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier The standard Rectifier consists of a 6-pulse SCR-bridge, which converts the 3-
phase Utility Voltage into a controlled and regulated DC-voltage.
This regulated DC-voltage is used to supply power to the Inverter, and to provide charging power to the
Battery.
Inverter The Inverter converts the DC voltage into a three-phase AC-voltage with
constant amplitude and frequency, which is completely independent and isolated from the AC-input
voltage.
Automatic Bypass The Automatic Bypass consists of a static semiconductor-switch (SSM: Static
Switch Module), used to provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection All SG Series UPS's are equipped with an automatic system for the protection
against voltage back feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 and K8 (in series with the thyristors of the
static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the Manual Bypass Q2.
Manual Bypass The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which
removes the UPS from the Load for maintenance, while still supplying the Load with power directly from
the Utility.
Battery The Battery supplies the DC power to the Inverter when the Utility is out of
accepted tolerances.

Modifications reserved Page 12/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.2 OPERATION MODES
3.2.1 Normal operation mode
During normal operation, the Rectifier converts
input AC power to DC.
The DC power provides input power for the
Inverter and charging power for the Battery.
The Inverter converts the DC power to
continuous and regulated AC power, which
supplies the critical load.
The control panel reports the Battery charge
status and the expected backup time with the
actual load.
Fig. 3.2.1-1 Block diagram normal operation mode
3.2.2 Utility failure operation
When the Utility is no longer within acceptable
tolerances, the Battery will provide the DC power
to the Inverter.
The Inverter will maintain continuous AC power
to the Load until the Battery Voltage reaches the
lower limit of the Inverter operation capability.
During the discharge, the LCD screen displays
the estimated time the Battery can support the
critical load.
Prior to the Battery completely discharging, the
"stop operation"alarm (shutdown imminent)
warns the operator that the Battery is almost
discharged and the UPS is about to shut down.
Fig. 3.2.2-1 Block diagram Utility Failure operation
In case of parallel operation
With a parallel system for power capacity (see Section 3.3)
• With the Bypass Utility power available, a low Battery warning on any unit will cause the Load to
be transferred to Utility (after a selectable time delay).
• With Bypass Utility power not available, a low Battery warning on any unit will start the “stop
operation” timer (adjustable).
The Load will shut down at the end of the “stop operation” time period.
With a parallel system for redundancy (see Section 3.3)
• When a Battery low warning occurs on a unit not necessary to support the present load, this unit
will shut down after a timeout period (selectable).
The Load is shared between the other units
• As the warning occurs on one unit necessary to support the present load, the system starts the
"stop operation" timeout (selectable).
The Load will shut down at the end of the “stop operation” time period.

Modifications reserved Page 13/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.2.3 Utility recovery operation
As soon as the AC input power recovers, the Rectifier will
start automatically, supplying DC power to the Inverter
and recharging the Battery.
If the Inverter was previously shut down due to low
Battery, the Load will be initially powered by Utility
through the Automatic Bypass.
When the Battery is recharged enough to ensure a
minimum time of operation with the present load, the
Inverter will start automatically and the Load will be
transferred back to the Inverter.
Fig. 3.2.3-1 Block diagram Utility recovery operation
In case of parallel operation
When the AC input power recovers, the Rectifiers will start up sequentially, according to their
number in the parallel system. This minimizes the initial inrush current.
The Inverters will start up automatically, but only when the Battery has recharged enough for a
minimum runtime with the present load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from the
Automatic Bypass back to the Inverter output.
3.2.4 Automatic Bypass
In normal operation, the Load is supplied by the Inverter.
When the control system detects a fault in the Inverter,
an overload condition or a short-circuit condition, the
Automatic Bypass will transfer the critical Load to the
Utility without interruption.
When the Inverter recovers, or the overload or short-
circuit condition is corrected, the Load will be
automatically transferred back to the Inverter.
If the UPS is unable to return to normal mode following
an automatic transfer to Bypass mode, an alarm
condition will be initiated.
A Manual Bypass (operator initiated) will not be
considered as an alarm condition.
Fig. 3.2.4-1 Block diagram Automatic Bypass
In case of parallel operation
Each unit has it’s own internal Bypass. These units are continuously exchanging information, enabling
all of the internal Bypass circuits in a parallel system to operate simultaneously.
If the Inverter of a unit fails, it’s Bypass circuit remains available to the parallel system.
It is excluded only if the unit is separated from the common bus by opening it’s output switch Q1.
3.2.5 Manual Bypass
The Manual Bypass circuit consists of Q1 and Q2 manual
switches, which permits transfer of the Load directly to
the unconditioned AC power without interruption, leaving
the UPS available for maintenance.
Fig. 3.2.5-1 Block diagram Manual Bypass

