Installation og opstart / Installation and start-up instructions
Specifications subject to change without prior notice. It is the responsibility of the product user to
determine the suitability of the products for a specific application. LINAK Danmark will at point of
delivery replace/repair defective products covered by the warranty if promptly returned
to LINAK Danmark. No liability is assumed beyond such replacement/repair.
Installation:
Monter aktuator og motorstyring efter anvisningerne fra
leverandøren af ventillationsanlægget.
Tilslut den anvendte aktuator og indstil DIP-switche og
jumper i henhold til skemaet på foregående side.
Tilslut forsyningsspænding på 230 VAC +/- 10%. LINAK
anbefaler at der monteres en forsyningsadskiller foran
motorstyringen.
Tilslut batteriet til styringen.
Opstart:
Første gang styringen tilsluttes forsyningsspænding og
batteri, kan alarmen for lav batterispænding blive aktiveret.
Alarmen forsvinder efter en tid når batteriet er ladet til-
strækkeligt af den indbyggede batterilader.
LA12 og LA35 med Hall-pot tilbagemelding, starter en
automatisk nulstillingsprocedure hver gang styringen for-
synes med spænding. Dette kan tage op til ere minutter
indtil aktuatoren er kørt helt ind. Den gule lysdiode blinker
under hele proceduren.
Drift:
Ved normal drift, lyser GRØN lysdiode i låget. Når aktua-
toren kører, lyser GUL lysdiode. Styringen går i dvaletil-
stand efter 60 min. uden forsyning. Ingen diode lyser.
Fejl indikation:
Fejl i styringen vises med forskellige typer af blink i den
grønne lysdiode:
1 kort blink ingen 230VAC forsyning
Kontroller og lslut 230VAC
2 korte blink baerifejl
3 korte blink kontrolsignal under 1 volt
Kontroller signal fra styreenhed
4 korte blink arudt på max. strøm
Fjern overbelastning og kør aktuator i modsat retning
5 korte blink ingen lbagemelding fra aktuator
Kontroller signal fra aktuator
Installation:
Install the actuator and motor control as instructed by the
supplier of the ventilation system.
Connect the actuator used and set DIP switches and jumper
in accordance with the diagram on the previous page.
Connect the power supply of 230 VAC +/- 10%. LINAK recom-
mends the installation of an isolator switch before the motor
control.
Connect the battery to the control.
Start-up:
The rst time that the control is connected to the power sup-
ply and battery, the low battery voltage alarm may be activa-
ted. The alarm will stop after a time, when the battery has
been suciently charged by the built-in battery charger.
LA12 and LA35 with Hallpot report start an automatic reset
procedure every time power is connected to the control.
This can take up to several minutes, until the actuator is run
right in. The yellow light ashes during this procedure.
Operation:
On normal operation, the GREEN light diode will light up in
the cover. When the actuator is running, the YELLOW light
diode will light up. The control unit will enter sleep mode after
60 mins with no power connected. All diodes will be switched o
Error indication:
Control errors are displayed as dierent types of ashes of
the green light diode:
Control and connect 230VAC
control signal below 1 volt
Control the signal from the control unit
4 short flashes interrupted at maximum power
Remove overload and run actuator in the opposite
direcon
Control the signal from the actuator
For yderligere vejledning, henvises til brugsanvisningen
på www.linakthirdparty.com
For detailed instructions please refer to the Instruction
manual at www.linakthirdparty.com
Produceret af / Produced by Electromen OY
Installation:
Montera ställdon och motorstyrning enligt teknikerns
rekommendationer.
Ställ in DIP switchar och jumper samt anslut ställdon enligt
ovanstående schema.
Anslut 230 VAC +/-10%. En arbetsbrytare rekommenderas före
motorstyrningen.
Anslut batteriet.
Uppstart:
Första gången styrningen ansluts till nätspänning och batteri kan
larmet för låg batterispänning aktiveras, vilket försvinner igen efter
en stund, då batteriet är uppladdat.
LA12 och LA 35 med Hall-pot lägesrapportering, startar en
automatisk nollställningsprocedur varje gång styrning ansluts till
nätspänning, vilket tar några minuter. Den gula lysdioden blinkar
under hela proceduren.
Drift:
Vid normal drift lyser GRÖN lysdiod i locket. När ställdonet kör lyser
GUL lysdiod. Om ingen förändring gjorts på 60 minuter släcks alla
lysdioder.
Felindikation:
Fel i styrningen visas med koder i den gröna lysdioden:
Felsignal: Fel: Åtgärd:
1 kort blink Ingen 230 VAC försörjning Kontrollera och anslut 230 VAC
2 korta blink Batterifel Byt ut batteriet
3 korta blink Styrsignal under 1 V Kontrollera/justera signalen från styrenheten
4 korta blink Avbrott pga. överbelastning Ta bort orsaken till överbelastningen och kör ställdonet åt andra hållet.
5 korta blink Ingen lägesrapportering från ställdonet. Kontrollera signal från ställdonet