gefran GQ 15 Series User manual

GQ 15 / 25 / 50 / 90 A
SINGLE PHASE SOLID STATE RELAYS
Main features
• Alternating current solid state relay
• Zero crossing switching
• Copper/semiconductor coupling
technology
• 15, 25, 50 and 90Arms nominal
current
• Non-repetitive voltage: up to
1600Vp
• Nominal Voltage: up to 600 Vac
• Control voltage : 3...32Vcc and
20...260Vac/Vcc with connector
• Isolation ((input-output)
4000Vrms
• RedLEDdriveactivesignal
• InternalMOV(option)
Main applications
• PackagingMachinery
• Thermoforming
• Plastic extrusion lines
• Industrial ovens and
furnaces
• Control application with
high switching speed
PROFILE
Zero crossing relay with antiparallel thy-
ristor output is the most used solid state
relay in industrial applications.
In fact, it can be used for resistive, inducti-
ve and capacity loads.
“Zero crossing” relay is energised when
voltage meets the zero point and disener-
gised when current meets the zero point,
depending on the signal control on the
input circuit.
This relay has been designed to stand
high-value transitory applications .
When the relay has to stand high currents
for a long period, it is necessary to grant a
proper dissipation and an adequate elec-
trical connection between relay terminals
and the load.
Varistors, fuses, thermostats and fans are
available as fittings.
Use the relay with an opportune heatsink
(see section accessories).
TECHNICAL DATA
General features
Rated frequency: 45...65Hz
Activation time:
GQ...-D- ≤1/2 cicle GQ...-A- ≤1 cicle
Deactivation time:
GQ...-D- ≤1/2 cicle GQ...-A- ≤1 cicle
Power factor: ≥0,5
Protection level: IP20
• Uimp = 4,8KV
• Ui = 660V
• Overload current profile = 10
• Conditional short circuit current = 5KA with
type 1 coordination and respective fuse protec-
tions.
GQ15/25 fuse type aM6A
GQ50 fuse type aM16A
GQ90 fuse type aM20A
GQ...- 24-
Nominal voltage: 24...230 Vac
(max range 20...253Vac)
Non-repetitive voltage: ≥ 600 Vp
Zero switching voltage: ≤ 20V
GQ...- 48-
Nominal voltage: 48...480 Vac
(max range 40...528Vac)
Non-repetitive voltage: ≥ 1200 Vp
Zero switching voltage: ≤ 40 V
GQ...- 60-
Nominal voltage: 48...600 Vac
(max range 40...660Vac)
Non-repetitive voltage: ≥ 1200 Vp
Zero switching voltage: ≤ 40V
Control input A1 - A2
GQ...-D-
Control voltage: 3...32Vcc
Turn ON voltage: ≥ 2,7Vc.c
Turn OFF voltage: ≤ 1Vcc
Reverse voltage: < 36Vcc
Consumption: ≤ 13mA@32V
GQ...-A-
Control voltage: 20...260Vac/Vcc
Turn ON voltage: ≥ 15Vac/Vcc
Turn OFF voltage: ≤ 6Vac/Vcc
Consumption: ≤ 8mAac/cc@260Vac/Vcc
Series connection of control inputs:
max. no. GQ...-A in series = Vcontrol
-10% / 20
Output L1 - T1
GQ - 15 -
Nominal current :
AC51: 15Arms; AC53A (*): 3Arms
Min load current: 0,1Arms
Repetitive overcurrent t=1 s: ≤ 35Arms
Non-repetitive overcurrent t=20ms:200Ap

