Leviton Intellect ZL070-B00 User manual

• For indoor applications only. DO NOT use outdoors.
• DO NOT use this equipment for other than intended use.
• DO NOT mount near gas or electric heaters.
• Equipment should be mounted in locations and at heights where it will not
be subjected to tampering by unauthorized personnel.
• Use this device with COPPER OR COPPER CLAD WIRE ONLY.
• SAVE THESE INSTRUCTIONS.
Wireless Intelligent Fixture Controller
INSTALLATION INSTRUCTIONS ENGLISH
PK-A3378-10-00-2A-X3
The Intellect™ Wireless Intelligent Fixture Controller integrates wireless
control technology directly into lighting fixtures. The controller is designed
to be installed into the wiring compartment of the fixture and interface
to the driver via 0-10V or DALI, depending on the model. The fixture
controller interfaces with Leviton’s wireless systems using its built-in radio.
The controller is designed to be powered from the driver and in the case
of 0-10V, requires a dim-to-off driver to be used. The controller may be
installed into your fixture by the fixture manufacturer or may be added in
the field if all requirements are met. When the controller is pre-installed on
a fixture, refer to fixture documentation for installation methods, means,
and requirements.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER
at circuit breaker or fuse and test that power is off before wiring!
Installation
1. Secure the controller within the wiring compartment using the included
mounting screws.
2. Remove 4 to 5 mm of insulation from each circuit conductor.
3. Make sure ends of conductor are straight.
4. Push conductor firmly into appropriate wire connector.
5. For controllers with external antenna (ZL070-B0A, B2A,
ZL0D0-B0A): The grommet on the end of the antenna wire is
designed for installation into a 2 mm diameter hole to provide stability
for the antenna wire outside the fixture. Locate a 2 mm hole as
needed on the fixture housing. Thread antenna wire through hole.
Push grommet into hole until secure.
6. If installing with Emergency Sense Module (ZL027-0ES): Connect
the Emergency Sense Module to the Controller using the cable
included with the ZL027-0ES.
7. Connect the Emergency Sense Module to Normal Power.
8. Restore power at circuit breaker or fuse.
9. Proceed to device enrollment per the included sheet and configuration
per your system requirements. Installation is complete.
Installation Requirements
•Installation and servicing should always be performed by qualified
personnel.
•Mounts within fixture wiring compartment.
•Dim-to-OFF LED driver with 12-24V AUX power supply and 0-10V or
DALI control.
Wiring Diagrams
ZL070-B20, B2A
Emergency Wiring
When used for emergency lighting, the ZL027-0ES Emergency Sense
Module is required and shall be connected using the supplied cable.
The control input wires for the emergency light fixture are connected
to emergency power, and the Emergency Sense Module is connected
to normal power. Upon loss of normal power, the relay closes, and the
controller or sensor 0-10V lines go to high impedance allowing the load to
go to full output powered from the EM Source. Commands to change the
device output from full are ignored when the Emergency Sense Module is
in this mode. Upon restoration of normal power, the controller or sensor
will automatically resume normal operation.
Emergency Self-Test: NFPA 101 Life Safety Code and NEC (Article
700.3(B)) requires regular testing of all emergency equipment. To
perform a test of these products, a Test Switch that is a normally open,
momentary-break type, that returns the equipment to normal status when
released can be installed locally to interrupt normal power and perform
emergency system test.
*The diagram below depicts a “Momentary-Break Type Test Switch” ($)
on the normal power line to trigger the emergency systems test. Clarify
requirements with all local authorities.
Intellect™
EMERGENCY
SENSOR
MODULE
ZL027-0ES
FIXTURE
LIGHT FIXTURE
EMERGENCY
POWER
LIGHTING CIRCUI
T
LINE FEED
(NORMAL POWER)
AUX +
AUX -
VIOLET (DIM +)
GRAY (DIM -)
LINE
LINE
NEUTRAL
NEUTRAL
Controller or
Sensor
12 in. Cable
provided
with
Emergency
Sensor Module
$*
NL
LN
Neutral
Line
2-Channel
LED Driver
With Auxiliary
Power Output
GNDEarth
(-) LED-2
TO CH-2
LED Modules
TO CH-1
LED Modules
(+) LED-2
(-) LED-1
(+) LED-1
(+) AUX
(-) AUX
(+) DIM-1
AUX+
AUX-
DIM1+
DIM2+
DIM-
(-) DIM-1
(-) CCT-2
(+) CCT-2
NL
LN
Neutral
Line 1-Channel
LED Driver
With Auxiliary
Power Output
GNDEarth
(-) LED
(+) LED
(+) AUX AUX+
AUX-
DIM1+
DIM-
(-) AUX
(+) DIM
(-) DIM
WC, 0-10V, DALI
Cat. Nos. ZL070-B00, B0A; ZL070-B20, B2A; ZL0D0-B00, B0A
NL
LN
Neutral
Line
DALI
LED Driver
GNDEarth
(-) LED
(+) LED
(+) DALI
(-) DALI
DALI+
DALI-
ZL0D0-B00, B0A
Reset
Switch
LED Indicator
ZL070
Reset
Switch
LED Indicator
ZL0D0
ZL070-B00, B0A
WARNINGS
•
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
• TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER OR
FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• Controller is intended to be installed by the fixture manufacturer, but in some cases may be
installed in the field. Field installation must use approved electrical enclosures.
NOTE: Suitable for use in air handling spaces (plenums).
• The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition.
Product Description
NOTE: Antenna applies to B0A and B2A models only.