Modifications reserved Page 14/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.3 PARALLEL SYSTEM OPERATION
3.3.1 Introduction to the parallel system
Two or more equal power units can be paralleled to increase the output power (paralleling for capacity)
or to improve the overall reliability of an UPS system (paralleling for redundancy).
The outputs of parallel units are connected to a common power bus, and in normal operation the units
connected on the parallel bus share the Load equally.
The modular concept of SG Series allows parallel operation of up to 8 units, without using paralleling
switchgear, external bypass circuits or common control circuitry (see Fig. 3.3.1-1).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a
single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal
power.
In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the
Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n+1 out of n redundant paralleled modules must be equal to or greater
than the required Load power.
The Load will be equally shared by the nunits connected on the output bus.
Should one of the nparalleled units trip Off-line, the remaining (n+1) modules will supply the load,
maintaining conditioned power to the critical load.
From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between
Failures).
Fig. 3.3.1-1 Block diagram parallel system operation

Modifications reserved Page 15/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.3.2 Features of RPA parallel system
The SG Series parallel system is designed to provide a complete Redundant Parallel Architecture, and
is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with redundant
modular concept.
When one UPS needs maintenance or service, the Load is powered by the other units supplying the
Load bus.
The redundant communication bus to which all units are connected keeps each unit informed about the
status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
3.3.3 System control
A high-speed redundant, serial communication bus guarantees the exchange of data and thus the
communication between the CPU's of each unit.
Each module controls it's own function and operational status and communicates with all other
modules, in order to act or react if necessary, adapting it to the new conditions.
3.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as the later is
within tolerances.
In case of reference failure, another unit in the parallel system is automatically chosen to take over the
reference role.
The Bypass Input for all the units of the parallel system must be supplied from the same AC source (no
phase shift allowed between them).
3.3.5 Load sharing
On each unit of the parallel system, Inverter Output Voltage and Current are measured and applied to a
Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or
fuses should be inserted between the unit’s output and the Load common bus bars.
However, it is recommended that a disconnect or isolation switch be inserted.

Modifications reserved Page 16/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.4 RECTIFIERS PARALLELED ON THE SAME BATTERY
NOTE !
A parallel system with a Common Battery for two or more Rectifiers, requires a
particular installation and adequate setting of some parameters, (accessible
only through password), and can therefore only be done by a qualified
engineer from GE.
Usually each Rectifier-Inverter Unit runs with its own Battery.
In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 3.4-1), the sharing
circuit between individual Rectifier is integrated in the communication bus of the system in order to
assure an equal sharing of the Rectifiers output currents.
Fig. 3.4-1 Diagram RPA system with Rectifiers on Common Battery
1 –
2 –
3 –
4 –
5 –
6 –
7 –
8 –
Rectifier
Inverter
Automatic Bypass
Manual Bypass
Mains Power
Load Bus Bar
External Battery Fuse
Battery
Pay attention to the following recommendations:
• The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.
• The installation must be performed only with the UPS system must be completely shut down.
• The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.
• Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
• It is recommended to install the fuses / MCB (7) on each line connecting the Rectifiers to the
common Battery for maintenance / safety reasons.
• In case one must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCB on the Battery line (7).
• It is recommended to connect an external NO free contact “Battery Fuses” to the UPS and to enable
the function by setting the parameter (see Section 4.1 of the “Installation Guide”).
• If an emergency generator set supply the UPS, and the free contact “Generator ON” is connected to
the Customer interface, connect a separate NO free contact on each parallel unit.
• The parameters enabling the Battery test, both manual and automatic, must be set in the same
mode on all the units having the Rectifiers on Common Battery.
• Do not connect the temperature sensor for automatic battery floating voltage compensation.
• Do not enable the function Boost charge (parameter 87).

Modifications reserved Page 17/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3.5 RECYCLING AT THE END OF SERVICE LIFE
NOTE !
This product has been designed to respect the environment, using
materials and components respecting eco-design rules.
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen
Carbon Fluor Clorid).
GE, in compliance with environment protection recommends to the
User that the UPS equipment, at the end of its service life, must be
recovered conforming to the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance for the
environment, therefore it must be correctly recycled by specialised
companies!