DIMENSIONS
Dimensions in mm, (inc) (*) See installation notes
*Apply thermoconductive
paste
Raise the guard to access the
fastening hole or the terminals
Current drop at nominal voltage and frequencies:
≤ 8mArms
I2t for fusing t=1-10ms: ≤ 200A2s
Critical dl/dt: ≥ 100A/µs
Voltage drop at nominal current: ≤1,45Vrms
Critical dV/dt off-state: ≥ 1000V/µs
Ith = 15A
GQ - 25 -
Nominal current :
AC51: 25Arms; AC53A (*): 5Arms
Min load current: 0,3Arms
Repetitive overcurrent t=1 s: ≤ 60Arms
Non-repetitive overcurrent t=20ms: 300Ap
Current drop at nominal voltage and frequencies:
≤ 8 mArms
I2t for fusing t=1-10ms: ≤ 450A2s
Critical dl/dt: ≥ 100A/µs
Voltage drop at nominal current: ≤ 1,45Vrms
Critical dV/dt off-state:≥ 1000V/µs
Ith = 25A
GQ - 50 -
Nominal current :
AC51: 50Arms; AC53A (*): 15Arms
Min load current: 0,3Arms
Repetitive overcurrent t=1 s: ≤ 125Arms
Non-repetitive overcurrent t=20ms: 600Ap
Current drop at nominal voltage and frequencies:
≤ 8mArms
I2t for fusing t=1-10ms: ≤ 1800A2s
Critical dl/dt: ≥ 100A/µs
Voltage drop at nominal current: ≤1,35Vrms
Critical dV/dt off-state: ≥ 1000V/µs
Ith = 50A
GQ - 50B -
(with high I2t fusing current)
Nominal current :
AC51: 50Arms; AC53A (*): 18Arms
Min load current: 0,4Arms
Repetitive overcurrent t=1 s: ≤ 140Arms
Non-repetitive overcurrent t=20ms: 1150Ap
Current drop at nominal voltage and frequencies:
≤ 10mArms
I2t for fusing t=1-10ms: ≤ 6600A2s
Critical dl/dt: ≥ 100A/µs
Voltage drop at nominal current: ≤1,2Vrms
Critical dV/dt off-state: ≥ 1000V/µs
Ith = 50A
GQ - 90 -
Nominal current
AC51: 90Arms; AC53A (*): 20Arms
Min load current: 0,5Arms
Repetitive overcurrent t=1 s: ≤ 150Arms
Non-repetitive overcurrent t=20ms: 1500 Ap
Current drop at nominal voltage and frequencies:
≤ 10mArms
I2t for fusing t=1-10ms: ≤ 11200A2s
Critical dl/dt: ≥ 100A/µs
Voltage drop at nominal current:≤ 1,35Vrms
Critical dV/dt off-state: ≥ 1000V/µs
Ith = 90A
(*) Only versions: GQ-XX-24-X-1
GQ-XX-48-X-1
Insulation
Nominal insulation voltage
Input/output:: ≥ 4000 Vac
Nominal insulation voltage
Output/case: ≥ 2500 Vac
Insulation resistance
Input/output: ≥ 1010Ω
Insulation resistance
Output/case: ≥ 1010Ω
Insulation capacity Input/Output: ≤ 8pF
Insulation capacity Output/case: ≤ 100pF
Ambient conditions
• Ambient temeparure: -25...+80°C
• Storage Temperature: -55...+100°C
• Maximum relative humidity: 50% a 40°C
• Maximum installation height: 2000 slm
• Pollution level: 3
Thermal features
GQ - XX -
Junction Temperature: ≤ 125°C
Rth junction/ambient: ≤ 12 K/W
GQ - 15 - / GQ - 25 -
Rth junction/case: ≤ 1,25 K/W
GQ - 50 -
Rth junction/case: ≤ 0,65 K/W
GQ - 50B -
Rth junction/case: ≤ 0,33 K/W
GQ - 90 -
Rth junction/case: ≤ 0,3 K/W
Solid State Relay Dissipated Power
Calculation
Single phase state relay
Pd GQ .. 15/25 = 1,45 . Irms [W]
Pd GQ .. 50/90 = 1,35 . Irms [W]
Pd GQ .. 50B = 1,2 . Irms [W]
IRMS = single-phase load current
Heatsink Thermal Resistance Calculation
Rth = (90°C - T.amb. max) / Pd
where Pd = dissipated power
Max. amb. T = max air temperature inside the
electrical cabinet.
Use a heatsink with thermal resistance inferior
to the calculated one (Rth).
*
*30.5 (1.2) with option “command signal Terminal” = 4

ELECTRICAL CONNECTIONS
Connection of 3-phase load and 2-phase control Connection of single-phase load
Heatsink (accessory)
Connection of 3-phase load with closed/open triangle or star
Digital
output
on/off
Relay
output
Installation notes
The device must be protected by a high speed
fuse (accessory).
Applications with power solid state relays must
also have a switch to isolate the power line.
Protect the solid state relay against overheating
by using a heatsink (accessory).
The heatsink must be sized according to room
temperature and load current (see technical
data).
Heatsink installation procedure:
spread 1 gram of thermoconductive silicone
paste (we recommend DOW CORNING 340)
on the dissipative metal surfaces of the module.
The surfaces must be clean and the thermocon-
ductive paste must not contain any impurities.
As alternative it is also possible to use the slide
SIL-GQ available as accessory.
Alternately tighten the two fastening screws
until reaching a torque of 0.4…0.6 Nm.
Wait 5 minutes for any excess paste to run off.
Alternately tighten the two fastening screws
until reaching a torque of 1.2…1.4 Nm.
Attention
The contact surface of the heatsink module
may have a maximum planarity error of 0.1 mm
and maximum roughness of 0.02 mm.
The fastening holes on the heatsink must be
threaded and countersunk.
The heatsink must be grounded.

