KNX Sensoren
Art.-no.: WS 10 D, WS 10 T, WS 10 H
Terminal designations:
+UB: operating voltage 24 V DC
GND: reference potential (ground) non-earthed
OUT: output 0 – 10 V
4. Fitting instructions
•The sensors must be installed in an accessible place to permit
necessary cleaning, if needed.
•Do not install the sensors in the vicinity of RF transmitters (e.g.
cellular radio transmitters).
•Do not lay sensor cables parallel to mains or other electrically loaded
lines. To prevent EMC problems, there should be a distance of a few
centimeters between these lines and the sensor cable.
•Make sure the sensors are perfectly adjusted (e.g. pointing in the
right direction) as the measured values might otherwise be incorrect.
5. Technical Data
General
Supply voltage : 24 V DC (15 - 30 V DC)
Connecting terminals : screw-type terminals,, max. 2,5 mm²
Connecting cable: through screwed conduit entry no. 7
Recommended cable: 3 x 0,25 mm²
Length of cable: max. 100 m
(observe installation ínstructions)
Voltage output : 0...10 V DC
(into a load of at least 1 kΩ, shortcircuit
protected)
Ambient temperature : - 30 to + 70 °C
Type of protection: IP 65
Mounting position : optional
recommend:
Type of fastening: screw fastening
Dimensions : 58 x 90 x 35 mm
2