© 2021 Leviton Mfg. Co., Inc.
LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in
materials and workmanship under normal and proper use for two years from the purchase date. Leviton’s only obligation is to correct such defects by repair or
replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of
this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered
in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of
any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of
any such implied warranty, including merchantability and fitness for a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect,
special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to
perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call: 1-800-824-3005 (U.S. Only) or 1-800-405-5320 (Canada Only) www.leviton.com
INDICATOR LIGHT DESCRIPTIONS
LED Action / Definition
No activity Enrolled in network/
normal operation
Slow blink GREEN Searching for network
Rapid blink BLUE 2X, pause, repeat Bluetooth connection active
Solid BLUE Emergency sense input active
Blink GREEN 4X per second Software update in progress
1X blink AMBER
(Enrolled in Zigbee network) Status (press reset less than
5 sec.)
2X blink AMBER
(Enrolled in Zigbee network,
incorrectly commissioned)
Status (press reset less than
5 sec.)
Blink WHITE 4X per second Factory reset (press reset more
than 5 seconds)
Factory Default (Out-of-the-Box) Operation:
• At first power-up or after factory reset, the controller will bring the
load to 100% in approximately 1 second and then dim down to 0% in
approximately 1 second.
This process will repeat once and then the load will return to 100%.
• The controller will be in auto-join mode and attempting to connect to a
network.
Test Mode:
• Press and hold the reset button for 1 to 3 seconds to initiate.
• The controller will bring the load down to 0% within 1 second and back
up to 100% within 1 second and then repeat once.
• The controller will then return to normal operation.
Factory Reset:
• Press and hold the reset button; LED will turn WHITE.
• Release reset button after at least 5 seconds, but no longer than 10
seconds.
• LED will blink WHITE 4 times per second until reset completes.
Changes to Default Operation:
• System must be configured. See "Configuration" section.
Operation
Configuration
1. System Configuration may be refined using the Leviton GreenMAX
DRC application, downloadable from Google Play™ or the Apple
Store®, using any Bluetooth™ enabled Android™ or iOS Device. Use
the application to:
a. Manually add/remove fixtures from the room.
b. Add additional keypads to the room.
c. Change sensor parameters like sensitivity, timeout, and target light
level.
d. Create user-defined groups of fixtures.
e. Define scenes (meeting, presentation, lunch, dinner, test, etc.).
2. For additional Information about Leviton’s Intellect enabled products
including information about installation, use case diagrams, solution
sheets, and other related products, please visit www.Leviton.com/
intellect.
SPECIFICATIONS
Catalog Numbers ZL070-B00,
B20, B0A, B2A ZL0D0-B00,
B0A
Input Rating 12-24VDC DALI
Control Output 0-10V, 5mA
sinking DALI
Operating Temperature 32°F to 185°F (0°C to 85°C)
Storage Temperature -4°F to 185°F (-20°C to 85°C)
Mounting Fixture wiring compartment
IP Rating IP20
Purpose of Control Energy Management Equipment
Action Control Type 1
Pollution Degree 2
Impulse Voltage 800V
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention of the Quality
Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
FCC SUPPLIERS DECLARATION OF CONFORMITY
Manufactured by Leviton Manufacturing, Inc., 201 N Service Road, Melville, NY, http://www.Leviton.com. This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference
that may cause undesired operation.
FCC STATEMENT
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
RF EXPOSURE AND CO-LOCATION
To ensure compliance with FCC’s and ISED Canada’s RF exposure requirements, this device must be installed to provide a minimum of 20 cm. between the device and
people. This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
Trademark Disclaimer
Intellect is the trademark of Leviton, registered in the United States, Canada, Mexico and the UK. The Leviton logo is a registered trademark of Leviton Manufacturing Co.,
Inc. Google Play and Android are trademarks of Google, LLC. The App Store is a registered trademark of Apple, Inc. Bluetooth is a trademark of Bluetooth SIG, Inc. Use
herein of other third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their
respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement. No part of this document may be reproduced, transmitted or transcribed without the
express written permission of Leviton Manufacturing Co., Inc.
IC Statement
This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s license-exempt RSS(s). Operation
is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to operate the equipment.
This manual suits for next models
6
Table of contents
Other Leviton Home Automation manuals

Leviton
Leviton smartlockpro GFCI Manual

Leviton
Leviton 5480 User manual

Leviton
Leviton WSG15-0DZ User manual

Leviton
Leviton TWR20-W User manual

Leviton
Leviton 35249 User manual

Leviton
Leviton 35249 User manual

Leviton
Leviton ZLD1Z-I0W User manual

Leviton
Leviton ODCØP-S0W User manual

Leviton
Leviton Decora Smart DG15S User manual

Leviton
Leviton IUM1H User manual