FUSES/ FUSES HOLDER
SECTION CABLEHEATSINK/ THERMAL RESISTANCE
TERMINALS AND LEADS: SPECIFICATIONS
HIGH SPEED FUSES FUSE HOLDER
Model Size
I2T
Code
Format
Model
Code
Dissipated
power @ In
Model Code
Approval
Max power
dissipated
Max continuative
current
GQ15... 16A
150A2S
FUS-016
10x38
FWC16A10F
338470 3,5W PFI-10x38
337134
UR 30A@690V
3W
13A
GQ25...
25A
390A2S
FUS-025
10x38
FWC25A10F
338474 6W 13A
375A2SFUS-026
14x51
FWC25A14F
338130 7W PFI-14x51
337503
UR 50A@600V
5W
18A
GQ50...
50A
1800A2S
FUS-051
14x51
FWC50A14F
338079 9W 27A
50A
1600A2S
FUS-050
22x58
FWC50A22F
338127 9,5W
PFI-22x58
337223
UR 80A@600V
9,5W
50A
GQ90...
80A
6600A2S
FUS-080
22x58
FWP80A22F
338199 14W 50A
100A
12500A2S
FUS-100
22X58
FWP100A22F
338478 16W 60A
Model GEFRAN HEATSINK
(see accessories)
THERMAL
RESISTANCE
GQ15...
GQ25...
DIS 25GD
DIS 50G
Rth ≥ 2,8 K/W
Rth ≥ 0,83 K/W
GQ50... DIS 50G Rth ≥ 0,83 K/W
GQ90... DIS 90G Rth ≥ 0,56 K/W
Data relating to 40°C ambient temperature, heatsink in vertical position with
15 cm of free air above and below.
Model Section
GQ15... 2,5mm2
GQ25... 6mm2
GQ50... 12mm2
GQ90... 25mm2
Minimum allowed rated section based on the rated currents of
the power solid state relays, for copper leads isolated in PVC in
continuous use and at room temperature of 40°C, according to
standards CEI 44-5, CEI 17-11, IEC 408 pursuant to standard
EN60204-1.
Power terminals in compliance with standard EN60947-1
Description Power terminals
1-L1 2-T2 Extractable 2 poles command terminals 3-A1 / 4-A2
Terminal type
screw (M4)
contact area
(LxP) 13x11mm
with self-locking
spring
MORS1
with spring
double connection
MORS2
with screw M3
MORS3
with screw M2.5
MORS4
Stripped
wire
1x2.5...6mm2
2x1.5...2.5mm2
2x2.5...6mm2
Stripped 11mm
1x0.2...2.5mm2
2x0.5...0.75mm2 (#)
Stripped 10mm
2x(1x0.2...2.5mm2)
2x(2x0.2...0.75mm2)(#)
Stripped 10mm
1x0.25...2.5mm2
2x0.25...1mm2 (#)
Stripped 7mm
1x0.5...1.5mm2
Stripped 6mm
Prod
cable
1x1.5...6mm2
2x1.5...2.5mm2
2x2.5...6mm2
1x0.2...1.5mm2
2x0.2...0.75mm2 (#)
2x(1x0.25...2.5mm2)
2x(2x0.25...0.75mm2)
(#)
1x0.25...2.5mm2
2x0.25...1mm2 (#) ---
Prod cable
with collar
1x1.5...10mm2
2x1.5...2.5mm2
2x2.5...6mm2
1x0.2...1.5mm21x0.25...1.5mm21x0.25...2.5mm2
2x0.25...1.5mm2 (#) ---
Fork or eyelet cable 1x2.5...25mm2--- --- --- ---
Locking torque
/
screwdriver type
slot 1x5...6mm
cross ø 5...6mm
2...2,4Nm
with slot 0,6x3,5mm
for contact opening
thrust
with slot 0,6x3,5mm
for contact opening
thrust (with flexible
stripped cable)
with slot 0,6x3,5mm
with cross ø 3...3,8mm
0,5...0,6Nm
with slot
0.6x3.5mm 0.4Nm
(#) When inserting two leads in the same termi-
nal they must have the same cross-section
Note: The minimum and maximum sections
shown refer to unipolar copper wires isolated
in PVC.

