KeContact P30 – Charging station
Quick Installation Guide
KEBA AG
Gewerbepark Urfahr
4041 Linz, Austria
+43 732 7090
www.keba.com
Translation of the original manual:
en, V 3.12, Nr.: 93481 © KEBA
Specifications are subject to change due to
further technical developments. Details
presented may be subject to correction.
All rights reserved.
The latest manuals are available in the download area
on our website www.keba.com.
1 Safety notes
The safety instructions for the installation and commis-
sioning of the charging station in the supplied manuals
must be read prior to installation or commissioning and
must be observed.
Not observing the safety instructions can result in
risk of death, injuries and damage to the device!
The device manufacturer assumes no liability for result-
ing claims!
WARNING!
Danger due to electric shock and fire hazard!
Installation, commissioning, maintenance or ret-
rofitting of the charging station must be per-
formed by correctly trained, qualified and author-
ized electricians who are fully responsible for the
compliance with existing standards and installa-
tion regulations.
On the right-hand side of the connection area
(X1−X4: Ethernet connections as well as terminals
for enable input and switch contact output) only
voltages and circuits are permitted to be con-
nected which have a safe separation to danger-
ous voltages (for example sufficient insulation).
2 Power supply
Information
The charging station is set to 10 A in the delivery state. In
order to adapt the maximum current to the installed line cir-
cuit breaker, a configuration via the DIP switches is neces-
sary. For details, see DIP switch settings.
The power supply (supply line) must be hardwired to an ex-
isting domestic installation and comply with the applicable
national regulations.
Selection of RCD / fault-current circuit breaker
Each charging station must be connected via a sepa-
rate RCD (Residual Current Device / fault-current circuit
breaker). No other consumers may be connected to this
circuit.
An RCD with at least Type A must be used since all
P30 variants have an internal DC fault current monitor-
ing ≥6 mA.
During installation, other important issues such as "cas-
cading” of RCD and selection of a suitable line circuit
breaker must be considered.
Dimensioning of the line circuit breaker
The nominal current must be determined in accordance
with the type plate data in coordination with the desired
charging power (DIP switch settings for charging current
specification) and the supply line.
I
(DIP switch)
≤I
(circuit breaker)
≤I
(supply line)
≤I
(nominal current)
3 Dismount covers
1) Unscrew the two
screws on the bottom
side of the housing
cover.
2) Lift the housing cover
at bottom max. 1 cm
1and then push up-
wards 2.
3) Loosen the four
screws of the con-
nection panel cover
and remove the con-
nection panel cover
upwards.
4) Loosen the two
screws of the termi-
nal cover and re-
move the terminal
cover upwards.
4 Prepare cable insertion
Place the charging station on a stable surface.
1) Using a hammer and flat-head screwdriver, gently
knock out the required cable insertion openings.
Surface-mounting cable insertion: Cable insertion
openings on the top side
Flush-mounting cable insertion: Cable insertion
openings on the back side
2) Insert the cable glands (surface-mounted cable inser-
tion) or double-membrane seals (flush-mounted cable
insertion) into the corresponding cable insertion open-
ings.
5 Mount charging station
NOTICE!
Property damage due to moisture!
Only a vertical installation of the charging station is
permitted. The charging station must be mounted with
the supplied washers at a 90° angle to the mounting
surface – no inclination is allowed, otherwise water
drainage will not be possible and damage to the device
will result.
1Washer for adjusting 2Rear wall of the
charging station
3Washer for nut 4Nut
5Hanger bolt x
20 mm
1) Mark the 4 holes on the wall using the supplied drilling
template.
2) Drill boreholes and, if necessary, insert anchors in the
holes.
3) Turn the hanger bolts into the hole / anchors until the
thread still protrudes approx. 20 mm x.
4) Pull the cable through the prepared openings on the
charging station. Pay attention to leak tightness!
5) 4 of the supplied washers can be used to compensate
for any unevenness and to ensure proper water flow
behind the device: If necessary, place the washers 1on
the hanger bolts.
6) Position the charging station on the wall and secure it
with the 4 washers 3 and nuts 4to the hanger bolts 5.
6 Connect voltage supply
The charging station can be connected in the following
ways:
1-phase: via terminals L1, N and PE
3-phase: via terminals L1, L2, L3, N and PE
The supply terminals are designed as spring-type termi-
nals. The handling instructions enclosed in the terminal
area must be observed.
The supply line must be sufficiently inserted into the cable
gland or the double-membrane seals so that the cable
sheath 1is visible in the connection area.
1) Shorten the connection wires to the appropriate length
(as short as possible). The protective conductor PE
must be longer than the other conductors!
2) Strip the connection wires to approx. 12 mm. For
stranded wires with fine wires, use wire end sleeves.
3) Insert the flat-head screwdriver (5.5 mm) into the sup-
ply terminal as shown. The screwdriver must rest on
the housing.
4) Press the screwdriver straight into the terminal until the
contact opens completely. The angle of the screwdriver
changes while pressing in.
!