Modifications reserved Page 18/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
4 LAYOUT
4.1 LAYOUT SG Series 400 & 500 kVA
SGS_400-500_UPS_GE_02a
Fig. 4.1-1 SG Series general view
Q2
Q1
SGS_400-500_UPS_GE_03a
Fig. 4.1-2 SG Series general view with open door
SGS_400-500_Switches Q1-Q2_01
Q1
Q2
Fig. 4.1-3 Manual operated switches
Fig. 4.1-4 Control Panel
P4 Customer Interface Board
Q1 UPS output switch
Q2 Manual Bypass switch
SGS_400-500_Customerinterface_03
P4
SNMP
Fig. 4.1-5 Connectivity Rack
SNMP Advanced SNMP Card (option)

Modifications reserved Page 19/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
5 CONTROL PANEL
5.1 CONTROL PANEL
Fig. 5.1-1 Control Panel
5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL
inverter on/off
Key to switch the Inverter ON ( I )
(This key is also used to reset “total off”if pressed simultaneously with total off
push button).
inverter on/off
Key for Inverter shutdown ( O )
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.
mute
Key to reset general alarm and buzzer.
test
Key to test the control panel LEDs and buzzer.
(Pressing this key causes all the LEDs to light and the buzzer to sound 3 times).
The push-button “total off”is protected by a red cover.
By pressing it, you immediately separate the UPS from Utility and the Load.
Attention: “total off”cannot disconnect the UPS from the Load with Q2 closed.
To reset “total off”: push and hold the “total off”push-button and the “I”key
(inverter on) simultaneously for some seconds.
For parallel system: if “total off”is pressed on one unit connected to
the parallel bus (switch Q1 closed), all the units are separated from the load.
The “total off” reset must be done only on one unit connected to the parallel bus
(switch Q1 closed).
NOTE !
Special care must be taken in using this command, in order to
avoid accidental Load disconnection.

Modifications reserved Page 20/86
OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
alarm
General alarm condition
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with alarm condition still present) and the buzzer
stops as the key “mute”has been pressed.
service check
LED ON indicates that a regular maintenance service is needed.
May be reset by a service technician only.
See Section 11 – Maintenance.
The LED is ON also when the output switch Q1 is open, indicating that the
Inverter is in service mode, not supplying the load.
a)LED ON indicates that the Battery reserve lasts for only 3 more minutes
(selectable).
b) LED ON in case of overtemperature or overload >125% together with
missing Utility.
After the timeout the Inverter will shut down.
All LEDs ON indicate that the Battery is fully charged
LED a Yellow:
• Fixed: indicating last 25 % of Battery backup.
• Blinking: indicating Battery backup
≤
5%.
LED b, c, d Green:
• Each one indicating 25 % of Battery backup.
LEDs ON indicate the Load status of the UPS
LED d red (≥100 % load)
LED c yellow (100% load)
LED b green (66% load)
LED a green (33% load)
Fig. 5.2-1 LEDs on synoptic diagram
LEDs on synoptic diagram
LED 1 = Input Utility Rectifier (green)
LED 2 = Input Utility Bypass (green)
LED 3 = Rectifier ON (green)
LED 4a = Discharging (yellow)
LED 4b = Charging (green)
LED 5 = Inverter ON (green)
LED 6 = Load on Inverter (green)
LED 7 = Load on Utility (green)
LED 8 = Output Load Voltage (green)
LED 9 = Manual Bypass (Q2) ON (yellow)
Fig. 5.2-2 LCD screen
User LCD Interface
Consist of an LCD screen, 4 lines with 20
characters each and six keys. It offers:
• UPS operating, AC and DC metering
information.
• History of events (alarms and messages).
• Functionality can be programmed to meet
customer needs by changing parameters.
This manual suits for next models
1
Table of contents
Other GE UPS manuals

GE
GE 750 UL S2 User manual

GE
GE TLE 160 User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE VH UL series User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE EP 700T User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE SG 750 UL S2 Series User manual

GE
GE Amersham Imager 600 User manual

GE
GE LanPro 11 U User manual

GE
GE LP33 Series 80 User manual

GE
GE SG SERIES 10 User manual

GE
GE 400 Series User manual

GE
GE SG Series User manual

GE
GE Uninterruptible Power Supply User manual

GE
GE Match User manual

GE
GE TLE Scalable Series User manual

GE
GE Match lite 500 User manual

GE
GE Lanpro 33 User manual

GE
GE LP 33U Series User manual