REFERENCE NORMS
EMC Emission
EN 61000-6-4 Emissions conducted at radiofrequency Class A (Industrial devices)
EN 61000-6-4 Emissions irradiated at radiofrequency Class A (Industrial devices)
The product is designed for type A environments. Use of the product in type B environments may cause undesired electromagnetic
noise. In this case, the user should take appropriate steps for improvement.
EMC Immunity
EN 61000-6-2 Immunity for industrial environments
EN 61000-4-2 Electrostatic discharges 4kV by contact; 8 kV in air. Performance criterion 2.
EN 61000-4-6 Electromagnetic field at radiofrequency Test level 3. Performance criterion 1
0,15-80MHz
EN 61000-4-3 Electromagnetic field at radiofrequency Test level 10V/m. Performance criterion 1.
80-1000MHz
EN 61000-4-4 Immunity to burst Test level 2kV/100 KHz. Performance criterion 2.
EN 61000-4-5 Immunity to surge Test level: 2kV (Phase-ground); 1kV (Phase-phase).
Performance criterion 2.
Safety
EN 61010-1 Safety requirements
ORDER CODE
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
GQ
Please, contact GEFRAN sales people for the codes availability.
(*) Version with high I2t fusing current (short-circuit
proof, using a specific magnetothermic switch)
(**) Available only in versions GQ-XX-60-X-1-X
(overloading protection always present)
CONNECTORS
0Without connector
1(MORS1) Two-pin spring
connector,enclosed
2(MORS2) Two-pin double
spring connector, enclo-
sed
3(MORS3) Two-pin screw
connector, enclosed
4(MORS4) Two-pin screw
connector, low profile
enclosed
OVERVOLTAGE PROTECTION
0External
1Internal
CONTROL VOLTAGE
D3...32Vc.c.
A20...260Vac/Vcc
NOMINAL CURRENT
15ACArms 15
25ACArms 25
50ACArms 50
50ACArms (*) 50B
90ACArms 90
NOMINAL VOLTAGE
230VACrms 24
480VACrms 48
600VACrms (**) 60
MODEL
GQ

WARNING: this symbol indicates danger.
Before installation, please read the following advices:
• follow the indications of the manual scrupulously when making the connections to the instrument.
• use a cable that is suitable for the ratings of voltage and current indicated in the technical specifications.
• if the instrument is used in applications where there is risk of injury to persons and damage to machines or materials, it is essen-
tial that it is used with an auxiliary alarm device.
It is advisable to verify frequently that the alarm device is functional even during the normal operation of the equipment.
• The instrument must NOT be used in environments where there could be the presence of dangerous atmospheres (inflammable
or explosive).
• During continuous operation, the heatsink may reach 100°C and remain at a high temperature due to thermal inertia even after
the device is switched off. Therefore, DO NOT touch the heat sink or the electrical wires.
• do not operate on the power circuit untless the main supply is disconnected.
• DO NOT open the cover if device is “ON”!
(use the holes in the cover for eventual re-calibration).
Installation:
• connect the device to the ground using the proper ground terminal.
• the power supply wiring must be kept separate from that of inputs and outputs of the instrument; always check that the supply
voltage corresponds to that indicated on the instrument cover.
• evitare la polvere, l’ umidità, i gas corrosivi, le fonti di calore.
• keep away from dust, humidity, corrosive gases and heat sources.
• The connection cable must be shorter than 3 meters if the current transformer is used.
Maintenance: Check the correct operation of the cooling fans at regular intervals; clean the ventilation air filters of the installation
at regular intervals.
• Repairs must be performed only by specialized or appropriately trained personnel. Cut off power to the device before accessing
internal parts.
• Do not clean the box with solvents derived from hydrocarbons (trichloroethylene, gasoline, etc.). Using such solvents will compro-
mise the mechanical reliability of the device. To clean external plastic parts, use a clean cloth wet with ethyl alcohol or water.
Technical service : GEFRAN has a technical service department. Defects caused by use not conforming to the instructions are exclu-
ded from the warranty.
•WARNINGS
GEFRAN spa
via Sebina, 74 - 25050 Provaglio d’Iseo (BS)
Tel. +39 030 9888.1 - fax +39 030 9839063 Internet: http://www.gefran.com DTS_GQ_12-2012_ENG
In conformity to ECC 2004/108/CE and 2006/95/CE and following modification with reference to standard EN 60947-4-2 (Low voltage
equipment - AC Semiconductor starters and contactors)
“
In Conformity with UL508 - File: E243386
This manual suits for next models
3
Table of contents
Other gefran Relay manuals

gefran
gefran GQ Series User manual

gefran
gefran GTT 25/230 User manual

gefran
gefran GT 25 User manual

gefran
gefran GS User manual

gefran
gefran GTS User manual

gefran
gefran GTS User manual

gefran
gefran GTZ 25 Series Instruction manual

gefran
gefran GRP-H15A Owner's manual

gefran
gefran GTZ 25 Quick start guide

gefran
gefran GTS-T 10/230 User manual
Popular Relay manuals by other brands

Helo
Helo WE 5 product manual

Wieland
Wieland SNV 4274SL Translation of the original instructions

Sterling Power Products
Sterling Power Products Pro Latch R 80 instructions

BERNSTEIN
BERNSTEIN SCR ON4-W22-3.6-S Installation and operating instructions

SPEL
SPEL Smart4house RE-00 Series Installation and operating instructions

ABB
ABB CO manual