Alarm system JA-65 MAESTRO - 9 - MFM51210
•The keypad will display a "P", confirming that the system is in the programming mode (for system setting, enrollment of
wireless items and for testing).
Note: if „P“ is not displayed, the control panel is not in the factory default setting. Perform a Factory default reset. (See section 17).
12. Control panel programming
Functions of the system can be customized. The most convenient programming method is via a connected PC using the Comlink
software (see 19). Programming can also be performed by entering programming sequences from the system keypad while in the
programming mode:
•If the control panel is not in the programming mode, open it (entering F 0 SC - SC = Service Code, factory default SC=6060) –
The programming mode will be indicated by a „P“ on the LED display. This mode can only be entered when the panel is
disarmed. In this mode, no alarm can be triggered. Detectors and other accessories can be enrolled, the system parameters
can be set up and the system can be tested.
•The parameters of the control panel can be set by entering programming sequences from the keypad. Any unfinished
programming sequence can be terminated by pressing the Nkey.
•To exit the programming mode, press the N key („P“ will turn off). If any fault is indicated when you try to exit the
programming mode, the control panel will inform you of the problem (see programming sequence 39x for more details).
List of control panel programmable parameters
Function sequence options factory d. note
Enrolling of detectors and controllers 1 1& 7scroll, 2 erase pos., 3
controllers, 4 all - w. Rmodule only
Hard-wired zone input setting 60 nn xyz nn– zone n., x– triggering,
y– reaction, s- section all off w. Hmodule only
Exit / Entrance delay 21x x= 1 to 9 (x 10sec.) 30sec.
Alarm duration 22x x = 1 to 8 (min.), 0=10s, 9=15min 4min.
Function of PgX output 23x x= 0 to 8 (0-Chime, 1-Fire, 2-
Arm, 3-Panik, 4-Alarm, 5-Door,
6-Home, 7-No AC, 8-Phone
Chime split system has
different setting
Function of PgY output 24x x= 0 to 8 (0-Chime, 1-Fire, 2-
Arm, 3-Panik, 4-Alarm, 5-Door,
6-Home, 7-No AC, 8-Phone
Arm split system has
different setting
Voice m. & tel. Numbers editable in the user mode 25x 251 = YES 250 = NO NO w. Xmodule only
Radio signal jamming regular testing 26x 261 = YES 260 = NO NO w. Rmodule only
Regular communication check enabled 27x 271 = YES 270 = NO NE w. Rmodule only
RESET enabled 28x 281 = YES 280 = NO YES
Subsystem arming enrollment 290 will enroll to sub-control panel as wireless controller w. Rmodule only
Control panel enrollment to a UC-2xx, subsystem,... 299 will send enrolling signal w. Rmodule only
No code requested (effects , , , F4, F8 & F9) 30x 301 = YES 300 = NO YES
Partial (Home) arming enabled ( ) 31x 311 = YES 310 = NO YES
Siren alarm enabled 32x 321 = YES 320 = NO YES
Exit delay audible indication enabled 33x 331 = YES 330 = NO YES
Partial arming exit delay audible indication 34x 341 = YES 340 = NO NO
Entrance delay audible indication enabled 35x 351 = YES 350 = NO YES
Arming & disarming chirp sounds enabled 36x 361 = YES 360 = NO NO
Siren in Disarm & Partial arming enabled 37x 371 = YES 370 = NO YES
Wireless siren alarm enabled 38x 381 = YES 380 = NO YES w. Rmodule only
Indication of system problems when arming 39x 391 = YES 390 = NO NO
Split control panel (A, B & C sections) 690x 6901 = YES 6900 = N0 NO
Only first source of alarm is recorded 691x 6901 = YES 6910 = NO NO
Alarm triggered by opened zone when arming 692x 6921 = YES 6920 = NO NO only if 391
Addressing of wireless controllers to sections 63 nns nn– controller n., s- section all A split & R module
Automatic arming/disarming setting 64nahhmm n- 0-9, a-action #, hh-hours,
mm-min. all off split & partial
arming see 12.21
New Service Code setting 5 nSC nSC nSC = new Service Code 6060 enter code twice
Real time and date setting 4 hh mm DD MM RR 00 00 01 01 00
User Mode entering 6999 Switching to the User mode -